最新消息: USBMI致力于为网友们分享Windows、安卓、IOS等主流手机系统相关的资讯以及评测、同时提供相关教程、应用、软件下载等服务。

HD 235 火灾防护私有有限公司 H3 弹性钢铁防水阀门技术数据说明书_百

IT圈 admin 23浏览 0评论

2024年6月3日发(作者:哈睿博)

DELUGE VALVE MODEL-H3

(DUCTILE IRON)

TECHNICAL DATA

MODEL

NOMINAL SIZE

H3-Ductile Iron ASTM A

536-77 GRADE 65-45-12

200, 150, 100, 80 and 50NB

HD FIRE PROTECT

PVT. LTD.

SERVICE PRESSURE 1.4 to 17.5 Bar

(20 to 250 PSI)

THREADED OPENING BSPT

MOUNTING

FACTORY

HYDROSTATIC

TEST PRESSURE

Vertical or Horizontal

mounting

35 Kg./. (500 PSI)

LISTED

9P76

FLANGE CONNECTION ANSI B 16.5 #150FF

(RF-Optional)

WET PILOT

SPRINKLER

HEIGHT LIMITATION

NET WEIGHT

WITHOUT TRIM

As per graph in the

catalogue

200 NB

150 NB

100 NB

80 NB

50 NB

- 153 Kg

- 79 Kg

- 50 Kg

- 35 Kg

- 32 Kg

pressure detection of fire the top chamber

is vented to atmosphere through the outlet port via

opened actuation devices. The top chamber pressure

cannot be replenished through the restricted inlet

port, and the upward force of the supply pressure

lifts the clapper allowing the water flow to the system

piping network and alarm devices.

TRIM DESCRIPTION

The trims are functionally termed as Dry Pilot Trim,

Wet Pilot Trim, Electric Trim and Test and Alarm Trim

as per the mehod of actuation of the deluge valve.

The functionality of these trims is described below..

FINISH

APPROVAL

ORDERING

INFORMATION

RAL 3000

UL Listed

of valve

specification

trim vertical or

horizontal

type

a)DRY PILOT TRIM (PNEUMATIC RELEASE)

Dry pilot operation uses a pilot line of closed

Sprinkles/QB detectors containing air under

pressure, located in the areato be protected.

It requires regulated dry air supply with main supply

point through restricted orifice. The air pressure

to bemaintained as specified in the catalogue of

Dry Pilot Actuator. The pilot line is connected to air

inlet side of actuator. The top chamber of the

deluge valve is connected to water inlet side of

actuator.

When there is an air pressure drop, or due to

release of any of the release device on detection

of fire, the diaphragm of actuator is lifted and

allows the water to drain. This releases the water

pressure in the top chamber of the deluge valve,

allowing the deluge valve to open and water to flow

into the system piping & alarm devices.

Recommended air supply pressure for dry pilot

trim system is 3.5 kg/.

User must install non return valve at air supply

connection to deluge valve trim.

In dry pilot trim, an actuator (DPA) is provided.

An optional Pneumatic Reset Device (PRD) can

HD 235

DESCRIPTION

Deluge Valve is known as a system control valve in a

deluge system, used for fast application of water in a

spray system. Deluge valve protects areas such as

power transformer installation, storage tank, conveyor

protection and other industrial application etc. With

the addition of foaming agent deluge valve can be used

to protect aircraft hanger and inflammable liquid fire.

VALVE OPERATION

HD Deluge valve is a quick release, hydraulically

operated diaphragm valve. It has three chambers,

isolated from each other by the diaphragm operated

clapper and seat seal. While in SET position, water

pressure is transmitted through an external bypass

check valve and restriction orifice from the system

supply side to the top chamber, so that supply

pressure in the top chamber act across the diaphragm

operated clapper which holds the seat against the

inlet supply pressure because of the differential

NOVEMBER, 2015PAGE 1 OF 16

HD FIRE PROTECT

PVT. LTD.

be provided, which acts as a manual reset device

in the dry pilot line.

TRIM TYPES

The trims are designated as follwing.

W =Wet Pilot trim. D = Dry Pilot Trim

b) WET PILOT TRIM (HYDRAULIC RELEASE)

Wet pilot operation uses a pilot line of closed

Sprinklers/QB detectors containing pressurized

water, supplied through the upstream side of

the Deluge valve, through a restricted orifice. All

the release lines are connected to a common

release line. Due to release of any one of the

release device, the water pressure in the top

chamber of the Deluge valve drops and the Deluge

valve opens.

a) Type ET-W and ET-D

This type of trim is basic trim required to

operate the deluge valve. A solenoid valve for

electric remote actuation and pressure switch

for sensing & announciation are optional.

b) Type ETW-D and ETD-D

This trim type is a combination of components

of the ET trim along with the drip and drain

trim. A solenoid valve for electric remote actuation

and pressure switch for sensing & announciation

are optional.

c) ELECTRIC RELEASE TRIM

To actuate a Deluge valve electrically, a solenoid

valve is provided to drain the water from the top

chamber of the Deluge valve. A pressure switch is

provided to activate an electric alarm, to shut

down the desired equipment or to give “Tripped”

indication of the Deluge valve. In addition to this a

pressure switch can also monitor “Low air

pressure” and “Fire condition” when used in dry

pilot air line.

c) Type ETW-T and ETD-T

This trim type is a combination of components of

the ET trims along with the test and alarm trim.

In dry pilot trim, an actuator DPA-H1 is provided

with optional Pneumatic Reset Device (PRD-1).

A solenoid valve for electric remote actuation

and pressure switch for sensing & announciation

are optional.

d) TEST AND ALARM TRIM

This trim is supplied with a test valve is provided

to test thenormal operation of the sprinkler alarm

bell. The sprinkler alarmcan be supplied additionally,

which bells on actuation of the Deluge valve.

d) Type NT-W and NT-D

This trim type is a combination of components of

the ET trim along with the test and alarm trim

as well as the drip and drain trim. A solenoid valve

for electric remote actuation and pressure switch

for sensing & announciation are optional.

e) DRAIN AND DRIP TRIM

This consists of main and system drain valve in

addition with drip valve.

TRIM

MODEL

NO.

ETW

ETD

ETW-T

ETD-T

ETW-D

ETD-D

NTW

NTD

ETW

ETD

ETW-T

ETD-T

ETW-D

ETD-D

NTW

NTD

TRIM DESCRIPTION

Basic Wet Pilot Trim

Basic Dry Pilot Trim

Basic Wet Pilot Trim with Test & Alarm Trim

Basic Dry Pilot Trim with Test & Alarm Trim

Basic Wet Pilot Trim with Drip & Drain Trim

Basic Dry Pilot Trim with Drip & Drain Trim

Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Wet Pilot Trim

Basic Dry Pilot Trim

Basic Wet Pilot Trim with Test & Alarm Trim

Basic Dry Pilot Trim with Test & Alarm Trim

Basic Wet Pilot Trim with Drip & Drain Trim

Basic Dry Pilot Trim with Drip & Drain Trim

Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

MOUNTINGSCHEMATIC

NO.

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Schematic 1

Schematic 2

Schematic 3

Schematic 4

Schematic 5

Schematic 6

Schematic 7

Schematic 8

Schematic 9

Schematic 10

Schematic 11

Schematic 12

Schematic 13

Schematic 14

Schematic 15

Schematic 16

NOVEMBER, 2015PAGE 2 OF 16HD 235

2024年6月3日发(作者:哈睿博)

DELUGE VALVE MODEL-H3

(DUCTILE IRON)

TECHNICAL DATA

MODEL

NOMINAL SIZE

H3-Ductile Iron ASTM A

536-77 GRADE 65-45-12

200, 150, 100, 80 and 50NB

HD FIRE PROTECT

PVT. LTD.

SERVICE PRESSURE 1.4 to 17.5 Bar

(20 to 250 PSI)

THREADED OPENING BSPT

MOUNTING

FACTORY

HYDROSTATIC

TEST PRESSURE

Vertical or Horizontal

mounting

35 Kg./. (500 PSI)

LISTED

9P76

FLANGE CONNECTION ANSI B 16.5 #150FF

(RF-Optional)

WET PILOT

SPRINKLER

HEIGHT LIMITATION

NET WEIGHT

WITHOUT TRIM

As per graph in the

catalogue

200 NB

150 NB

100 NB

80 NB

50 NB

- 153 Kg

- 79 Kg

- 50 Kg

- 35 Kg

- 32 Kg

pressure detection of fire the top chamber

is vented to atmosphere through the outlet port via

opened actuation devices. The top chamber pressure

cannot be replenished through the restricted inlet

port, and the upward force of the supply pressure

lifts the clapper allowing the water flow to the system

piping network and alarm devices.

TRIM DESCRIPTION

The trims are functionally termed as Dry Pilot Trim,

Wet Pilot Trim, Electric Trim and Test and Alarm Trim

as per the mehod of actuation of the deluge valve.

The functionality of these trims is described below..

FINISH

APPROVAL

ORDERING

INFORMATION

RAL 3000

UL Listed

of valve

specification

trim vertical or

horizontal

type

a)DRY PILOT TRIM (PNEUMATIC RELEASE)

Dry pilot operation uses a pilot line of closed

Sprinkles/QB detectors containing air under

pressure, located in the areato be protected.

It requires regulated dry air supply with main supply

point through restricted orifice. The air pressure

to bemaintained as specified in the catalogue of

Dry Pilot Actuator. The pilot line is connected to air

inlet side of actuator. The top chamber of the

deluge valve is connected to water inlet side of

actuator.

When there is an air pressure drop, or due to

release of any of the release device on detection

of fire, the diaphragm of actuator is lifted and

allows the water to drain. This releases the water

pressure in the top chamber of the deluge valve,

allowing the deluge valve to open and water to flow

into the system piping & alarm devices.

Recommended air supply pressure for dry pilot

trim system is 3.5 kg/.

User must install non return valve at air supply

connection to deluge valve trim.

In dry pilot trim, an actuator (DPA) is provided.

An optional Pneumatic Reset Device (PRD) can

HD 235

DESCRIPTION

Deluge Valve is known as a system control valve in a

deluge system, used for fast application of water in a

spray system. Deluge valve protects areas such as

power transformer installation, storage tank, conveyor

protection and other industrial application etc. With

the addition of foaming agent deluge valve can be used

to protect aircraft hanger and inflammable liquid fire.

VALVE OPERATION

HD Deluge valve is a quick release, hydraulically

operated diaphragm valve. It has three chambers,

isolated from each other by the diaphragm operated

clapper and seat seal. While in SET position, water

pressure is transmitted through an external bypass

check valve and restriction orifice from the system

supply side to the top chamber, so that supply

pressure in the top chamber act across the diaphragm

operated clapper which holds the seat against the

inlet supply pressure because of the differential

NOVEMBER, 2015PAGE 1 OF 16

HD FIRE PROTECT

PVT. LTD.

be provided, which acts as a manual reset device

in the dry pilot line.

TRIM TYPES

The trims are designated as follwing.

W =Wet Pilot trim. D = Dry Pilot Trim

b) WET PILOT TRIM (HYDRAULIC RELEASE)

Wet pilot operation uses a pilot line of closed

Sprinklers/QB detectors containing pressurized

water, supplied through the upstream side of

the Deluge valve, through a restricted orifice. All

the release lines are connected to a common

release line. Due to release of any one of the

release device, the water pressure in the top

chamber of the Deluge valve drops and the Deluge

valve opens.

a) Type ET-W and ET-D

This type of trim is basic trim required to

operate the deluge valve. A solenoid valve for

electric remote actuation and pressure switch

for sensing & announciation are optional.

b) Type ETW-D and ETD-D

This trim type is a combination of components

of the ET trim along with the drip and drain

trim. A solenoid valve for electric remote actuation

and pressure switch for sensing & announciation

are optional.

c) ELECTRIC RELEASE TRIM

To actuate a Deluge valve electrically, a solenoid

valve is provided to drain the water from the top

chamber of the Deluge valve. A pressure switch is

provided to activate an electric alarm, to shut

down the desired equipment or to give “Tripped”

indication of the Deluge valve. In addition to this a

pressure switch can also monitor “Low air

pressure” and “Fire condition” when used in dry

pilot air line.

c) Type ETW-T and ETD-T

This trim type is a combination of components of

the ET trims along with the test and alarm trim.

In dry pilot trim, an actuator DPA-H1 is provided

with optional Pneumatic Reset Device (PRD-1).

A solenoid valve for electric remote actuation

and pressure switch for sensing & announciation

are optional.

d) TEST AND ALARM TRIM

This trim is supplied with a test valve is provided

to test thenormal operation of the sprinkler alarm

bell. The sprinkler alarmcan be supplied additionally,

which bells on actuation of the Deluge valve.

d) Type NT-W and NT-D

This trim type is a combination of components of

the ET trim along with the test and alarm trim

as well as the drip and drain trim. A solenoid valve

for electric remote actuation and pressure switch

for sensing & announciation are optional.

e) DRAIN AND DRIP TRIM

This consists of main and system drain valve in

addition with drip valve.

TRIM

MODEL

NO.

ETW

ETD

ETW-T

ETD-T

ETW-D

ETD-D

NTW

NTD

ETW

ETD

ETW-T

ETD-T

ETW-D

ETD-D

NTW

NTD

TRIM DESCRIPTION

Basic Wet Pilot Trim

Basic Dry Pilot Trim

Basic Wet Pilot Trim with Test & Alarm Trim

Basic Dry Pilot Trim with Test & Alarm Trim

Basic Wet Pilot Trim with Drip & Drain Trim

Basic Dry Pilot Trim with Drip & Drain Trim

Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Wet Pilot Trim

Basic Dry Pilot Trim

Basic Wet Pilot Trim with Test & Alarm Trim

Basic Dry Pilot Trim with Test & Alarm Trim

Basic Wet Pilot Trim with Drip & Drain Trim

Basic Dry Pilot Trim with Drip & Drain Trim

Basic Wet Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

Basic Dry Pilot Trim with Test & Alarm Trim and Drip & Drain Trim

MOUNTINGSCHEMATIC

NO.

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Vertical

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Horizontal

Schematic 1

Schematic 2

Schematic 3

Schematic 4

Schematic 5

Schematic 6

Schematic 7

Schematic 8

Schematic 9

Schematic 10

Schematic 11

Schematic 12

Schematic 13

Schematic 14

Schematic 15

Schematic 16

NOVEMBER, 2015PAGE 2 OF 16HD 235

发布评论

评论列表 (0)

  1. 暂无评论