2024年8月28日发(作者:拱丰)
HV9000
3.1
Standard Application
Analog output function
See
table “Group 3, output and
supervision
page l-8.
parameters” on the
Page 1-15
I
%
t
Unfiltered signal
3.2
Analog output filter time
Filters the analog output signal.
See figure 1.58.
-I
Par.
3.
2
Figure 1.5-8 Analog output filtering.
3.3
Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
See figure 1.5-9
Figure 1.59
Analog oofput invert.
3.4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4
mA. See figure
1.510.
3.5
Analog output scale
Scaling factor for analog output.
See figure 1.5-l 0.
Max. speed (n,xf,,Jf,)
Figure 1.510 Analog output scale.
q
3.6
3.7
3.8
Page 1-16
Standard Application
HV9000
Digital output function
Relay output 1 function
Relay output 2 function
Setting value
0 = Not used
Signal content
Out of operation
Diaital outout DO1 sinks current and oroarammable
relav fR01, R02) is activated when:
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
6 = Warning
9 = Reversed
1 O= Multi-step speed selected
1 1 = At speed
12= Motor regulator activated
13= Output frequency superwsion
14= Control from I10 terminals
The drive is ready to operate
The drive operates
A fault trip has occurred
A fault trip has occurred
The heat-sink temperature exceeds +7O”C
Fault or warning depending on parameter 7. 2
Fault or warning depending on parameter 7. 1
-
if analog reference is 4-20 mA and signal IS <4mA
Always if a warning exists
The reverse command has been selected
A multi-step speed has been selected
The output frequency has reached the set reference
Overvoltage or overcurrent regulator was activated
The output frequency goes outside of the set super-
vision low limit/ high limit (par. 3. 9 and 3. 10)
Ext. control mode selected with progr. push-button #2
Tab/e 1.5-Z Output signals via DO 1 and output relays RO 1 and ROZ.
3.9
Output frequency limit supervision function
0 = No supervision
1 = Low limit supervision
2 =
High limit supervision
If the output frequency goes under/over the set limit (3. 10) this function generates
a warning message via the digital output DO1 and via a relay output ROl or RO2
depending on the settings of the parameters 3.6-3.8.
3.10
Output frequency limit supervision value
The frequency value to be supervised by the parameter 3. 9.
See figure 1.511.
fW1
par3,,0 ..~~~~~~~~~ ,~~~.__.._,_
Par. 3.9 = 2
‘/- *
Example: B ‘B &’
Figure 1.577
Output frequency supervision.
HV9000
4.1
4.2
Standard Application
Page 1-17
AcclDec ramp 1 shape
Acc/Dec ramp 2 shape
The acceleration
parameters.
and deceleration ramp shape can be programmed with these
L
Setting the value = 0 gives you a linear ramp shape. The output frequency
immediately follows the input with a ramp time set by parameters 1.3, 1.4 (4.3,4.
4 for Acc/Dec. time 2).
Setting 0.1-l 0 seconds for 4. 1
(4.2) causes an S-shaped ramp.
The speed changes are smooth.
Parameter 1. 3/ 1. 4 (4. 3/ 4. 4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure 1.5-
12.
f
WI
t
,’
I’
1
1.3,1.4 _
(4.3,4.4)
~
~
I
:t,i
4. 1 (4. 2)
/
I I
‘t):
I
4. 1 (4.2)
Id
"0009K20
-rgure is-12
S-shapedacceleratron/
deceleration.
4.3
4.4
Acceleration time 2
Deceleration time 2
These values correspond to the time required for the output frequency to change
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possibile to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2.2.
4.5
Brake chopper
0 = No
brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor, the energy stored in the inertia of the
motor and the load is fed into the external brake resistor. If the brake resistor is
selected correctly the drive is able to decelerate the load with a torque equal to
that of acceleration. See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may extend the
acceleration times).
Page 1-18
Standard Application
Flying start:
1
HV9090
The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7 Stop
function
Coasting:
0 The motor coasts to an uncontrolled
Stop command is issued.
stop with the HV9000 off, after the
Ramp:
1 After the Stop command is issued, the speed of the motor is decelerated
based on the deceleration ramp time parameter.
If the regenerated energy is high, it may be necessary to use an external
braking resistor for faster deceleration.
current
4.8
DC braking
Defines the current injected into the motor during DC braking.
4.9
DC braking time at stop
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4.7. See figure 1.5-13.
0
ro
DC-brake is not used
DC-brake is in use depending on the setup of the stop function
(param. 4. 7). The time is set by the value of parameter 4. 9:
= 0 (coasting): Stop-function
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .ll), the value
of parameter 4.9 determines the braking time. When the frequency is 5 10% of
the nominal, the braking time is 10% of the set value of parameter 4.9. See figure
1.5-l 3.
HV9000
Standard Application
Page 1-19
fn 7
S
P
e
:
fn
Output frequency
,,
Motor speed
Output frequency
”
*
*
~
RUN
STOP
Motor speed
DC-braking ON ‘1,
“”
t
*
.
__
DC-braking ON
t = 0 1 x par. 4.9
:
t
.
.
RUN
STOP
t = 1 xpar.4.9
“WOOKZI
Figure 1.513 DC-braking fime when stop = coasting.
StoD-function = 1 framol:
After a Stop command, the speed of the motor is reduced based on the deceleration
ramp parameter. If no regeneration occurs due to load inertia DC-braking starts at
0.5 Hz.
The braking time is defined by
par. 4.9. If the load has a high
inertia, use an external braking
resistor for faster deceleration.
See figure 1.514.
Figure 1.5-14 DC-braking time when stop
function = ramp.
5.1
5.2
Prohibit frequency area
Low limit/High limit
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance problems.
With these parameters it is
possible to set limits for one “skip
frequency” region between 0 Hz
and 120 Hz/500 Hz. Accuracy of
the setting is 0.1 Hz.
See figure 1.5-l 5.
t
[Hz1
Figure 1.5- I5 Example ofprohibit frequency
area setting.
Page
l-20
Standard Application
Motor control mode
0 =
Frequency control:
(V/Hz)
1 = Speed control:
(sensorless vector)
HV9000
6.1
The I/O terminal and panel references are frequency ref-
erences and the drive controls the output frequency (out-
put freq. resolution 0.01 Hz)
The I/O terminal and panel references are speed refer-
ences and the drive controls the motor speed (control
accuracy + 0.5%).
6.2
Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHzA40 Hp)
check the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter
5.2 of the User’s Manual.
6.3
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage reaches
the set maximum value (parameter 6. 4). Above that frequency the output voltage
remains constant at the set maximum value. Below that frequency the output voltage
depends on the setting of the V/Hz curve parameters 1. 8, 1. 9, 6. 5, 6. 6 and 6. 7.
See figure 1.5-16.
When the parameters 1. 10 and 1. 11, nominal voltage and nominal frequency of
the motor, are set, parameters 6.3 and 6. 4 are also set automatically to the same
values. If you need different values for the field weakening point and the maximum
output voltage, change these parameters after setting parameters 1. 10 and 1. 11.
6.4
6.5
V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle frequency point of the curve. See figure 1.5-16.
6.6 V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle voltage point of the curve. See figure 1.5-16.
6.7
Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1. 8, this
parameter defines the zero frequency voltage of the curve. See figure 1.5-16.
6.6
6.9
Overvoltage
Undervoltage
controller
controller
These parameters allow the over/undervoltage controllers to be switched ON or OFF.
This may be useful in cases where the utility supply voltage varies more than -15%-
+10% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/undervoltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undervoltage trips may occur when the controllers are not used.
HV9000
Standard Application
Page l-21
h
Parameter
6.4
“”
UM
Default: nominal
Parameter 6.6
Default 10% --
Parameter 6.7
Default 1.3 %
/
Default: nominal frequency
<
Parameter 6.5
(Default 5 Hz)
Parameter 6.3 f(Hz]
Figure
1.5-16
Programmable V/Hz curve.
7.1
Response to reference faults
0 = No response
1 = Warning
2 = Fault, stop mode after fault detection according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA.
The information can also be programmed via digital output DO1 and via relay
outputs ROl and R02.
7.2
Response to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault detection according to parameter
3 = Fault, always coasting stop mode after fault detection
4.7
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3.
The information can also be programmed
outputs ROl and R02.
7.3
into digital output DO1 and into relay
Phase supervision of the motor
0 = No action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
7.4
Ground fault protection
0 = No action
2 = Fault
Ground fault protection ensures that the sum of motor phase currents is zero. The
standard overcurrent protection is always present and protects the drive from ground
faults with high current levels.
Page l-22
Standard Application
HV9000
7.5 Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip
The motor thermal protection protects the motor from overheating. In the
Standard application the thermal protection has fixed settings. In other
applications it is possible to set the thermal protection parameters. A trip or a
warning will give an indication on the display. If trip is selected, the drive will stop
the motor and generate a fault.
Deactivating the protection by setting the parameter to 0 will reset the internal thermal
model to 0% heating.
The HV9000 is capable of providing
higher than nominal current to the
motor. If the load requires this high
current there is a risk that motor will
be thermally overloaded. This is
true especially at low frequencies.
With low frequencies the cooling
effect of the motor fan is reduced
and the capacity of the motor is
reduced. Motor thermal protection
is based on a calculated model and
it uses the output current of the
drive to determine the load on the
motor.
Overload area
IT
I
I
I
I
35 Hz
f WI
*
“UC”, ia
The thermal current Ir specifies
Figure 1.5- 17
Motor thermal current IT curve
the load current above which the
motor is overloaded. See figure
1.5-17. If the motor current is over the curve the motor temperature is increasing.
CAUTION! The calculated model does not protect the motor if the cooling of
the motor is reduced either by blocking the airflow or due to dust
or dirt.
Stall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
The Motor Stall protection provides a warning or a fault based on a short time overload
of the stalled shaft. The stall protection is faster than the motor thermal
protection. The stall state is defined with Stall Current and Stall Frequency. In the
Standard application they both have fixed values. See figure 1.5-l 8. If the current is
higher than the set limit and output frequency is lower than the set limit the stall
state is true. If the stall lasts longer than 15 s a stall warning is given on the display
panel. In the other applications it is possible to set the parameters of the Stall
protection function. Tripping and warning will give a display indication. If tripping is
set on, the drive will stop and generate a fault.
HV9000
Standard Application
Page l-23
Deactivating the stall protection by
setting the parameter to 0 will
reset the stall time counter to zero.
I
Stall area
L
Figure
1.5-18 Sal/state.
8.1
8.2
Automatic restart: number of tries
Automatic restart: trial time
The Automatic restart function will restart the drive after the following faults:
- overcurrent
-
overvoltage
-
undervoltage
-
over/under temperature of the drive
-
reference fault
Three faults
Figure 1.5-19 Automatic restart.
Parameter 8. 1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The count time starts from the first autorestart. If the number of restarts does not
exceed the value of the parameter 8.1 during the trial time, the count is cleared after
the trial time has elapsed. The next fault starts the counting again.
q
8.3
Notes:
Page l-24
Standard Application
.
HV9000
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
HV9000 Local/Remote Control Application
Page
2-l
LOCAL/REMOTE CONTROL APPLICATION
(par. 0.1 = 3)
CONTENTS
2 Local/Remote Control Application ..2-1
2.1
General .......................................
.2-2
2.2
Control I/O.. .................................
.2-2
2.3
Control signal logic.. .....................
2-3
2.4
Parameters Group 1
....................
2-4
2.4.1 Parameter table
.................. 2-4
2.4.2 Description of 2-5
2.5 Special parameters, Groups 2-8 2-8
2.5.1 Parameter tables 2-8
2.5.2 Description of Group 2 par.. 2-15
Page 2-2
Local/Remote Control Application
HV9000
2.1 General
By utilizing
the Local/Remote Control
Application, the use of two different control
and frequency reference sources is
programmable. The active control source is
selected with digital input DIB6.
The Local/Remote Control Application can be
activated from the Group 0 by setting the value
of parameter 0. 1 to 3.
Basic connections of inputs and outputs are
shown in the figure 2.2-l. The control signal
logic is shown in the figure 2.3-l. Programming
of l/O terminals is explained in chapter 2.5,
Special parameters.
2.2
Control l/O
Local reference
potentiometer
Terminal Signal
Description
r-k- -9
+iOV,,t Reference output
Voltage for a potentiometer, etc.
j _ _~ 2 VI,+
;;,;pei;p4ud$rammab,e)
;;;;E;;qvugy
reference
L_____
9
GND
I/O ground
Ground for reference and controls
Remote reference - - 4
Analog input, Source A frequency reference
O(4)-20 mA - - s
I,,+
1,“‘
current (programmable)
range O-20 mA
Remote control
“y -/___-
l/-____
Remote
--------
control ground
r-------
FAULT
220 -----
--
Figure
2.2-l Default I/O
configuration and connection example of the Local/
Remote
Control Application.
Page 2-4
Local/Remote Control Application
HV9000
2.4 Basic parameters, Group 1
a.1 Parameter table
1 = Anal. current input (term. 4)
2 = Set reference from the panel
3 = Slgnal from internal motor pot.
Visibility of the parameters:
0 = All parameter groups wble
1 = Only group 1 is visible
1.16 Parameter value lock O-l
1
0
Disables parameter changes:
0 = Changes enabled
1 = Changes disabled
2-i
Tab/e 2.4-I Group 1 basic parameters.
Note! m =
Parameter value can be changed only
*
If 1.2 > motor synchr. speed, check suitability for motor
and drive system. Selecting 120 Hz/500 Hz range, see
page 2-5.
** Default value for a four pole motor and a nominal
size HV9000.
*** Up to MIO. Bigger classes case by case.
when the drive is stopped.
Page 2-6
Local/Remote Control Application HV9000
Squared:
The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1 point (par. 6. 3) where the nominal maximum voltage is supplied to
the motor. See figure 2.4-1.
The motor runs undermagnetized below the field weakening point
and produces less torque and electromechanical noise. A squared
V/Hz ratio can be used in applications where the torque demand of
the load is proportional to the square of the speed, e.g. in centrifugal
fans and pumps.
u
WI
V”
Default: Nominal
Field weakening
point
Default: Nominal
frequency of the
motor
j
WI
Figure
2.4- 1
Linear and squared V/Hz cutves.
V/Hz curve can be programmed with three different points.
V/Hz curve The parameters for programming are explained in chapter 2.5.2
2
Programmable V/Hz curve can be used if the standard settings
do not satisfy the needs of the application. See figure 2.4-2.
I
Parameter 6.7 v!
1
of the motor
Default 1.3 % 1
! V
/
Parameter 6.5
Parameter 6.3 QHz]
)
(Default 5 Hz)
Figure 2.4-2 Programmable V/Hz curve.
HV9660
1.9
Local/Remote Control Application
Page 2-7
V/Hz optimization
Automatic
torque
boost
The voltage to the motor changes automatically which allows the
motor to produce torque enough to start and run at low frequencies.
The voltage increase depends on the motor type and horsepower.
Automatic torque boost can be used in applications where starting
torque due to starting friction is high, e.g. in conveyors.
NOTE!
In high torque - low speed applications
-
it is &e/y the motor wi// overheat.
If the motor has to run for a prolonged time under these conditions, special
attention must be paid to cooling of the motor. Use external cooling for
the motor if the temperature rise is too high.
1.10
Nominal voltage of the motor
Find this value V, from the nameplate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6.4, to 100%
1.11
x Vnmotor.
Nominal frequency of the motor
Find the nominal frequency f, from the nameplate of the motor.
This parameter sets the field weakening point, parameter 6.3, to the same value.
1.12 Nominal speed of the motor
Find this value nn from the nameplate of the motor.
1.13
Nominal current of the motor
Find the value In from the nameplate of the motor.
The internal motor protection function uses this value as a reference value.
1.14 Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2,4,5, and 6. See table 2.4-1.
1.15
Parameter conceal
Defines which parameter groups are available:
0 = all groups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access for changing the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
If you have to adjust more of the functions of the Local/Remote Control Application, see
chapter 2.5 to set up parameters of Groups 2-6.
HVQOOO
Local/Remote Control Application
Page 2-Q
code
2.16
Parameter
Free analog input,
signal selection
Free analog input,
function
2.19
=l=
Range
&2
step
1
3efault
1 custom
Description
0 = Not uset
1 = Vi, (analog voltage input)
2 = Iin (analog current input)
le
‘ag
2-2 !O
2.20
Motor potentiometer
ramp time
T
-1
Range
O-7
’
‘0
0 = No function 2-2
1 = Reduces current limit (par. I. 7)
2 = Reduces DC-braking current
3 = Reduces act. and decel. times
4 = Reduces torque supewis. limit
2
2-2
1
Group 3, Output and supervision parameters
-
Gxle
3.1
‘ammeter
rnalog output function
lefault
1
Description
Scale 100%
0 = Not used
1 = O/P frequency
(o-f,..)
2 = Motor
speed
(0-max. speed)
3 = O/P current
(o-Z.0 x 1”““s)
4 = Motortorque (O-2 x T.,&
5 = Motor power (o-2 x pnMot)
6 = Motor voltage (O-1 00% x VnMo,
7 = DC-linkvolt.
(0-1000 V)
4
ie
2
!-2
_
2
!-2
12
!-2
_
!-2 2
-
12
!-2
-
!P ‘3
3.2
3.3
3.4
3.5
3.6
nalog output filter time
nalog output inversion
*********!
&I
6-l
I.01 s
1
1
1%
1
100s
0
0
0 = Not iwelted
1 = Inverted
O=OmA
1=4mA
nalog output scale
Xgital output function
1 O-1 000%
O-21
100%
1 0 = Not used
1 = Ready
2=Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7= Reference fault or warning
6 = Warning
9 = Reversed
10 = Jog speed selected
11 = At speed
12 = Motor regulator activated
13 = Output frequency limit
superv. 1
14 = Output frequency limit
superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
16 = Control from I/O terminals
19 = Drive temperature limit super
vision
20 = Unrequested rotation directic
21 = External brake control
I=
Parameter value can be changed only when the drive is stopped
Page 2-l 0
Local/Remote Control ADDlication
HV9000
I
cods
I
Parameter
Relay
1 flame 1 step
I Default I Custom IDescdption
As parameter 3.6
I Paw
output
1 function
supervision value
(2),
I I
3.13
I
Torque limit
supervision function
3.14
1
Torque limit
supervision value
Active reference limit
supervision
Active reference limit
supervision value
1
0.~200.0%
x Tntw
O-2
1
0.1%
j
100.0%
1
1 0 O=No
1 = Low limit
2 = High limit
1
2-24
2-24 3.15
3.16 O.&f,,
(par. 1.2)
1 0.0-100.0s
0.1 Hz
1 0.1 s
2-24
I 2-25
1 3.17 I External brakeOFFdelav
I 3.16 1 ExternalbrakeONdelay
3.19 Drive
temperature limit
supervision function
Drive
temperature limit
l/O-expander board (opt.)
analog output function
l/O-expander board (opt.)
analoa output filter time
1
0.5 s
/
0 0 = No supewision
1 = Low limit
2 = High limit
I
O.(
O-2
I
0.1 s
I 1.5s I
1
1
2-25
2-25
3.20
3.21
3.22
-10-+75”C
&7
0.00-l
0-l
1
1
+wc
3
1 .OO s
1
I
0
0
1
I
See parameter 3.1
See parameter 3.2
ISeeparameter3.3
ISee parameter3.4
ISeeparameter3.5
2-25
2-22
2-22 0.00 s 0.01 s
1 1
1
analog output inversion
l/O-expander board (opt.)
(
board (opt.)
analog output minimum
1
2-22
I
2-22
(
2-22
1 C-1 /
I
I
3.25
analog output scale
I/O-expander board (opt.)
1
l&1000%
1
1
I
100%
1
Note! m =
Parameter value can be changed only when the drive is stopped
HV9000
Local/Remote Control Application
Page 2-11
Group 4, Drive control parameters
>O = S-curve . time
0 = Brake chopper not in use
1 = Brake chopper in use
Group 5, Prohibit frequency parameters
Note!m=
Parameter value can be changed only when the drive is stopped.
Page 2-l 2
Local/Remote Control ADDlication
HV9000
Group 6, Motor control parameters
code I Parameter
I
I
Default ICustcm
I
Description
Note!
m =
Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
Cc&
7.1
Parameter
Response to
reference fault
Local/Remote Control Application
Page 2-l 3
Range
O-3
step
Default
1 0
Custom Description
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3 = Fault, always coasting stop
0 = No action
1 = Warning
2 = Fault. stoo accordina to
I oar. 4.7
”
3 = kault, always coasting stop
Page
2-30
7.2
Response to
external fault
o-3
1 0
2-31
l-
7.3
7.4
7.5
Phase supervision of
the motor
Ground fault protection
Motor thermal protection
&2
&2
g#Jgq-
1.0%
1 .O%
0.5
mix
1 Hz
100.0%
45.0%
17.0
min.
35 Hz
Default value is set
according
to motor nominal current
/ I
_I
7.0
7.9
7.10
Motor thermal protection
time constant
Motor thermal protection
break point frequency
Stall protection
0.5-300.0
minutes
1 O-500 Hz
&2
7.11
7.12
7.13
7.14
Stall current limit
Stall time
Maximum stall frequency
Underload protection
5.0-200.0%
x l”MOTOR
2.0-120.0 s
2-32
2-32
2-33
2-33
2= Fault -
1 .O%
(
130.0%
2-34
1
I 2-4
t-fIllax
O-2
7.15
7.16
7.17
Underload pmt., field
weakening area load
Underload protection,
zero frequency load
Underload time
10.0-l 50.00,
I
1 .O%
10.0%
I
XT~MOTOR
5.0-150.0%
I
I
2-35
Paae 2-l 4
Local/Remote COntrOl ADDhCatiOn
HV9000
Group 8, Autorestart parameters
Table 2.5 7
Special
parameters,
Groups
2-8.
HV9000
Local/Remote Control Application
Page 2-15
2.5.2 Description of Groups 2-9
2.1
parameters
Start/Stop logic selection
0:
DIAl:
closed contact = start forward
DIA2: closed contact = start reverse,
See figure 2.5-l.
Figure 2.5 7
Start forward/Start reverse.
0
0
0
1:
The first selected direction has the highest priority
When DlAl contact opens, the direction of rotation starts to change
If Start forward (DIAl) and Start reverse (DIA2) signals are active
simultaneously, the Start forward signal (DIAl) has priority.
DlAl : closed contact = start
DIA2: closed contact = reverse
See figure 2.5-2.
open contact = stop
open contact = forward
Figure 2.5-2
Start,
Stop, reverse.
Page 2-16
Local/Remote Control Application HV9000
2:
DlAl : closed contact = start
open contact = stop
DIA2:
closed contact = start enabled open contact = start disabled
3:
3-wire connection (pulse control):
DlAl : closed contact = start pulse
DIA2: closed contact = stop pulse
(DIA3 can be programmed for reverse command)
See figure 2.5-3.
4: DIAl: closed contact = start forward
DIA2: closed contact = reference increases (motor potentiometer
reference, par. 2. 1 is automatically set to 4 if
par. 1. 5 is set to 3 or 4).
Figure 2.5-3
Sfafi
pulse /Stop pulse.
2. 2
DIA3 function
1: External
fault, closing contact = Fault is shown and motor is stopped when
the contact is closed
2: External fault, opening contact = Fault is shown and motor is stopped when
the input is open
3: Run enable
contact open = Start of the motor disabled
contact closed
= Start of the motor enabled
4: Act. I Dee
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5: Reverse
contact open
= Forward Can be used for reversing if
contact closed
= Reverse
II
parameter 2. 1 has value 3
6: Jogfreq.
contact closed
= Jog frequency selected for freq. refer.
7: Fault reset
contact closed
= Resets all faults
8: Acc./Dec. operation prohibited
contact closed
= Stops acceleration and deceleration until
the contact is opened
9: DC-braking command
contact closed
= In the stop mode, the DC-braking operates
until the contact is opened, see figure 2.5-4.
DC-brake current is set with parameter 4. 8.
10:
Motor pot. meter down
contact closed = Reference decreases until the contact is
opened
Page 2-20
Local/Remote Control Application
HV9000
2.13 Source B Start/Stop logic selection
See parameter 2. 1, settings O-3.
2.14, Source A reference scaling, minimum value/maximum value
2.15
Setting limits: 0 < par. 2. 14 < par. 2. 15 < par. 1. 2.
If par. 2. 15 = 0 scaling is set off. See figures 2.5-11 and 2.512.
(h the figures below voltage input Vin with signal range O-70 V selected for source A
reference)
Figure 2.5- 7 1
Reference scaling. Figure 2.5-12 Reference scaling,
par. 2. 15 = 0.
2.16,
Source B reference scaling,
2.17
minimum value/maximum value
See parameters 2.14 and 2. 15.
2. 18 Free analog input signal
Selection of input signal of
a free
analog input (an input not used for reference signal):
0 = Not in use
1 = Voltage signal V,,
2 = Current signal I,,
2.19
Free analog input signal
function
Use this parameter to select a
function for a free analog input
signal:
0 = Function is not used
1 = Reducing motor
current limit (par. 1. 7)
This signal will adjust the
maximum motor current between
0 and ,par. 1.7 set max. limit. See
figure 2.5-l 3.
Figure 2.5- 13
Scaling of max. motor current.
HV9000
Local/Remote Control Application
2 = Reducing DC brake
current.
The DC braking current can be
reduced with the free analog input
signal between current 0.15 x InHvS
and the current set by parameter
4.8. See figure 2.5-14.
Page
2-21
Figure 2.5 14
3 = Reducing acceleration
and deceleration
times.
The acceleration and deceleration
times can be reduced with the free
analog input signal according to
the following formulas:
Reduced time = set act./
(par. 1. 3, 1. 4; 4. 3,
4. 4) divided by the factor R from
figure 2.5-l 5.
Reducing DC brake current.
Figure 2.5- 15 Reducing acceleration and
deceleration times
4 = Reducing torque
supervision limit.
Torque supervision limit can be
reduced with a free analog input
signal between 0 and the set
supervision limit (par. 3. 14). See
figure 2.5-l 6.
te
figure 2.5 16 Reducing torque supervision limit
Paoe 2-22
Local/Remote Control Audication
Motor potentiometer ramp
HV9000
2.20
time
Defines how fast the electronic
motor potentiometer value
changes.
3.1
Analog
output Content
See
table for parameter 3.1 on
page 2-9.
3.2
Analog output filter
time
Filters the analog output signal.
See figure 2.5-i 7.
-I
Par. 3.2
Figure
2.5- 17
Analog output Wering.
3.3 Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
3. 4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4 mA.
See figure 2.5-l 9.
3.5
Analog output
scale
Scaling factor for analog output.
Figure 2.5- 18
Analog output invert.
See figure 2.5-19.
I
Sianal
1 Max. value
of the signal
output fre-
Max. frequency (p. 1. 2)
quency
Motor speed Max. speed (n,xf,,JfJ
Output
2x1
current
nnvs
Motor torque 2 xT,~,,,
Motor power 2 x PnMot
Motor voltage
100% x
VnMof
DC-link volt. 1000 V
Figure2.5-19Analog outputscale
HV9000 Local/Remote Control Application
Page 2-23
3.6
3.7
3.6
Digital output function
Relay output 1 function
Relay output 2 function
Setting value
0 = Not used
Signal content
Out of operation
Diaital outout DO1 sinks current and oroarammable
relav (ROl, R021 is activated when:
The drive is ready to operate
The drive operates (motor is running)
A fault trip has occurred
A fault trip h&n&t occurred
The heat-sink temperature exceeds +7O”C
Fault or warning depending on parameter 7. 2
Fault or warning depending on parameter 7. 1
-
if analog reference is 4-20 mA and signal is c4mA
0 = Warning
Always if a warning exists
9 = Reversed
The reverse command has been selected
1 O= Jog speed
Jog speed has been selected with digital input
1 1 =
At speed
The output frequency has reached the set reference
12= Motor regulator activated
Overvoltage or overcurrent regulator was activated
13= Output frequency supervision 1
The output frequency goes outside of the set supervision
Low limit! High limit (par. 3. 9 and 3. 10)
14 = Output frequency supervision 2
The output frequency goes outside of the set supervision
Low limit/ High limit (par. 3. 11 and 3. 12)
15 = Torque limit supervision
The motor torque goes outside of the set supervision
Low limit/ High limit (par. 3. 13 and 3. 14)
16 = Active reference Active reference goes outside of the set supervision
limit supervision
Low limit/ High limit (par. 3. 15 and 3. 16)
17= External brake control External brake ON/OFF control with programmable
delay (par 3. 17 and 3. 18)
18= Control from I/O terminals External control mode selected with prog. pushbutton #2
19= Drive
Temperature on drive is outside the set
temperature limit supervision supervision limits (par. 3. 19 and 3. 20)
20= Unrequested rotation direction Rotation direction of the motor shaft is different from the
requested one
21= External brake control inverted External brake ON/OFF control (par. 3.17 and 3.18).
output active when brake control is OFF
Table 2.52 Output signals via DO 7 and output relays RO 7 and ROZ.
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
Page 2-24
Local/Remote Control Application
HV9000
3.9
Output frequency limit 1, supervision function
3.11
Output frequency limit 2, supervision function
0 = No
supervision
1 = Low limit supervision
2 =
High limit supervision
If the output frequency goes under/over the set limit (3. 10, 3. 12) this function
generates a warning message via the digital output DO1 or via a relay output ROl
or R02 depending on the settings of the parameters 3. 6-3. 8.
3.10
Output frequency limit 1, supervision value
3.12
Output frequency limit 2, supervision value
The frequency value to be supervised by the parameter 3. 9 (3. 11). See figure
2.5-20.
3.13
Torque limit
,
supervision
function
0 = No
supervision
1 = Low limit supervision
2 = High limit supervision
If the calculated torque value goes
under/over the set limit (3.14) this
function generates a warning
message via the digital output
DO1 or via a relay output ROl or
Figure 2.5-20 Output frequency supervision.
R02 depending on the settings of
the parameters 3. 6-3.8.
3.14
Torque limit
,
supervision value
The calculated torque value to be supervised by the parameter 3. 13. Torque
supervision value can be reduced below the setpoint with a free analog input signal,
see parameters 2. 18 and 2. 19.
3.15
Reference limit , supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3. 16) this function generates a
warning message via the digital output DO1 or via a relay output ROl or R02
depending on the settings of the parameters 3. 6-3. 8. The supervised reference
is the current active reference. It can be source A or B reference depending on DIB6
input or panel reference if panel is the active control source.
3.16
Reference limit , supervision value
The frequency value to be supervised by the parameter 3.15.
HV9000 Local/Remote Control Application
Page 2-25
3.17
3.18
External brake-off delay
External brake-on delay
The function of the external brake can be delayed from the start and stop control
signals with these parameters. See figure 2.521.
Figure
2.52 1 Ext.
brake controf; a) Start&top logic selection par 2. 7 = 0, 1 or 2
b) StarCStop logic selection par 2. 7 = 3.
The brake control signal can be programmed via the digital output DO1 or via
one of the relay outputs ROl and R02, see parameters 3. 6-3.8.
3.19
Drive temperature limit supervision
0 = No supervision
1 =
Low limit supervision
2 = High limit supervision
If temperature of the unit goes under/over the set limit (par. 3. 20) this function
generates a warning message via the digital output DO1 and via a relay output ROl
or R02 depending on the settings of the parameters 3. 6-3. 8.
3.20
Drive temperature supervision limit value
The set temperature value to be supervised with the parameter 3. 19.
Page 2-26 Local/Remote Control Application
HV9000
4.1
Acc/Dec ramp 1 shape
4.2
AcclDec ramp 2 shape
The acceleration and deceleration ramp shape can be programmed with these
parameters.
Setting the value = 0 gives you a linear ramp shape. The output frequency immediately
follows the input with a ramp time set by parameters 1.3, 1.4 (4.3,4.4 for Acc/Dec
time 2).
Setting 0.1-10 seconds for 4.1
(4.2) causes an S-shaped ramp.
t
f [Hz1
The speed changes are smooth.
Parameter 1.3/ 1.4 (4.3/ 4.4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure
: ~
(4.3,4.4) :
2.5-22.
+T-
I’
1.3.1.4_
I-;
4. 1 (4. 2)
/,
Figure 2.5-Z
S-shaped acceleration/deceleration
4.3
Acceleration time 2
4.4
Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possible to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2. 2. Acceleration/deceleration times can be reduced
with a free analog input signal. See parameters 2. 18 and 2. 19.
4.5
Brake chopper
0 = No brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor,
the energy stored in the inertia of the motor
and the load is fed into the external brake resistor. If the brake resistor is selected
correctly the drive is able to decelerate the load with a torque equal to that of
acceleration, See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may cause prolonged
acceleration times).
HV9000
Local/Remote Control Application
Page 2-27
Flying start:
1 The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7
Stop function
Coasting:
The motor coasts to an uncontrolled stop with the HV9000 off, after the Stop
0
command.
Ramp:
1 After the Stop command, the speed of the motor is decelerated based on
the deceleration ramp time parameter.
If the regenerated energy is high, it may be necessary to use an external
braking resistor for faster deceleration.
4.8
DC
braking current
Defines the current injected into the motor during DC braking.
The DC braking current can be reduced from the setpoint with a external free
analog input signal, see parameters 2. 18 and 2. 19.
4.9
DC
braking time at stop
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4.7. See figure 2.5-23.
0
SO
DC-brake is not used
DC-brake is in use and its function depends of the stop function,
(parameter 4. 7), The time is set by the value of parameter 4. 9:
Stoo-function = 0 (coastina):
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .l l), the value
of parameter 4.9 determines the braking time. When the frequency is c 10%
of the nominal, the braking time is 10% of the set value of parameter 4.9. See
figure 2.5-13.
Stop-function = 1 (ramp):
After a Stop command, the speed of the motor is reduced based on the
deceleration ramp parameter. If no regeneration occurs due to load inertia DC-
braking starts at a speed defined by parameter 4. 10.
Page 2-28
Local/Remote Control Application HV9000
Figure 2.5-23 DC-braking time when par. 4. 7 = 0.
The braking time is defined
by par. 4.9. If the load has a
high inertia, use an external
braking resistor for faster
decelerationSee figure 2.5-
24.
4.10 Execute frequency of DC-
brake during ramp Stop
Figure 2.5-24 DC-braking time when par. 4. 7
= 1.
See figure 2.524.
4.11
DC-brake time at start
fom
WI
0 DC-brake is not used
>O
The DC-brake is activated
by the start command
given. This parameter
defines the time before the
brake is released. After the
brake is released the output
t
frequency increases
I
: par4.11:
according to the set start
,-
function parameter 4.6
RUN
and the acceleration
STOP
“D012Kz2
parameters (1. 3, 4. 1 or 4.
‘igore2.5-25 DC-braking time
2,4.3). See figure 2.5-25.
at start.
HWOOO
Local/Remote Control Application Page 2-29
4.12 Jog speed reference
This parameter value defines the jog speed if the DIA3 digital input is programmed
for Jog and is selected. See parameter 2.2.
5. l- 5.6
Prohibit frequency area
Low limit/High limit
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance
problems.
With these parameters it is
possible to set limits for three “skip
frequency” regions between 0 Hz
and 500 Hz. The accuracy of the
setting is 0.1 Hz. See figure 2.5-26
frequency
reference
Reference [HZ,
*
Figure 2.5-26
Example of prohibit frequency
area setting.
6.1
Motor control mode
0 = Frequency control:
(V/Hz)
1 = Speed control:
(sensorless vector)
The I/O terminal and panel references are frequency
references and the drive controls the output frequency
(output freq. resolution 0.01 Hz)
The l/O terminal and panel references are speed
references and the drive controls the motor speed (control
accuracy * 0.5%).
6.2
Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHz >40 Hp) check
the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter 5.2 of the
User’s Manual.
6.3
6.4
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage reaches
the set maximum value (parameter 6. 4). Above that frequency the output voltage
remains constant at the set maximum value. Below that frequency the output voltage
depends on the setting of the V/Hz curve parameters 1.8, 1.9, 6.5,6.6 and 6.7.
See figure 1.5-l 8.
When the parameters 1.10 and 1.11, nominal voltage and nominal frequency of the
motor, are set, parameters 6.3 and 6.4 are also set automatically to the same values.
If you need different values for the field weakening point and the maximum output
voltage, change these parameters after setting parameters 1. 10 and 1. 11.
Page 2-30
Local/Remote Control Application
HV9000
6.5 V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle frequency point of the curve. See figure 2.5-27.
6.6 V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle point voltage (% of motor nominal voltage) of the curve. See figure
2.5-27.
6.7 Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the zero frequency voltage (% of motor nominal voltage) of the curve. See
figure 2.5-27.
Parameter 6.5
Parameter 6.3 qHz]
(Default 5 Hz)
Figure 2.5-27
Programmable V/Hz cwve.
6.8 Overvoltage controller
6.9 Undervoltage controller
These parameters allow the over/undervoltage controllers to be switched ON or OFF.
This may be useful in cases where the utility supply voltage varies more than -15%-
+1 0% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/under-voltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undervoltage trips may occur when controllers are not used.
7. 1
Response to the reference fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA. The information can also be
programmed via digital output DO1 and via relay outputs ROl and R02.
HV9000
Local/Remote Control Application
Page 2-31
7.2
Response to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated from the external fault signal
on digital input DIA3. The information can also be programmed into digital output
and into relay
DO1
outputs ROl and R02.
7.3
Phase supervision
0 = No action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
7.4 Ground fault protection
0 = No action
2 = Fault message
Ground fault protection ensures that the sum of the motor phase currents is zero.
The standard overcurrent protection is always present and protects the frequency
converter from ground faults with high current levels.
Parameters 7.5-7.9 Motor thermal protection
of the motor
General
Motor thermal protection protects the motor from overheating. The HV9000 drive is
capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that motor will be thermally overloaded. This is true
especially at low frequencies. With low frequencies the cooling effect of the motor
fan is reduced and the capacity of the motor is reduced. If the motor is equipped
with a separately powered external fan, the load derating at low speed is small.
Motor thermal protection is based on a calculated model and it uses the output cur-
rent of the drive to determine the load on the motor. When the motor is powered
from the drive, the calculated model uses the heatsink temperature to determine
the initial thermal state of the motor. The calculated model assumes that the ambi-
ent temperature of the motor is 40°C.
Motor thermal protection can be adjusted by setting several parameters. The thermal
current IT specifies the load current above which the motor is overloaded. This cur-
rent level is a function of the output frequency. The curve for IT is set with param-
eters 7.6, 7. 7 and 7. 9. See figure 2.5-28. The default values of these parameters
are set from the motor nameplate data.
With the output current at IT the thermal state will reach the nominal value (100%).
The thermal state changes by the square of the current. With output current at 75%
of IT the thermal state will reach 56% and with output current at 120% of $ the thermal
stage would reach 144%. The function will trip the drive (refer par. 7.5) If the thermal
state reaches a value of 105%. The response time of the thermal model is deter-
mined by the time constant parameter 7.8. The larger the motor, the longer it takes
to reach the final temperature.
Page 2-32
Local/Remote Control Application
HV9000
The thermal state of the motor can be monitored through the display. Refer to the
table for monitoring items. (User’s Manual, table 7.3-l).
CAUTION!
The calculated mode/ does not protect the motor if the cooling of
A
!
the motor is reduced either by blocking the airflow or due to dust or
dirt.
7. 5 Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection by setting this parameter to 0, will reset the thermal stage
of the motor to 0%.
7.6 Motor thermal protection, break point current
This current can be set between 50.0-150.0% x InMatar.
This parameter sets the value for thermal current at frequencies above the break
point on the thermal current curve. Refer to the figure 2.5-28.
The value is set as a percentage of the motor nameplate nominal current, parameter
1. 13, not the drive’s nominal output current.
The motor’s nominal current is the current which the motor can withstand in direct
online use without being overheated.
If parameter 1. 13 is adjusted, this parameter is automatically restored to the default
value.
Setting this parameter (or
I
parameter 1. 13) does not affect
the maximum output current of the
drive. Parameter 1.7 alone
determines the maximum output
current of the drive.
Par. 7. 6
---------
Overload area
IT
Par. 7.7
Figure 2.5-28 Motor thermal current, I,
curve.
7.7
Motor thermal protection, zero frequency current
This current can be set between lO.O-150.0% x InMotor
This parameter sets the value for thermal current at zero frequency. Refer to the
figure 2.5-28.
The default value is set assuming that there is no external fan cooling the motor. If
an external fan is used this parameter can be set to 90% (or higher).
HV9000
Local/Remote Control Application Page 2-33
The value is set as a percentage of the motor’s nominal nameplate current,
parameter 1.13, not the drive’s nominal output current. The motor’s nominal current
is the current which the motor can stand in direct on-line use without being
overheated.
If you change parameter 1.13, this parameter is automatically restored to the default
value.
Setting this parameter (or parameter 1. 13) does not affect to the maximum output
current of the drive. Parameter 1.7 alone determines the maximum outout current
of the drive.
7.8
Motor thermal protection, time constant
This time can be set between 0.5-300 minutes.
This is the thermal time constant of the motor. The larger the motor the greater
the time constant. The time constant is defined as the time that it takes the calcu-
lated thermal stage to reach 63% of its final value.
The motor thermal time is specific to a motor design and it varies between different
motor manufacturers.
The default value for the time constant is calculated based on the motor
nameplate data from parameters 1. 12 and 1. 13. If either of these parameters is
reset, then this parameter is set to default value.
If the motor’s t6 -time is known (given by the motor manufacturer) the time
constant parameter could be set based on ts -time. As a rule of thumb, the motor
thermal time constant in minutes equals to 2xts (t6 in seconds is the time a motor
can safely operate at six times the rated current). If the drive is stopped the time
constant is internally increased to three times the set parameter value. Cooling in
the stop stage is based on convection with an increased time constant
7.9
Motor thermal protection, break point frequency
This frequency can be set between 10-500 Hz.
This is the frequency break point of the thermal current curve. With frequencies
above this point the thermal capacity of the motor is assumed to be constant.
Refer to the figure 2.528.
The default value is based on the motor’s nameplate data, parameter 1. 11. It is 35
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the
frequency at the field weakening point (parameter 6.3). Changing either parameter
1. 11 or 6.3, will restore this parameter to its default value.
f Changed v&l
ad,“sted with
parameter
7.8
motor
s,.z* and
“MC”7
.
92
figure
25-29
Calculafing
motor
temperature.
Page 2-34
Local/Remote Control Application HV9000
Parameters 7.1 O- 7.13, Stall protection
General
Motor stall protection protects the motor from short time overload situations like a
stalled shaft. The reaction time of stall protection can be set shorter than with motor
thermal protection. The stall state is defined with two parameters, 7.11, Stall Current
and 7.13., Stall Frequency. If the current is higher than the set limit and output
frequency is lower than the set limit the stall state is true. There is no true detection
of rbtation. Stall protection is a type of overcurrent protection.
7.10
Stall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is set on, the drive will stop and generate a fault. Deactivating the stall
protection by setting the parameter to 0 will reset the stall time counter to zero.
7.11 Stall current limit
The current can be set between
o.O-200% x InMotor.
In a stall the current has to be
above this limit. See figure 2.5
30. The value is set as a
I
Stall area
percentage of the motor name-
plate nominal current, parameter
1. 13. If parameter 1.13 is
adjusted, this parameter is
Par.7.11
automatically restored to its
default value.
f [Hz1
Pk7. 13 "MCH7_11
i
7.12
Stall time
Figure 2.5-30 Setring the
stall characterisfics.
The time can be set between
2.0-120 s.
A!
Stall time counter
1
This is the maximum allowed
time for a stall. There is an
Trip area
internal up/down counter to
Par. 7. 12
count the stall time. See figure
2.5-31. If the stall time counter
value goes above this limit, this
protection will cause a trip (refer
to the parameter 7. 10).
7.13
Maximum stall frequency
This frequency can be set
between l-f,,X (param. 1. 2). In
the stall state the ouput frequency
has to be smaller than this limit.
See figure 2.5-30.
Figure 2.5-37
Counting the stall time.
HV9000
Parameters 7.14-
General
Local/Remote Control Application
7.17, Underload protection
Page 2-35
The purpose of motor underload protection is to ensure there is a load on the motor
while the drive is running. If the motor load is reduced, there might be a problem in
the process, e.g. broken belt or dry pump.
Motor underload protection can be adjusted by setting the underload curve with
parameters 7.15 and 7. 16. The underload curve is a squared curve set between
zero frequency and the field weakening point. The protection is not active below
5Hz (the underload counter value is stopped). See figure 2.5-32.
The torque values for setting the underload curve are set with percentage values
which refer to the nominal torque of the motor. The motor’s nameplate data,
parameter 1 .13, the motor’s nominal current and the drive’s nominal current Icr
are used to create the scaling ratio for the internal torque value. If other than a
standard motor is used with the drive, the accuracy of the torque calculation is
decreased.
7.14
Underload protection
Operation:
0 = Not in use
1 = Warning message
2 = Fault message
Tripping and warning will give a display indication with the same message code. If
tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection, by setting this parameter to 0, will reset the underload
time counter to zero.
7.15
Underload protection, field weakening area load
The torque limit can be set
between 20.0-l 50 % x TnMotor.
This parameter is the value for
the minimum allowed torque
when the output frequency is
above the field weakening point.
Refer to the figure 2.5-32.
If parameter 1. 13 is adjusted,
this parameter is automatically
restored to its default value.
t
Torque
F
5 Hz
Field weak&fling
point par. 6. 3
Setting
of minimum load.
7.16
Underload protection, zero
frequency load
Figure 25-32
The torque limit can be set between
10.0-150 % x
TnMotor.
This parameter is the value for the minimum allowed torque with zero frequency.
See figure 2.5-32. If parameter 1. 13 is adjusted, this parameter is automatically
restored to its default value.
Page 2-36
Local/Remote Control Application
HV9000
7.17
Underload time
Underload time counter
This time can be set between 2.0-
t
600.0 s.
This is the maximum allowed time
Par. 7. 17 --
for an underload state. There is an
internal up/down counter to
accumulate the underload time.
See figure 2.533.
If the underload counter value
goes above this limit, the
underload protection will cause a
trip (refer to the parameter 7. 14).
If the drive is stopped the
underload counter is reset to zero.
figure 2.533
Counting the underload time.
8.1
Automatic restart: number of tries
8.2 Automatic restart: trial time
The Automatic restart function restarts the drive after the faults selected with
parameters 8.4-8.8. The Start type for Automatic restart is selected with parameter
8.3. See figure 2.5-34.
A
Number of faults
during
t = ttllal
‘trial
‘trial
I
4 --
I
3--
’
2 -- l-l
:
Par. 8.1 = 3
: ttria, = par. 8.
2
1 ~~
t
.
Figure 25-34
Automatic restart.
Parameter 8. 1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The count time starts from the first autorestart. If the number of restarts does not
exceed the value of parameter 8.1 during the trial time, the count is cleared after the
trial time has elapsed. The next fault starts the counting again.
HV9000
8.3
Local/Remote Control Application
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
Page 2-37
8.4 Automatic restart after undervoltage
0 = No
automatic restart after undervoltage fault
1 = Automatic restart after undervoltage fault condition returns to normal.
(DC-link voltage returns to the normal level)
8.5
Automatic restart after overvoltage
0 = No
automatic restart after overvoltage fault
1 = Automatic restart after overvoltage fault condition returns to normal
(DC-link voltage returns to the normal level)
8.6 Automatic restart after overcurrent
0 = No automatic restart after overcurrent fault
1 = Automatic restart after overcurrent faults
8.7
Automatic restart after reference fault
0 = No automatic restart after reference fault
1 = Automatic restart after analog current reference signal (4-20 mA)
returns to the normal level (24 mA)
8.8
Automatic restart after over-/undertemperature fault
0 = No automatic restart after temperature fault
1 = Automatic restart after heatsink temperature has returned to its normal
level
between -1 O”C-+75”C.
Page 2-38
Local/Remote Control Application
HV9000
Notes:
HV9000
Multi-steu SDeed
COtItrOl
ADDliCatiOn
Page 3-l
MULTI-STEP SPEED CONTROL APPLICATION
(par. 0.1 = 4)
CONTENTS
3 Multi-step Speed Control Appl. ....... .3-l
3.1 General ....................................... .3-2
3.2 Control I/O.. ................................. .3-2
3.3 Control signal logic.. .................... .3-3
3.4 Parameters Group 1 .................... 3-4
3.4.1 Parameter table ................. .3-4
3.4.2 Description of 3- 5
3.5 Special parameters, Groups 2-8 .3-8
3.51 Parameter tables .................. 3-8
3.52 Description of Groups.. ...... .3-14
Page 3-2
3.1 GENERAL
Multi-step Speed Control Application
HV9000
The Multi-step Speed Control Application can
be used in applications where fixed speeds are
needed. in total 9 different speeds can be
programmed: one basic speed, 7 multi-step
speeds and one jog speed. The speed steps
are selected with digital signals DIB4, DIB5 and
DIB6. If jog speed is used, DIA3 can be
programmed
select.
from fault reset to jog speed
The basic speed reference can be either a
voltage or a current signal via analog input
terminals (Z/3 or 4/5). The other analog input
can be programmed for other purposes
All outputs are freely programmable
3.2 CONTROL
Reference
I/O
y--_+_
I-
-__;_
,____
----
I
-
--- I-
-
I/- _
Jl_
-
‘l--J-
-
I---$
k
FAULT
220 -----
--
Figure 3.2- 1 Default //O configuration and connection example of the
Multi-step speed Control Application.
HV9000
Multi-steD SDeed Control ADDliCatiOn
Page 3-3
3.3
Control signal logic
PROGRAMMABLE
PUSH-BUTTON 2
frequency
reference
)
Internal
I
Multi-step speed selection 1
-.-.-.-.-.-.-.-.-.-.-.
Multi-step speed selection 2
.-.-.-.-.-.-.-
_tu&i-_s*.zeed
.-.-.-.-.-.-.-
selection 3
m
B
D
I
-
Internal
fault reset
Jog speed reference selection (programmable input)
Fault reset (prowammable input)
Reverse signal
- =sigx4line
Figure 3.3- 1
Control signal logic of the Multi-step Speed Control Application
Switch positions shown are based on the factory settings.
Page 3-4
Multi-step Speed Control Application
HV9000
3.4 Basic parameters, Group 1
Parameter
Minimum frequency
I I
Description
3-5
fmi,-120/500Hz
0.1-3000.0
0.1-3000.0
1 Hz
Time from f,,, (1.
1) to f,,, (1.21
Time from f,,, (1.2) to f,,, (1. lj
0 = Analog voltage input (term.2)
1 = Analog current Input (term 4)
5.0 Hz
3-5
3-5
-
3-5
3-5
Maximum frequency
Acceleration time 1
Deceleration time 1
s
/
0.1 s
s
1
0.1 s
&l
Jog speed
reference
Current limil
1.6
V/Hz ratio selection O-2
1
1
0.1 Hz
fin,” -fmax
(1.1) (1.2)
3-5
1
*“Output curr. limit [A] of the unit
0 = Linear
1 = Squared
2 = Programmable V/Hz ratio
0 = None
1 = Automatic torque boost
Voltage code 2
Voltage code 4
Voltage code 5
Voltaae code 6
3-5
3-6
3-7
3-7
1.11
Nominal frequent
of the motor
3&500 Hz
1 Hz
f, from the nameplate of
the motor
I720 rpm
I
n, from the nameplate of
the motor
3-7
3-7
In
from the nameplate of
the motor
Supply voltage
230V
Voltaae code 2
Voltaae code 4
1 36&500
3-7
3-7
I
Voltaoe code 5
Voltage code 6
Visibility of the parameters:
0 = all parameter groups visible
1 = only group 1 is visible
3-7
1.16
Pararneterval”elock
1
%l
)
1
Disables parameter
changes:
0 =
changes enabled
1 = changes disabled
3-7
Note! m =
Parameter value can be changed
only wnen tne frequency converter is
stopped.
.
’ If 1.
2 >
motor synchr. speed, check suitability
for motor and drive system
Selecting 120/500 Hz range see page 3-5.
** Default value for a four pole motor and a
nominal size HV9000.
‘** Up to Ml 0. Bigger classes case by case.
HV9000
Multi-sten Steed Control ADDlication
Page 3-5
reference 6
1.23
Multi-step speed
reference 7
(l.l)(l.Z)
fm-fmx
(1.1)(1.2)
0.1 Hz 50.0 Hz
3-7
Tab/e 3.4-l Group 1 basicparameters.
3.4.2 Description of Group 1 parameters
1. 1, 1.2
Minimum/maximum frequency
Defines the frequency limits of the HV9000.
The default maximum value for parameters 1.1 and 1.2 is 120 Hz. By setting 1.2 =
120 Hz in the when the drive is stopped (RUN indicator not lit) parameters 1. 1 and
1.2 are changed to 500 Hz. At the same time the resolution of the panel reference is
changed from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting parameter
1. 2 to 119 Hz while the drive is stopped.
1.3,l. 4 Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to
accelerate from the set minimum frequency (par. 1. 1) to the set maximum
frequency (par. 1. 2). Acceleration/deceleration times can be reduced with a free
analog input signal, see parameters 2. 18 and 2. 19.
1.5
Basic reference selection
0:
1:
Analog
voltage reference from terminals 2-3, e.g. a potentiometer
Analog current reference trom terminals 4-5, e.g. a transducer
1.6 Jog speed refrence
The value of this parameter defines the jog speed selected with the DIA3 digital input
which if it is programmed for Jog speed. See parameter 2. 2.
Parameter value is automatically limited between minimum and maximum frequency
(par 1.1,1.2)
1.7 Current limit
This parameter determines the maximum motor current that the HV9000 will provide
short term. Current limit can be set lower with a free analog input signal, see
parameters 2. 18 and 2. 19.
Paae 3-6
Multi-step Speed Control Application
HV9000
1.8 V/Hz ratio selection
Linear:
The voltage of the motor changes linearly with the frequency in
the constant flux area from 0 Hz to the field weakening point
0
(par. 6.3) where a constant voltage (nominal vaue) is supplied to
the motor. See figure 3.4-l.
A linear V/Hz ratio should be used in constant torque applications
This default setting should be used if there is no special
requirement for another setting.
Squared:
The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1
point (par. 6. 3), where the nominal voltage is supplied to
the motor. See figure 3.4-i.
The motor runs undermagnetized below the field weakening point and
produces less torque and electromechanical
noise. A squared V/Hz ratio
can be used in applications where the torque demand of the load is
proportional to the square of the speed, e.g. in centrifugal fans and
v
[VI
1
Default: Nominal voltage of
7
Field weakening point
the motor
Default: Nominal
frequency of the
motor
- Wzl
Figure
3.4- 7
Linearand squared V/Hz curves.
Programm. The V/Hz curve can be programmed with three different points.
V/Hz curve The parameters for programming are explained in chapter 35.2.
2
A programmable V/Hz curve can be used if the standard settings do
not satisfy the needs of the application. See figure 3.4-2.
Parameter 6.6
Default 10%
Default: nominal frequency
Parameter 6.7
of the motor
/
Default 1.3 % 4
Parameter 6.5
I
Parameter 6.3
I/
qHz]
1
(Default 5 Hz)
Figure 3.4-2
Programmable V/Hz curve.
HV9000
1.9
Multi-step
V/Hz optimization
Automatic
torque
boost
Speed Control Application
Page 3-7
The voltage to the motor changes automatically which
allows the motor to produce enough torque to start and
run at low frequencies. The voltage increase depends on the motor type
and horsepower. Automatic torque boost can be used in applications
where starting torque due to starting friction is high, e.g. in conveyors.
In high torque - low speed applications - it is likely the motor will
overheat.
If the motor has to run for a prolonged time under these conditions,
special attention must be paid to cooling the motor. Use external
cooling for the motor if the temperature rise is too high.
NOTE!
A
1.10
!
Nominal voltage of the motor
Find this value V, from the nameplate of the motor.
This parameter sets the voltage at the field weakening
-
point, parameter
6.4, to 100% x V,,,tor
1.11 Nominal frequency of the motor
Find then nominal frequency f, from the nameplate of the motor.
This parameter sets the field weakening point, parameter 6.3, to the same value.
1.12
Nominal speed of the motor
Find this value nn from the nameplate of the motor.
1.13 Nominal current of the motor
Find the value In from the nameplate of the motor.
The internal motor protection function uses this value as a reference value.
1.14 Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2,4, 5, and 6. See table 3.4-l.
1.15 Parameter conceal
Defines which parameter groups are available:
0 = all parameter groups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
Page 3-6
Multi-step Speed Control Application
HV9000
1. 17 - 1. 23 Multi-step speed reference l-7
These parameter values define the Multi-step speeds selected with the DIA4, DIB5
and DIB6 digital inputs
These values are automatically limited between minimum and maximum frequency
(par. 1.1,1.2).
Speed Multi-step speed select
Multi-step speed select
:
Multi-step speed select 3
reference DIB4
DIB5
DIB6
Par. 1. 6 0
0
0
Par. 1. 17
1
0
0
Par. 1. 18
0 1
0
Par. 1.19 1
1
0
Par. 1. 20
0
0
1
1
0 1
0
1
1
1
1
1
Table 3.4-Z Selection
of multi-step speed reference
l-7.
HV9000
Multi-step Speed Control Application
Page 3-9
3.5 Special parameters, Groups 2-9
3.5.1 Parameter tables
Input signal parameters, Group 2
1=4--20mA
3 = Reduces act. and decel. times
4 = Reduces torque supervision limit
Note! u =
P
arameter value can be changed only when the drive is stopped.
Page 3-10
Multi-step Speed Control Application
HV9000
Group 3, Output and supervision parameters
code 1 Parameter
Range 1
Default Custom
1
Description
I
Paal
overheat warning
ad rotation direction
Note! m =
P
arameter value can be changed only when the drive is stopped.
HV9000
Multi-step Speed Control Application
Page 3-l 1
analog output inversion
3.24
3.25
l/O-expander board (opt.)
analog output minimum
l/O-expander board (opt.)
analog output scale
lo-1000% 1 1 Own
See parameter 3.5
3-22
O-l 1 0
See parameter 3.4
3-22
Group 4, Drive control parameters
code
4.1
4.2
4.3
4.4
4.5
Parameter
Acc./Dec. ramp 1 shape
Acc./Dec. ramp 2 shape
Acceleration time 2
Deceleration time 2
Brake chopper
Raw
0.6-10.0
0.0-10.0
Step
S
s
0.1 s
0.1 S
0.1 s
0.1 s
1
Default
0.0 s
0.0 s
10.0s
10.0s
0
Ct.&cm Description
0 = Linear
10 = S-curve acc./dec. time
0 = Linear
>O = S-curve acc./dec. time
Page
3-25
3-25
3-25
3-25
0.1-3000.0s
0.1-3000.0s
O-2
0 = Brake chopper
not in use
1 = Brake chopper in use
2 = External brake chopper
0 = Ramp
1 = Flying start
3-26
4.6
Start function
O-l
1
0
3-26
Note!m =
P
arameter value can be changed only when the drive is stopped.
Page 3-12
Multi-step Speed Control Application
HV9000
Page
3-26
3-26
code
4.7
4.6
4.9
4.10
Parameter
Stop function
DC-braking current
DC-braking time at Stop
Range
O--l
0.1+1.5x
lnw (A)
0.00-250.00s
Hz
step
1
0.1 A
0.01 s
0.1 Hz
0.01 s
Default
0
Custom Description
0 = Coasting
1 =
Ramp
0.5 x InHVc
0.00 s
1.5 Hz
0.00 s 0 = DC-brake is off at Start
0 = DC-brake is off at stop
3-26
3-26
3-26
t-
4.11
Turn on frequency of DC 0.1-10.0
brake durino ramo Stoo
DC-brake time at Start 0.0&25.00
Group 5, Prohibit frequency parameters
Cede
5.1
5.2
5.3
5.4
5.5
5.6
Parameter
Prohibitfrequency
ranoe 1 low limit
Prohibitfrequency
ranae 1 hiah limit
Prohibitfrequency
range 2 low limit
Prohibit frequency
range 2 high limit
Prohibit frequency
range 3 low limit
Pmhibit frequency
range 3 high limit
Range
frnm-
oar. 5.2
Step
0.1 Hz
Defauil
0.0H.z
Custom Description Page
3-26
1 fm;4,2j
1
f,,,-
par. 5.4
fnv-fInax
(1. 1) (1.2)
frnn-
par. 5.6
fnwrfnw
(1.1) (1.2)
1
1 I
O=Prohibitrangelisoff
I
3-261
1
0.1 Hz
/
0.1 Hz
0.1 Hz
0.1 Hz
0.0 Hz
l /
0 = Prohibit range 2 is off
I I
3-26
3-26
3-26
3-28 0 = Prohibit range 3 is of
Grou
6, Motor control parameters
Parameter
6.1
Motor control mode
m
Switching frequency 6.0 kHz 0.1 kHz 10/3.6 kHz
Range
C-l
Step
1
Default
0
Custom Description
0 = Frequency control
1 = Speed control
Dependant on Hp rating
Page
3-29
3-29
t=
1 6.2
6.3
1 6.4
V/Hz-curve. midpoin
6.7
6.6
6.9
Overvoltagecontroller
Undervoltagecontroller
&l
&l
Parameter maximum value =
0 = Controller is turned off
1 = Controller is operating
0 = Controller is turned off
1 = Controller is operating
Note! m = Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
Multi-step Speed Control Application
Page
3-l 3
2 = Fault, stop according to
Paae 3-l 4
Multi-step Speed Control Application
HV9000
Group 8, Autorestart parameters
Cc&
8.1
6.2
6.3
a.4
6.5
6.6
Parameter
Automatic restart:
number of tries
Automatic restart: multi
e
attempt maximum trial tims
Automatic restart:
start function
Automatic restart after
undelvoltage trip
Automatic restart after
overvoltage trip
Automatic restart after
overcurrent trip
Automatic restart after
reference fault trip
Automatic restart after
overlundertemperature
fault trip
0 = Ramp
1 = Flying start
O=No
1 =Yes
O=No
Iefault
I Qstom
Description
0 = not in use 3-36
1 =yes
O=No
1 = Yes
O=No
1 =Yes
O=No
1 =Yes
a.
7
a. a
Tab/e 3.5 1 Special parameters, Groups 2-8.
HV9000
Multi-step Speed Control Application
Page 3-15
3.5.2 Description of Groups 2-9 parameters
2.1 Start/Stop logic selection
0:
DIAl: closed contact = start forward
DIA2: closed contact = start reverse,
See figure 3.5-l.
Figure 3.5 1
Start forward/Start reverse.
0
0
0
1:
The first selected direction has the highest priority
When DlAl contact opens, the direction of rotation starts to change
If Start forward (DIAI) and start reverse (DIA2) signals are active
srmultaneously, the start forward signal (DIAI) has priority.
DIAl : closed contact = start
DIA2: closed contact = reverse
See figure 3.5-2.
open contact = stop
open contact = forward
Page
3-l 6
Multi-step Speed Control Application
HV9000
2:
DIAI : closed contact = start open contact = stop
DIA2:
closed contact = start enabled
open contact = start disabled
3:
3-wire connection
DIAl : closed contact = start pulse
DIA2: closed contact = stop pulse
(DIA3 can be programmed for reverse command)
See figure 3.53.
Figure 3.5-3
Start pulse /Stop pulse.
2. 2
DIAL3 function
1:
External fault. closina contact = Fault is shown and motor is stopped when
the contact is closed
2:
External fault, opening contact = Fault is shown and motor is stopped when
the input is open
3: Run enable
contact open
= Start of the motor disabled
contact closed
= Start of the motor enabled
4: Act. / Dee
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5:
Reverse
contact open
= Forward Can be used for reversing if
contact closed
= Reverse
II
parameter 2. 1 has value 3
6:
Jog speed
contact closed
= Jog speed selected for freq. refer.
7:
Fault reset
contact closed
= Resets all faults
8:
Acc./Dec. operation prohibited
contact closed
= Stops acceleration or deceleration until
the contact is opened
9:
DC-braking command
contact closed
= In Stop mode, the DC-braking operates
until the contact is opened, see figure 3.54.
DC-brake current is set with parameter 4.8.
See also param. 7.2!
HWOOO
Multi-steD SDeed Control
ADDkatiOII
Page
3-l 7
T
output
frequency
aram.
4. IO
RUN
STOP
“D009K32
DIA3 as DC-brake
4
command input and stop-mode = Ramp
I
D/A3 as DC-brake
UDO09K32
command input and stop-mode = Coasting
i
Figure 3.5-4
D/A3 as DC-brake command input:
a) Stop mode = Ramp,
b) Stop mode = Coasting.
2.3
V,” signal range
0 = Signal range 0-i 0
V
1 = Custom setting range from custom minimum (par. 2. 4) to custom
maximum (par. 2. 5)
2.4
2.5
V,” custom setting minimum/maximum
These parameters set Vi, for any input signal span within O-10 V.
Minimum setting:
Maximum setting:
Set the Vi, signal to its minimum level, select parameter 2.4,
press the Enter button
Set the Vi, signal to its maximum level, select parameter 2.5,
press the Enter button
Note!
The parameter values can only be set with this procedure (not with arrow up/
Page 3-l
a
Multi-step Speed Control Application
HV9000
arrow down buttons).
2.6
V,”
signal inversion
1:
V,,, is source B frequency
reference, par. 1. 6 = 1 (default)
Parameter 2. 6 = 0, no inversion
of analog V,” signal
Parameter 2. 6 = 1, inversion
of analog V,” signal
Parameter
max. V,” signal = minimum set
2 16
speed
i_ ~ i
I
$+
min. V,n signal = maximum set
0
Param. 2.4
Param. 2.5
io v
ChOlPMS
speed
Vgure
3.5-5
Vi0 no signal inversion
nput frequency
1
Par 24
Figure 3.5-6
V, signal inversion.
2.7
V,” signal filter time
%
.
Filters out disturbances from the
signal
incoming analog V,, signal. A
long filtering time makes drive
response slower. See figure 3.5-
7.
63%
!
t
F
L
Figure 3.5-7
I
Unfiltered
yn signal filtering.
HV9000
Multi-step Speed Control Application
Page
3-19
2.8 Analog input Ii, signal range
O=O-20mA
I= 4-20 mA
2 = Custom signal span
See figure 3.5-8.
2.9
2.10
Analog input I,, custom
setting minimum/maximum
With these parameters you can
scale the input current to
correspond to a minimum and
maximum frequency range. See
figure 3.5-8.
Minimum setting: Set the 1,” signal
to its minimum level, select
parameter 2. 9, press the Enter
button
Maximum setting:
Set the lin signal to its maximum
level, select parameter 2.10,
press the Enter button
Note! The parameter values can
only be set with this procedure
(not with arrow up/arrow down
buttons).
I
I
Figure 3.5-8 Analog inpuf I, scaling.
2.11 Analog input Iin inversion
1,” is source A frequency
reference, par. 1. 5 = 0 (default)
Parameter 2. 11 = 0, no
inversion of I,“input
Parameter 2. 11 = 1, inversion
of I,“input, see figure 3.5-9.
max. 1,” signal = minimum set
speed
min. 1,” signal = maximum set
speed
Figure 3.5-9
I, signal inversion.
2.12 Analog input 1,” filter time
Filters out disturbances from the
incoming analog lin signal. A long
filtering time makes drive response
slower. See figure 3.5-l 0.
-I
Par. 2. 12
figure 3.5 10
Analog input /in filter time.
Page 3-22
Multi-step Speed Control Application
HV9000
3.1
Analog output function
See
table for parameter 3.1 on
page 3-9.
UnfWxed signal
3.2
Analog output filter time
Filters the analog output signal.
See figure 3.5-17.
3.3
Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
-I
Par. 3.2
Figure
3.5- 17
Analog output filtering.
3.4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4 mA (living
zero). See figure 3.5-l 9.
Figure 3.5 18 Analog output invert.
3.5
Analog output scale
Scaling factor for analog output.
See figure 3.5-19.
Max. speed (n~xf,JfJ
2 x Tm,
2 x pm,
100% x v”M,
1000v
Figure
3.&i- 19
Analog output scale.
Page 3-24
Multi-step Speed Control Application
HV9000
3.13
Torque limit
,
supervision function
0 = No
supervision
1 = Low limit supervision
Par.
3.9 =
2
2 =
High limit supervision
f
f[W
If the calculated torque value goes
under/over the set limit (3.14) this
function generates a warning
message via the digital output
DO1 or via a relay output
ROl or
R02 depending on the settings of
the parameters 3. 6-3.8.
Figure 3.5-20 Output frequency supervision
3.14
Torque limit
,
supervision value
The calculated torque value to be supervised by the parameter 3.13.
Torque supervision value can be reduced below the setpoint with al free analog input
signal, see parameters 2.18 and 2.19.
3.15
Reference limit
,
supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3. 16) this function generates a
warning message via the digital output DO1 and via a relay output ROI or R02
depending on the settings of the parameters 3.6-3.8. The supervised reference is
the current active reference. It can be the source A or B reference depending on DIB6
input or the panel reference if the panel is the active control source.
3.16
Reference limit
,
supervision value
The frequency value to be supervised bv the oarameter 3. 15.
3.17
External brake-off delay
3.18
External brake-on delay
The function of the external brake
can be delayed from the start and
stop control signals with these
parameters. See figure 3.5-21.
YDDlN
The brake control signal can be
w
programmed via the digital output
DO1 or via one of the relay outputs
ROl and R02, see parameters 3.
6-3.8.
Figure 3.5-21
External brake control:
a) StarVStop logic selection par.
2.1=0, lor2
b) Start/Stop logic selection par.
2. 1 = 3.
HV9000
Multi-step Speed Control Application
Page 3-25
3.19
Drive temperature limit supervision
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the unit goes under/over the set limit (3. 20) this function
generates a warning message via the digital output DO1 or
via
a relay output ROI or
R02 depending on the settings of the parameters 3. 6-3.8.
3.20 Drive temperature limit value
The temperature value to be supervised by the parameter 3. 19.
4.1
4.2
AcclDec ramp 1 shape
AcclDec ramp 2 shape
The acceleration and deceleration ramp shape can be programmed with these
parameters.
Setting the value = 0 gives you a linear ramp shape. The output frequency immediately
follows the input with a ramp time
set by parameters 1. 3,l. 4 (4. 3,
4. 4 for Acc/Dec time 2).
t
[Hz1
Setting 0.1-10 seconds for 4. 1
(4.2) causes an S-shaped ramp.
The speed changes are smooth.
Parameter 1. 3/ 1. 4 (4. 3/ 4. 4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure 3.5-
22.
~+I-
8’
/’
1
1.3.1.4 _
(4.3.4.4)
:
I
~
1-I
4. 1 (4.2)
,
‘d
4. 1 (4. 2)
I
hl
"DM)OKzO
Figure 3.5-22
S-shapedacceleration/
4.3
4.4
Acceleration time 2
Deceleration time 2
These values correspond to the time required for output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possibile to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2.2. Acceleration/deceleration times can be reduced
with a free analog input signal. See parameters 2. 18 and 2. 19.
deceleration
Page 3-26
Multi-step Speed Control Application
HV9000
4.5 Brake chopper
0 = No
brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor, the energy stored in the inertia of the motor
and the load is fed into the external brake resistor. If the brake resistor is selected
correctly the drive is able to decelerate the load with a torque equal to that of
acceleration. See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may cause prolonged
acceleration times).
Flying start:
1
The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7
Stop function
Coasting:
0
The motor coasts to an uncontrolled stop with the HV9000 off, after the Stop
command.
Ramp:
1
After the Stop command, the speed of the motor is decelerated according
to the deceleration ramp time parameter. If the regenerated energy is high it
may be necessary to use an external braking resistor for faster
deceleration.
4.8
DC braking current
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4. 7. See figure 3.5-23.
0
DC-brake is not used
ro
DC-brake is in use depending on the setup of the stop function
(param. 4. 7). The time is set by the value of parameter 4. 9:
HV9000
Stop-function
Multi-steo Weed Control
ADDkatiOn
= 0 (coastinak
Page
3-27
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .ll), the value of
parameter 4.9 determines the braking time. When the frequency is I 10% of the
nominal, the braking time is 10% of the set value of parameter 4.9.
Stop-function = 1 (ramp):
After a Stop command, the speed of the motor is reduced based on the deceleration
ramp parameter. If no regeneration occurs due to load inertia DC-braking starts at a
speed defined by parameter 4. 10.
output frequency
, Motor speed
fn
I /
output frequency
, = 1 Y par 4.9
Figure 3.5-23
DC-braking
time when stop = coasting.
The braking time is defined with
parameter 4.9.
If a high inertia exists it is
recommended to use an external
braking resistor for faster
deceleration. See figure 3.5-24.
4.10
Execute frequency of DC-
brake during ramp Stop
See
figure 3.5-24.
Figure 3.5-24
DC-braking time when stop
function = ramp.
Page 3-26
Multi-step Speed Control Application
HV9000
4.11
DC-brake time at start
0
DC-brake
is not used
ro
DC-brake is active when the
start command is given. This
parameter defines the time
before the brake is released.
After the brake is released,
the output frequency
increases according to the
set start function parameter
! Par4.11:
4. 6 and the acceleration
I-
parameters (1.3,4.1 or 4.2,
4.3). See figure 3.5-25.
Figure 3.525 DC-braking time at start
5. l- 5.6 Prohibit frequency area
Low limit/High limit
I
4
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance
problems.
With these parameters it is
possible to set limits for three “skip
frequency” regions between 0 Hz
and 500 Hz. The accuracy of the
setting is 0.1 Hz. See figure 3.5-26.
Figure 3.526 Example of prohibit frequency
area setting.
HV9000
6.1
Multi-step Speed Control Application
Page 3-29
Motor control mode
0 = Frequency control: The I/O terminal and panel references are frequency
(V/Hz) references and the drive controls the output frequency (output
freq. resolution 0.01 Hz)
1 = Speed control: The I/O terminal and panel references are speed references
(sensortess vector) and the drive controls the motor speed (control accuracy *
0.5%).
6.2 Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHz ~-40 Hp) check
the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter 5.2 of the
User’s Manual.
6.3
6.4
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage
reaches the set maximum value. Above that frequency the output voltage remains
at the set maximum value.
Below that frequency output voltage depends on the setting of the V/Hz curve
parameters 1.8, 1.9, 6.5, 6. 6 and 6. 7. See figure 3.5-27.
When the parameters 1. 10 and 1. 11, nominal voltage and nominal frequency of
the motor are set, parameters 6. 3 and 6.4 are also set automatically to the
corresponding values. If you need different values for the field weakening point
and the maximum output voltage, change these parameters after setting
parameters 1. 10 and 1. 11.
6.5
V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1. 8, this
parameter defines the middle frequency point of the curve. See figure 3.5-27.
6.6
V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this
parameter defines the middle point voltage (% of motor nominal voltage) of the
curve. See figure 3.527.
6.7
Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this
parameter defines the zero frequency voltage of the curve. See figure 3.5-27.
Page 3-30
Multi-step Speed Control Application
HV9000
I
Parameter
“”
UM
6.4
i
Parameter 6.6
Default 10%
Parameter 6.7
Default 1.3 %
Parameter 6.5 Parameter 6.3 qHz]
(Default 5 Hz)
Figure 3.5-27 Programmable V/Hz curve.
6.6
Overvoltage controller
6.9
Undervoltage controller
These
parameters allow the ovedundervoltage controllers to be switched ON or
OFF.
This may be useful in
cases where the utility
supply voltage varies
more than -15%-
+10% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/undervoltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undetvoltage trips may occur when controllers are not used.
7.
1 Response to the reference fault
0 = No
response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA. The information can also be
programmed via digital output DO1 and via relay outputs R01 and
R02.
7.2 Response to external fault
0 = No
response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3. The information can also be programmed into digital output
DO1 and into relay outputs ROl and R02.
7.3
Phase supervision of the motor
0 = No
action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
HV9000
Multi-step Speed Control Application
Page 3-31
7.4
Ground fault protection
0 = No
action
2 =
Fault
Ground fault protection ensures that the sum of the motor phase currents is zero.
The standard overcurrent protection is always working and protects the frequency
converter from ground faults with high current levels.
Parameters 7.5-7.9
General
Motor thermal protection
Motor thermal protection is to protect the motor from overheating. The HV9000 drive
is capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that motor will be thermally overloaded. This is true
especially at low frequencies. With low frequencies the cooling effect of the motor
fan is reduced and the capacity of the motor is reduced. If the motor is equipped
with a separately powered external fan, the load derating at low speed is small.
Motor thermal protection is based on a calculated model and it uses the output
current of the drive to determine the load on the motor. When the motor is powered
from the drive, the calculated model uses the heatsink temperature to determine
the initial thermal state of the motor. The calculated model assumes that the ambient
temperature of the motor is 40°C.
Motor thermal protection can be adjusted by setting several parameters. The thermal
current IT specifies the load current above which the motor is overloaded. This
current limit is a function of the output frequency. The curve for IT is set with
parameters 7.6,7.7 and 7.9, refer to the figure 3.5-28. The default values of these
parameters are set from the motor nameplate data.
With the output current at IT the thermal stage will reach the nominal value (100%).
The thermal stage changes with the square of the current. With output current at
75% of IT the thermal stage will reach 56% and with output current at 120% of IT the
thermal stage would reach 144% The function will trip the drive (refer par. 7. 5) if
the thermal state reaches a value of 105%. The response time of the thermal stage
is determined by the time constant parameter 7.8. The larger the motor, the longer
it takes to reach the final temperature.
The thermal state of the motor can be monitored through the display. Refer to the
table for monitoring items. (User’s Manual, table 7.3-1).
CAUTION!
A
!
The calculated
mode/ does not protect the motor if the cooling of the
motor is reduced either by blocking the airflow or due to dust or dirt.
Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is selected, the drive will stop and activate the fault stage.
7.5
HV9000
7.8
Multi-step Speed Control Application
Motor thermal protection, time constant
Page
3-33
This time can be set between 0.5-300 minutes. This is the thermal time constant
of the motor. The larger the motor the greater the time constant. The time constant
is defined as the time that it takes the calculated thermal stage to reach 63% of its
final value.
The motor thermal time is specific to a motor design and it varies between different
motor manufacturers.
The default value for the time constant is calculated based on the motor nameplate
data from parameters 1 .12 and 1 .13. If either of these parameters is reset, then this
parameter is set to default value.
If the motor’s ts -time is known (given by the motor manufacturer) the time constant
parameter could be set based on ts -time. As a rule of thumb, the motor thermal
time constant in minutes equals to 2xte (te in seconds is the time a motor can safely
operate at six times the rated current). If the drive is stopped the time constant is
internally increased to three times the set parameter value. Cooling in the stop
stage is based on convection with an increased time constant.
7.9
Motor thermal protection, break point frequency
The frequency can be set between IO-500 Hz. This is the frequency break point of
the thermal current curve. With frequencies above this point, the thermal capacity of
the motor is assumed to be constant. See figure 3.5-28.
The default value is based on the motor’s nameplate data, parameter 1. 11. It is 35
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the
frequency at the field weakening point (parameter 6.3). Changing either parameter
1. 11 or 6. 3 will restore this parameter to its default value.
7.10
Stall protection
Operation:
0 =
Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is set on, the drive will stop and activate the fault stage. Setting the parameter
to 0 will deactivate the protection and will reset the stall time counter to zero.
Figure 3.5-29
Calculating motor temperature.
Paoe 3-34
Multi-steD SDeed Control Awlication
HV9000
Parameters 7. lo- 7.13, Stall protection
General
Motor stall protection protects the motor from short time overload situations like a
stalled shaft. The reaction time of stall protection can be set shorter than with motor
thermal protection. The stall state is defined with two parameters, 7.11. Stall Current
and 7.13. Stall Frequency. If the current is higher than the set limit and output
frequency is lower than the set limit the stall state is true. There is actually no real
indication of the shaft rotation. Stall protection is a type of overcurrent protection.
7.11
Stall current limit
The current can be set between O.O-200% x InMotor.
In a stall the current has to be above this limit. See figure 3.5-30. The value is set as
a percentage of the motor’s nameplate nominal current, parameter 1.13. If parameter
1. 13 is adjusted, this parameter is automatically restored to its default value.
7.12
Stall time
t1
1
The time can be set between
2.0-l 20 s. This is the maximum
allowed time for a stall. There is
an internal up/down counter to
count the stall time. See figure
Stall area
I
3.5-31. If the stall time counter
value goes above this limit the
protection will cause a trip (refer
Par. 7.
11
to parameter 7. 10).
7.13 Maximum stall frequency
The frequency can be set
between l-f,,X (parameter 1.
2).
In a stall, the output frequency
Figure 3.5-30 Setting the stall
characteristics.
has to be smaller than this
figure 3.530.
Stall time counter
1
Parameters 7.14- 7.17
Underload protection, General
Trip area
The purpose of motor underload
Par. 7. 12
protection is to ensure that there
I
is load on the motor while the
Tripiwarnlng
par. 7.
10
drive is running. If the motor load
is reduced, there might be a
problem in the process, e.g.
I-
broken belt or dry pump.
Motor underload protection can
be adjusted by setting the
underload curve with parameters
7.15 and 7.16. The underload
curve is a squared curve set
F@ure 3.5-31
Counting the stall time.
between zero frequency and the
HWOOO
Multi-step Speed Control Application
Page
3-35
field weakening point. The protection is not active below 5Hz (the underload
counter value is stopped). See figure 3.5-32.
The torque values for setting the underload curve are set with percentage values
which refer to the nominal torque of the motor. The motor’s nameplate data,
parameter 1. 13, the motor’s nominal current and drive’s nominal current Icr are
used to find the scaling ratio for the internal torque value. If other than a standard
motor is used with the drive, the accuracy of the torque calculation is decreased.
7.14
Underload protection
Operation:
0 = Not in use
1 = Warning
2 = Fault
Tripping and warning will give a display indication with the same message code. If
tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection, by setting this parameter to 0, will reset the underload
time counter to zero.
7.15
Underload protection, field weakening area load
The torque limit can be set between 20.0-l 50 % x TnMotor.
This parameter is the value for the minimum allowed torque when the output
frequency is above the field weakening point. See figure 3.5-32. If parameter 1.13 is
adjusted, this parameter is automatically restored to its default value.
7.16
Underload protection, zero frequency load
50 % x TnMotor. The torque limit can be set between 10.0-l
This parameter is the value for the minimum allowed torque with zero frequency.
Refer to the figure 3.5-32. If parameter 1.13 is adjusted this parameter is automatically
restored to its default value.
7.17
Underload time
s. This time can be set between 2.0-600.0
This is the maximum allowed time for an underload state. There is an internal up/
down counter to accumulate the underload time. Refer to the figure 3.5-33.
If the underload counter value goes above this limit, the protection will cause a trip
(refer to the parameter 7. 14). If the drive is stopped, the underload counter is reset
to zero.
Figure
3.5-32 Setting
of minimum load.
Figure 3.5-33 Counting the underload time
Page 3-36
Multi-step Speed Control Application
HV9000
8.1
Automatic restart: number of tries
8.2
Automatic restart: trial time
The Automatic restart function restarts the drive after the faults selected with
parameters 8. 4 - 8. 8. The Start function for Automatic restart is selected with
parameter 8.3. See figure 3.5-34.
f
Number of faults
4
I
I
kil
,
I
Three faults
Four faults
Figure 3.5-34 Automatic restart.
Parameter 8.1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The time counting starts from the first autorestart. If the number of restarts does not
exceed the value of the parameter 8.1 during the trial time, the count is cleared after
the trial time has elapsed. The next fault starts the counting again.
8.3
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
8.4
Automatic restart after undervoltage trip
0 = No automatic restart after undervoltage fault
1 = Automatic restart after undervoltage fault condition returns to the
normal condition (DC-link voltage returns to the normal level)
8.5
Automatic restart
after overvoltage trip
0 = No
automatic restart after overvoltage fault
1 = Automatic restart after overvoltage fault condition returns to the
normal condition (DC-link voltage returns to the normal level)
8.6
Automatic restart after overcurrent trip
0 = No automatic restart after overcurrent fault
1 = Automatic restart after overcurrent faults
HWOOO
8.7
Multi-step Speed Control Application
Automatic restart after reference fault trip
Page 3-37
0 = No automatic restart after reference fault
1 = Automatic restart after analog current reference signal (4-20 mA)
returns to the normal level (24 mA)
a.8
Automatic restart after over-/undertemperature fault trip
0 = No automatic restart after temperature fault
1 = Automatic restart after heatsink temperature has returned to its
normal level between -1 O”C-+75”C.
Notes:
Page 3-38
Multi-step Speed Control Application
HV9000
Notes:
HV9000
PI-control Application
Page 4-1
PI-CONTROL APPLICATION
(par. 0.1 = 5)
CONTENTS
4 PI-control Application
......................
.4-l
4.1 General
.......
.
................................
4-2
4.2 Control l/O..
.................................
.4-2
4.3
Control signal logic.. ..................... 4-3
4.4
Parameters Group 1
...................
.4-4
4.4.1 Parameter table
.................
.4-4
4.4.2 Description of 4- 5
4.5
Special parameters, Groups 2-8.. 4-8
4.5.1 Parameter tables .................. 4-8
4.5.2 Description of Groups..
......
.4-l 5
4.6
Panel reference ........................... .4-36
4.7
Monitoring data. ............................ 4-36
Page 4-2
PI-control Application
HWOOO
4.1 General
In PI-control application there are two I/O-
terminal control sources. Source A is the PI-
controller and source B is the direct frequency
reference. The control source is selected with
DIB6 input.
The PI-controller reference can be selected
from an analog input, motorized (digital)
potentiometer or panel reference. The actual
4.2 Control I/O
value can be selected from the analog inputs
or from mathematical functions of the analog
inputs.
The direct frequency reference can be used
for control without the PI-controller. The
frequency reference can be selected from
analog inputs or panel reference.
l
NOTE! Remember to connect CMA and
CMB inputs.
PI-controller
--
Figure 4.2- 1 Default I/O configuration and connecfion example of the
PI-Control Application with Z-wire transmirter.
Page 4-4
4.4 Basic parameters, Group 1
4.4.1 Parameter table, Group 1
code
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
V/Hz ratio selection
+2
Deceleration time 1
PI-control Application HV9000
Default
OH.?
Custom Description IPee
Time from f,,, (1.1) to f,,, (1.2)
I
4-5
1
0.1-3000.0 s
1
0.1 s Time from f,,, (1.2) to f,,, (1. 1)
1
1
dl
“‘Output con limit [A] of the unit 4-5
4-5
1.9 4-6
1.10
,:
1.11
f, from the nameplate of
the motor
n, from the nameplate of
the motor
I, from the nameplate of
the motor
Supply
voltage
mI=+
360-400
366-500
525-690
Parameterconceal
230 V
36OV
460 v
575v
( 1
4-7
1.12
4-7
4-7
I
I
I
I
I
Voltage code 2
Voltage code 4
I
4-7
I
Voltage code 5
Voltage code 6
Visibility of the parameters:
0 = All parameter groups visible
1 = Only group 1 is visible
Disables parameter changes:
0 = Changes enabled
1 = Changes disabled
I
1
-1
O
0
I
4-7
1.16 Parametervaluelock
/
(tl
/
1
4-7
Tab/e 4.4- 1 Group 1 basic parameters.
* If 1. 2 > motor synchr. speed, check suitability
for motor and drive system.
Selecting 120 Hz/500 Hz range see page 4-5.
** Default value for a four pole motor and a
nominal size HV9000.
*** Up to MlO. Bigger classes case by case
Note! m =
Parameter value can
be
changed
only when the drive is stopped.
HV9000 PI-control Aoolication
Page 4-5
4.4.2 Description of Group 1 parameters
1.1,1.2
Minimum
I
maximum frequency
Defines frequency limits of the HV9000.
The default maximum value for parameters 1. 1 and 1.2 is 120 Hz. By setting 1.2
= 120 Hz when the drive is stopped (RUN indicator not lit) parameters 1.1 and 1.
2 are changed to 500 Hz. At the same time the resolution of the panel is changed
from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting parameter 1.2
= 119 Hz while the drive is stopped.
1.3,1.4
Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to acceler-
ate from the set minimum frequency (par. 1. 1) to the set maximum frequency
(par. 1.2).
1.5
PI-controller gain
This parameter defines the gain of the PI-controller.
If this parameter is set to 1 OO%, a 10% change in error value causes the controller
output to change by 1 .O Hz.
If the parameter value is set to 0, the PI-controller operates as an l-controller.
1.6
1.7
PI-controller I-time
Defines the integration time of the PI-controller
Current limit
This parameter determines the maximum motor current that the HV9000 will pro-
vide short term.
A
0
1.8
V/Hz ratio selection
Linear:
0
The voltage of the motor changes linearly with the frequency in the con-
stant flux area from 0 Hz to the field weakening point
(par. 6.3) where a constant voltage (nominal value) is supplied to the
motor. See figure 4.4-2.
A linear V/Hz ratio should be used in constant torque applications.
This default setting should be used if there is no special requirement for
another setting.
Squared:
The voltage of the motor changes following a squared curve form with
1
the frequency in the area from 0 Hz to the field weakening
point (par. 6.3) where the nominal voltage is supplied to the motor. See
figure 4.4-2.
The motor runs undermagnetized below the field weakening point and produces
less torque and electromechanical noise. A squared V/Hz ratio can be used in
applications where the torque demand of the load is proportional to the square of
the speed, e.g. in centrifugal fans and pumps.
Page
4-6
PI-control Application
HV9000
Default: Nominal voltage of
Field weakening point
the motor
Default: Nominal
frequency of the
motor
- WI
1
Figure
4.4-2
Linear and squared V/Hz curves
Programm.
The V/Hz curve can be programmed with three different points.
V/Hz curve
The parameters for programming are explained in chapter 4.5.2.
2
A programmable V/Hz curve can be used if the standard settings do
not satisfy the
needs of the application. See figure 4.4-3.
UM
Parameter
“”
f
Default: nominal /I
6.4
voltage of the mot
Parameter 6.6
Default 10%
Parameter 6.7
Default 1.3 %
Parameter 6.5 Parameter 6.3 f[Hz]
(Default 5 Hz)
Figure 4.4-3
Programmable V/Hz curve.
1.9
V/Hz optimization
Automatic
The voltage to the motor changes automatically which makes the
torque
motor produce enough torque to start and run at low frequencies.
boost
The voltage increase depends on the motor type and horsepower.
Automatic torque boost can be used in applications where starting torque due to
starting friction is high, e.g. in conveyors.
NOTE!
In
high torque -low speedapplications - it is likely the motor will overheat.
If the motor has to run for a prolonged time under these conditions, special
attention must be paid to cooling the motor. Use external cooling for the
motor if the temperature rise is too high.
HV9000 PI-control
Nominal voltage of the motor
ADDfication
Paae 4-7
1.10
Find
this value V”from the nameplate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6. 4, to
100% x Vnmotor.
1.11
Nominal frequency of
the
motor
Find the nominal frequency f,, from the nameplate of the motor.
This parameter sets the frequency of the field weakening point, parameter 6. 3, to
the same value.
1.12
1.13
Nominal speed of the motor
Find this value nn from the nameplate of the motor.
Nominal current of the motor
Find the value In from the nameplate of the internal motor protection
function uses this value as a reference value.
1.14
Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2, 4, 5 and 6. See table 4.4-l
1.15
Parameter conceal
Defines which parameter groups are available:
0 = all parametergroups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
To adjust more of the functions of the PI-Control application, see chapter 4.5 to
modify the parameters of Groups 2-6.
Page 4-8
PI-control ADDlication
HV9000
4.5 Special parameters, Groups 2-9
4.5.1 Parameter tables
Group 2, Input signal parameters
-
code
!. 1
ammeter
ilA2 function
erminal9)
m
-
)efault
1
Iescription
PZ
w
4
I= Not used
I =
Ext. fault, closing contact
! = External fault, opening contact
3 = Run enable
1 =Acceler./deceler. time selectior
I
j = Reverse
3 = Jog speed
7 = Fault reset
3 = . operation prohibit
3 = DC-braking command
IO = Motor (digital) pot. UP
I= Not used
I =
Ext. fault, closing contact
! = External fault, opening contact
3= Run enable
1= Acc./dec. time selection
5 = Reverse
3 = Jog speed
7 = Fault reset
3 = . operation prohibit
3 = DC-braking command
10 = Motor (digital) pot. DOWN
3=&1OV
1 = Custom setting range
Range
O-10
3?p
-
1
-15
2.2
bIA3function
erminall0)
&lo
1 7
4 -16
2.3
2.4
-
IIn signal range
rln custom setting min.
I,” custom sethng max
I,, signal inversion
I,, signal filter time
,” signal range
4 -1c
4 -1f
-
4 .-lf
0 = Not inverted
1 = Inverted
0 = No filtering
O=&-20mA
1=4_20mA
2 = Custom setting range
4 .-lf
-
4 .-li
4 .-li
-
.-1;
4
4 .-1;
,” custom setting min.
,” custom
setting max.
1,” signal inversion
I” signal filter time
)IB5function
terminal 15)
•I
.Ol -10.00
o-9
3.01S
1
0 = Not inverted
1 = Inverted
0.10s
6
0 = No filtering
4 ,1;
4 I-11
-
4
I-lf
0 =
Not used
1 = Ext. fault, closing contact
2 = External fault, opening contac
t
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jog speed
7 = Fault reset
6 = Act idec. operation prohibit
9 = DC-braking command
-
Note! m =
P
arameter value can be changed only when the drive is stopped
HV9000
PI-control Application
Page 4-9
3 = Signal from internal motor pot.
reference, source B
1 = Analog current input (term. 4)
2 = Sat
reference
from the panel
3 = Signal from internal motor pot.
4 = Signal from internal motor pot.
Note! m =
P arameter
value can be changed only when the drive is stopped
Page
4-l 0
PI-control Application
HV9000
Group 3, Output and supervision parameters
3ustm
I
Analog output function
1111111
Description
( )= Not used
1
I =
O/P frequency
! =
Motor speed
:
3 = O/P current
1
1= Motor torque
5 = Motor power
t
j = Motor voltage
7 = DC-linkvolt.
PZ
cle
4. .21 Scale 100%
(c+f,&
(0-max. speed)
(o-2.0 x t”Hv9)
(o-2 x T,,u.,,)
(&2 x P,,&
(O-100% xVnMb
,)
(0-1000 V)
4 -21
0 = Not inverted
1 = Inverted
O=OmA
1=4mA
4 -21
4 -21
4 -21
(
3 = Not used
-
4nalog output filter time
Analog output inversion
Analog output minimum
4naloq output scale
3.6
3igital output function
I
1 = Ready
2=Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
,
6 = External fault or warning
7 = Reference fault or warning
6 = Warning
9 = Reversed
10 = Jog speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 =Torque limit supervision
16 = Reference limit supervision
17 = External brake control
16 = Control from I/O terminals
19 = Drive temperature limit
supervision
20 = Unrequested rotation directior
21 = External brakecontrol invelte ;
O-21
&21
o-2
1
4 m
3.7
3.6
3.9
Relay output 1 function
I
Relay output 2 function
I
Outputfreq. limit 1
supervwon function
Output freq. limit 1
supervision value
2
3
0
As parameter 3.6
As parameter 3.6
O=No
1 = Low limit
2 = High limit
4 t-2:
4 .-2:
1-2:
4
1
1
3.1c
0.6-f,,
(par. 1.2)
1.1 H
-
0.0 Hz
-
1
1-2:
-
Note! a =
P arameter value can be changed only when the drive is stopped.
HV9000
PI-control Application Page 4-11
3.12
0
I I
I I
O=No
1 = Low limit
2 = Hiah limit
Torque limit 00.0%
I I
4-23
I I
4-23
3.23
3.24
3.25
0
0
100%
See parameter 3.2
See parameter 3.3
See parameter 3.4
See parameter 3.5
4-21
4-21
4-21
4-21
Group 4, Drive control parameters
Note! m =
P
arameter value can be changed only when the drive is stopped.
Page 4-l 2
PI-control Awlication
I
I
Ranae
-
0.15-1.5x
I~HVS (A)
HV9000
I
code
I
Parameter
I steo I
Default
I custom
Description
I ’ I O I
0 = Coasting
1 =
Ramp
Page
4-25
4-25
I
4.7
I
4.6
4.9
4.10
Stop function
DC-braking current
I
0.01 s
0.00 s
15Hz
I
0 = DC-brake is off at Stop 4-25
4-26
DC-braking timeat stop
Turn on frequency of
DC-brake at rams Stoo
0.00-250.00s
I I
/ 4.11
4.12
I
1
-25.00s
/
/
0.01 s 1 0.00s
I
1
0 = DC-brake is off at Start 4-27
4-27
1
DC-braketimeatStart
Jog speed reference
I I
5. 1
5.2
5.3
0.1 Hz 1
Group 5, Prohibit frequency parameters
I code1
Parameter
Prohibitfrequency
range 1 low limit
Prohibitfrequency
range2 high limit
Prohibit frequency
range 2 low limit
Prohibitfrequency
range 2 high limit
Prohibitfrequency
ranae 3 low limit
Prohibit frequency
range 3 high limit
I Range
f,,,-
par. 5. 2
fnNrfln,x
(1.1)(1.2)
fInI”_
par. 5.4
fnw-f,,x
(1.1) (1.2)
frlw-
par. 5. 6
fnw-fmax
(1.1)(1.2)
0.1 Hz 0.0H.z
Description
I Page I
1 4-27
1
3 = no prohibit frequency range
:
I I
I 4-271
5.4
5.5
5.6
I 1
41
41
1
Descriptum
0 = no prohibit frequency range
0 = no prohibit frequency range
Group 6, Motor control parameters
I
code/
Parameter
6.1
6.2
6.3
6.4
6.5
Motor control mode
Switchinq freauencv
Field weakening
Voltage at field
weakening point
V/Hz-curve
;;,:/;,Enid
Output voltage at
mid
a
fl
poi
1 ~anae 1 Steo
I
Default
I
Custom
I
Paael
4-27
427
0 = Frequency control
1 = Speed control
1.0-16.0 kHz
3&500
1%200%
11111 x V,,,t
o.(Mm=
;,O%
0.1 Hz
0.01%
0.0 Hz
0.00%
Parameter maximum value =
param.
6.4
Hz
0.1 kHz 10/36kHz
1 Hz
1%
Param.
1.11
100%
Depends on HP ratinq
4-28
4-28
4-26
4-28
4-28
0 = Controller is not operating
1 = Controller is in operation
4-28
4-28
point frequency
6.6
6.7
6.8
6.9 Undervoltagecontroller C&l 1 1 0 = Controller is not operating
1 = Controller IS in operation
Note!m=
Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
code
7.1
Parameter
Response to
reference fault
PI-control Application
Page 4-l 3
Step
1
I
Lefault
0
2
2
2
2
CUStCfll
Description
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3 = Fault, always coasting stop
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3= Fault, always coasting stop
7.2 Response to
external fault
7.3
7.4
7.5
Phase supervision of
the motor
Ground fault protection
Motorthermal protection
O--2
&2
c-2
1
4
t
%
0.5
min.
1 Hz 35 Hz
s
1 Hz
25Hz
0 = No action
2 = Fault
0 = No action
2 = Fault
0 = No action
1 = Warning
2 = Fault
1
Page
4-29
4-29
4-29
4-29
4-30
i
4-30
4-30
Motorthermal protection
breakpoint current
Motorthermal protection
zero frequency current
Motorthermal protection
time constant
Motorthermal protection
break point frequency
Stall protection
io.+150.0
5.0-150.0%
x
hOTOR
x I”MOTOR
0.5-300.0
minutes
1 o--500 Hz
O-2
Default value is set according
to motor nominal current
4-31
4-31
0 = No action
1 = Warning
2 = Fault
Stall current limit
Stall time
5.+200.0%
x t”MOTOR
2.c-120.0
t-fInax
&2
1
0 = No action
1 = Warning
2 = Fault
7.15
7.1E
7.17
Underload pmt., field
weakening area load
Underload protection,
zero
frequency load
Underload time
0.&150,.09
x T~MOTOR
5.&-150.0%
~T,MOTOR
2.&-600.0 s
1 .O%
1.0%
1.0s 20.0s
I
50.0%
10.0%
-I
4-33
4-34
4-34
/
4-34J
Page4-14
PI-control Application
HV9000
Group 8, Autorestart parameters
a.7 Automatic restart after
reference fault trip
overhndeltemperature
fault trip
O-1
&l
1
1
0
0
O=No
1 =Yes
O=No
1 =Yes
4-35
4-35
a.8
Automatic restart after
Table 4.5- 7
Special
parameters,
Groups 2-8.
2024年8月28日发(作者:拱丰)
HV9000
3.1
Standard Application
Analog output function
See
table “Group 3, output and
supervision
page l-8.
parameters” on the
Page 1-15
I
%
t
Unfiltered signal
3.2
Analog output filter time
Filters the analog output signal.
See figure 1.58.
-I
Par.
3.
2
Figure 1.5-8 Analog output filtering.
3.3
Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
See figure 1.5-9
Figure 1.59
Analog oofput invert.
3.4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4
mA. See figure
1.510.
3.5
Analog output scale
Scaling factor for analog output.
See figure 1.5-l 0.
Max. speed (n,xf,,Jf,)
Figure 1.510 Analog output scale.
q
3.6
3.7
3.8
Page 1-16
Standard Application
HV9000
Digital output function
Relay output 1 function
Relay output 2 function
Setting value
0 = Not used
Signal content
Out of operation
Diaital outout DO1 sinks current and oroarammable
relav fR01, R02) is activated when:
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
6 = Warning
9 = Reversed
1 O= Multi-step speed selected
1 1 = At speed
12= Motor regulator activated
13= Output frequency superwsion
14= Control from I10 terminals
The drive is ready to operate
The drive operates
A fault trip has occurred
A fault trip has occurred
The heat-sink temperature exceeds +7O”C
Fault or warning depending on parameter 7. 2
Fault or warning depending on parameter 7. 1
-
if analog reference is 4-20 mA and signal IS <4mA
Always if a warning exists
The reverse command has been selected
A multi-step speed has been selected
The output frequency has reached the set reference
Overvoltage or overcurrent regulator was activated
The output frequency goes outside of the set super-
vision low limit/ high limit (par. 3. 9 and 3. 10)
Ext. control mode selected with progr. push-button #2
Tab/e 1.5-Z Output signals via DO 1 and output relays RO 1 and ROZ.
3.9
Output frequency limit supervision function
0 = No supervision
1 = Low limit supervision
2 =
High limit supervision
If the output frequency goes under/over the set limit (3. 10) this function generates
a warning message via the digital output DO1 and via a relay output ROl or RO2
depending on the settings of the parameters 3.6-3.8.
3.10
Output frequency limit supervision value
The frequency value to be supervised by the parameter 3. 9.
See figure 1.511.
fW1
par3,,0 ..~~~~~~~~~ ,~~~.__.._,_
Par. 3.9 = 2
‘/- *
Example: B ‘B &’
Figure 1.577
Output frequency supervision.
HV9000
4.1
4.2
Standard Application
Page 1-17
AcclDec ramp 1 shape
Acc/Dec ramp 2 shape
The acceleration
parameters.
and deceleration ramp shape can be programmed with these
L
Setting the value = 0 gives you a linear ramp shape. The output frequency
immediately follows the input with a ramp time set by parameters 1.3, 1.4 (4.3,4.
4 for Acc/Dec. time 2).
Setting 0.1-l 0 seconds for 4. 1
(4.2) causes an S-shaped ramp.
The speed changes are smooth.
Parameter 1. 3/ 1. 4 (4. 3/ 4. 4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure 1.5-
12.
f
WI
t
,’
I’
1
1.3,1.4 _
(4.3,4.4)
~
~
I
:t,i
4. 1 (4. 2)
/
I I
‘t):
I
4. 1 (4.2)
Id
"0009K20
-rgure is-12
S-shapedacceleratron/
deceleration.
4.3
4.4
Acceleration time 2
Deceleration time 2
These values correspond to the time required for the output frequency to change
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possibile to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2.2.
4.5
Brake chopper
0 = No
brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor, the energy stored in the inertia of the
motor and the load is fed into the external brake resistor. If the brake resistor is
selected correctly the drive is able to decelerate the load with a torque equal to
that of acceleration. See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may extend the
acceleration times).
Page 1-18
Standard Application
Flying start:
1
HV9090
The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7 Stop
function
Coasting:
0 The motor coasts to an uncontrolled
Stop command is issued.
stop with the HV9000 off, after the
Ramp:
1 After the Stop command is issued, the speed of the motor is decelerated
based on the deceleration ramp time parameter.
If the regenerated energy is high, it may be necessary to use an external
braking resistor for faster deceleration.
current
4.8
DC braking
Defines the current injected into the motor during DC braking.
4.9
DC braking time at stop
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4.7. See figure 1.5-13.
0
ro
DC-brake is not used
DC-brake is in use depending on the setup of the stop function
(param. 4. 7). The time is set by the value of parameter 4. 9:
= 0 (coasting): Stop-function
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .ll), the value
of parameter 4.9 determines the braking time. When the frequency is 5 10% of
the nominal, the braking time is 10% of the set value of parameter 4.9. See figure
1.5-l 3.
HV9000
Standard Application
Page 1-19
fn 7
S
P
e
:
fn
Output frequency
,,
Motor speed
Output frequency
”
*
*
~
RUN
STOP
Motor speed
DC-braking ON ‘1,
“”
t
*
.
__
DC-braking ON
t = 0 1 x par. 4.9
:
t
.
.
RUN
STOP
t = 1 xpar.4.9
“WOOKZI
Figure 1.513 DC-braking fime when stop = coasting.
StoD-function = 1 framol:
After a Stop command, the speed of the motor is reduced based on the deceleration
ramp parameter. If no regeneration occurs due to load inertia DC-braking starts at
0.5 Hz.
The braking time is defined by
par. 4.9. If the load has a high
inertia, use an external braking
resistor for faster deceleration.
See figure 1.514.
Figure 1.5-14 DC-braking time when stop
function = ramp.
5.1
5.2
Prohibit frequency area
Low limit/High limit
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance problems.
With these parameters it is
possible to set limits for one “skip
frequency” region between 0 Hz
and 120 Hz/500 Hz. Accuracy of
the setting is 0.1 Hz.
See figure 1.5-l 5.
t
[Hz1
Figure 1.5- I5 Example ofprohibit frequency
area setting.
Page
l-20
Standard Application
Motor control mode
0 =
Frequency control:
(V/Hz)
1 = Speed control:
(sensorless vector)
HV9000
6.1
The I/O terminal and panel references are frequency ref-
erences and the drive controls the output frequency (out-
put freq. resolution 0.01 Hz)
The I/O terminal and panel references are speed refer-
ences and the drive controls the motor speed (control
accuracy + 0.5%).
6.2
Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHzA40 Hp)
check the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter
5.2 of the User’s Manual.
6.3
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage reaches
the set maximum value (parameter 6. 4). Above that frequency the output voltage
remains constant at the set maximum value. Below that frequency the output voltage
depends on the setting of the V/Hz curve parameters 1. 8, 1. 9, 6. 5, 6. 6 and 6. 7.
See figure 1.5-16.
When the parameters 1. 10 and 1. 11, nominal voltage and nominal frequency of
the motor, are set, parameters 6.3 and 6. 4 are also set automatically to the same
values. If you need different values for the field weakening point and the maximum
output voltage, change these parameters after setting parameters 1. 10 and 1. 11.
6.4
6.5
V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle frequency point of the curve. See figure 1.5-16.
6.6 V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle voltage point of the curve. See figure 1.5-16.
6.7
Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1. 8, this
parameter defines the zero frequency voltage of the curve. See figure 1.5-16.
6.6
6.9
Overvoltage
Undervoltage
controller
controller
These parameters allow the over/undervoltage controllers to be switched ON or OFF.
This may be useful in cases where the utility supply voltage varies more than -15%-
+10% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/undervoltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undervoltage trips may occur when the controllers are not used.
HV9000
Standard Application
Page l-21
h
Parameter
6.4
“”
UM
Default: nominal
Parameter 6.6
Default 10% --
Parameter 6.7
Default 1.3 %
/
Default: nominal frequency
<
Parameter 6.5
(Default 5 Hz)
Parameter 6.3 f(Hz]
Figure
1.5-16
Programmable V/Hz curve.
7.1
Response to reference faults
0 = No response
1 = Warning
2 = Fault, stop mode after fault detection according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA.
The information can also be programmed via digital output DO1 and via relay
outputs ROl and R02.
7.2
Response to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault detection according to parameter
3 = Fault, always coasting stop mode after fault detection
4.7
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3.
The information can also be programmed
outputs ROl and R02.
7.3
into digital output DO1 and into relay
Phase supervision of the motor
0 = No action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
7.4
Ground fault protection
0 = No action
2 = Fault
Ground fault protection ensures that the sum of motor phase currents is zero. The
standard overcurrent protection is always present and protects the drive from ground
faults with high current levels.
Page l-22
Standard Application
HV9000
7.5 Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip
The motor thermal protection protects the motor from overheating. In the
Standard application the thermal protection has fixed settings. In other
applications it is possible to set the thermal protection parameters. A trip or a
warning will give an indication on the display. If trip is selected, the drive will stop
the motor and generate a fault.
Deactivating the protection by setting the parameter to 0 will reset the internal thermal
model to 0% heating.
The HV9000 is capable of providing
higher than nominal current to the
motor. If the load requires this high
current there is a risk that motor will
be thermally overloaded. This is
true especially at low frequencies.
With low frequencies the cooling
effect of the motor fan is reduced
and the capacity of the motor is
reduced. Motor thermal protection
is based on a calculated model and
it uses the output current of the
drive to determine the load on the
motor.
Overload area
IT
I
I
I
I
35 Hz
f WI
*
“UC”, ia
The thermal current Ir specifies
Figure 1.5- 17
Motor thermal current IT curve
the load current above which the
motor is overloaded. See figure
1.5-17. If the motor current is over the curve the motor temperature is increasing.
CAUTION! The calculated model does not protect the motor if the cooling of
the motor is reduced either by blocking the airflow or due to dust
or dirt.
Stall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
The Motor Stall protection provides a warning or a fault based on a short time overload
of the stalled shaft. The stall protection is faster than the motor thermal
protection. The stall state is defined with Stall Current and Stall Frequency. In the
Standard application they both have fixed values. See figure 1.5-l 8. If the current is
higher than the set limit and output frequency is lower than the set limit the stall
state is true. If the stall lasts longer than 15 s a stall warning is given on the display
panel. In the other applications it is possible to set the parameters of the Stall
protection function. Tripping and warning will give a display indication. If tripping is
set on, the drive will stop and generate a fault.
HV9000
Standard Application
Page l-23
Deactivating the stall protection by
setting the parameter to 0 will
reset the stall time counter to zero.
I
Stall area
L
Figure
1.5-18 Sal/state.
8.1
8.2
Automatic restart: number of tries
Automatic restart: trial time
The Automatic restart function will restart the drive after the following faults:
- overcurrent
-
overvoltage
-
undervoltage
-
over/under temperature of the drive
-
reference fault
Three faults
Figure 1.5-19 Automatic restart.
Parameter 8. 1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The count time starts from the first autorestart. If the number of restarts does not
exceed the value of the parameter 8.1 during the trial time, the count is cleared after
the trial time has elapsed. The next fault starts the counting again.
q
8.3
Notes:
Page l-24
Standard Application
.
HV9000
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
HV9000 Local/Remote Control Application
Page
2-l
LOCAL/REMOTE CONTROL APPLICATION
(par. 0.1 = 3)
CONTENTS
2 Local/Remote Control Application ..2-1
2.1
General .......................................
.2-2
2.2
Control I/O.. .................................
.2-2
2.3
Control signal logic.. .....................
2-3
2.4
Parameters Group 1
....................
2-4
2.4.1 Parameter table
.................. 2-4
2.4.2 Description of 2-5
2.5 Special parameters, Groups 2-8 2-8
2.5.1 Parameter tables 2-8
2.5.2 Description of Group 2 par.. 2-15
Page 2-2
Local/Remote Control Application
HV9000
2.1 General
By utilizing
the Local/Remote Control
Application, the use of two different control
and frequency reference sources is
programmable. The active control source is
selected with digital input DIB6.
The Local/Remote Control Application can be
activated from the Group 0 by setting the value
of parameter 0. 1 to 3.
Basic connections of inputs and outputs are
shown in the figure 2.2-l. The control signal
logic is shown in the figure 2.3-l. Programming
of l/O terminals is explained in chapter 2.5,
Special parameters.
2.2
Control l/O
Local reference
potentiometer
Terminal Signal
Description
r-k- -9
+iOV,,t Reference output
Voltage for a potentiometer, etc.
j _ _~ 2 VI,+
;;,;pei;p4ud$rammab,e)
;;;;E;;qvugy
reference
L_____
9
GND
I/O ground
Ground for reference and controls
Remote reference - - 4
Analog input, Source A frequency reference
O(4)-20 mA - - s
I,,+
1,“‘
current (programmable)
range O-20 mA
Remote control
“y -/___-
l/-____
Remote
--------
control ground
r-------
FAULT
220 -----
--
Figure
2.2-l Default I/O
configuration and connection example of the Local/
Remote
Control Application.
Page 2-4
Local/Remote Control Application
HV9000
2.4 Basic parameters, Group 1
a.1 Parameter table
1 = Anal. current input (term. 4)
2 = Set reference from the panel
3 = Slgnal from internal motor pot.
Visibility of the parameters:
0 = All parameter groups wble
1 = Only group 1 is visible
1.16 Parameter value lock O-l
1
0
Disables parameter changes:
0 = Changes enabled
1 = Changes disabled
2-i
Tab/e 2.4-I Group 1 basic parameters.
Note! m =
Parameter value can be changed only
*
If 1.2 > motor synchr. speed, check suitability for motor
and drive system. Selecting 120 Hz/500 Hz range, see
page 2-5.
** Default value for a four pole motor and a nominal
size HV9000.
*** Up to MIO. Bigger classes case by case.
when the drive is stopped.
Page 2-6
Local/Remote Control Application HV9000
Squared:
The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1 point (par. 6. 3) where the nominal maximum voltage is supplied to
the motor. See figure 2.4-1.
The motor runs undermagnetized below the field weakening point
and produces less torque and electromechanical noise. A squared
V/Hz ratio can be used in applications where the torque demand of
the load is proportional to the square of the speed, e.g. in centrifugal
fans and pumps.
u
WI
V”
Default: Nominal
Field weakening
point
Default: Nominal
frequency of the
motor
j
WI
Figure
2.4- 1
Linear and squared V/Hz cutves.
V/Hz curve can be programmed with three different points.
V/Hz curve The parameters for programming are explained in chapter 2.5.2
2
Programmable V/Hz curve can be used if the standard settings
do not satisfy the needs of the application. See figure 2.4-2.
I
Parameter 6.7 v!
1
of the motor
Default 1.3 % 1
! V
/
Parameter 6.5
Parameter 6.3 QHz]
)
(Default 5 Hz)
Figure 2.4-2 Programmable V/Hz curve.
HV9660
1.9
Local/Remote Control Application
Page 2-7
V/Hz optimization
Automatic
torque
boost
The voltage to the motor changes automatically which allows the
motor to produce torque enough to start and run at low frequencies.
The voltage increase depends on the motor type and horsepower.
Automatic torque boost can be used in applications where starting
torque due to starting friction is high, e.g. in conveyors.
NOTE!
In high torque - low speed applications
-
it is &e/y the motor wi// overheat.
If the motor has to run for a prolonged time under these conditions, special
attention must be paid to cooling of the motor. Use external cooling for
the motor if the temperature rise is too high.
1.10
Nominal voltage of the motor
Find this value V, from the nameplate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6.4, to 100%
1.11
x Vnmotor.
Nominal frequency of the motor
Find the nominal frequency f, from the nameplate of the motor.
This parameter sets the field weakening point, parameter 6.3, to the same value.
1.12 Nominal speed of the motor
Find this value nn from the nameplate of the motor.
1.13
Nominal current of the motor
Find the value In from the nameplate of the motor.
The internal motor protection function uses this value as a reference value.
1.14 Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2,4,5, and 6. See table 2.4-1.
1.15
Parameter conceal
Defines which parameter groups are available:
0 = all groups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access for changing the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
If you have to adjust more of the functions of the Local/Remote Control Application, see
chapter 2.5 to set up parameters of Groups 2-6.
HVQOOO
Local/Remote Control Application
Page 2-Q
code
2.16
Parameter
Free analog input,
signal selection
Free analog input,
function
2.19
=l=
Range
&2
step
1
3efault
1 custom
Description
0 = Not uset
1 = Vi, (analog voltage input)
2 = Iin (analog current input)
le
‘ag
2-2 !O
2.20
Motor potentiometer
ramp time
T
-1
Range
O-7
’
‘0
0 = No function 2-2
1 = Reduces current limit (par. I. 7)
2 = Reduces DC-braking current
3 = Reduces act. and decel. times
4 = Reduces torque supewis. limit
2
2-2
1
Group 3, Output and supervision parameters
-
Gxle
3.1
‘ammeter
rnalog output function
lefault
1
Description
Scale 100%
0 = Not used
1 = O/P frequency
(o-f,..)
2 = Motor
speed
(0-max. speed)
3 = O/P current
(o-Z.0 x 1”““s)
4 = Motortorque (O-2 x T.,&
5 = Motor power (o-2 x pnMot)
6 = Motor voltage (O-1 00% x VnMo,
7 = DC-linkvolt.
(0-1000 V)
4
ie
2
!-2
_
2
!-2
12
!-2
_
!-2 2
-
12
!-2
-
!P ‘3
3.2
3.3
3.4
3.5
3.6
nalog output filter time
nalog output inversion
*********!
&I
6-l
I.01 s
1
1
1%
1
100s
0
0
0 = Not iwelted
1 = Inverted
O=OmA
1=4mA
nalog output scale
Xgital output function
1 O-1 000%
O-21
100%
1 0 = Not used
1 = Ready
2=Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7= Reference fault or warning
6 = Warning
9 = Reversed
10 = Jog speed selected
11 = At speed
12 = Motor regulator activated
13 = Output frequency limit
superv. 1
14 = Output frequency limit
superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
16 = Control from I/O terminals
19 = Drive temperature limit super
vision
20 = Unrequested rotation directic
21 = External brake control
I=
Parameter value can be changed only when the drive is stopped
Page 2-l 0
Local/Remote Control ADDlication
HV9000
I
cods
I
Parameter
Relay
1 flame 1 step
I Default I Custom IDescdption
As parameter 3.6
I Paw
output
1 function
supervision value
(2),
I I
3.13
I
Torque limit
supervision function
3.14
1
Torque limit
supervision value
Active reference limit
supervision
Active reference limit
supervision value
1
0.~200.0%
x Tntw
O-2
1
0.1%
j
100.0%
1
1 0 O=No
1 = Low limit
2 = High limit
1
2-24
2-24 3.15
3.16 O.&f,,
(par. 1.2)
1 0.0-100.0s
0.1 Hz
1 0.1 s
2-24
I 2-25
1 3.17 I External brakeOFFdelav
I 3.16 1 ExternalbrakeONdelay
3.19 Drive
temperature limit
supervision function
Drive
temperature limit
l/O-expander board (opt.)
analog output function
l/O-expander board (opt.)
analoa output filter time
1
0.5 s
/
0 0 = No supewision
1 = Low limit
2 = High limit
I
O.(
O-2
I
0.1 s
I 1.5s I
1
1
2-25
2-25
3.20
3.21
3.22
-10-+75”C
&7
0.00-l
0-l
1
1
+wc
3
1 .OO s
1
I
0
0
1
I
See parameter 3.1
See parameter 3.2
ISeeparameter3.3
ISee parameter3.4
ISeeparameter3.5
2-25
2-22
2-22 0.00 s 0.01 s
1 1
1
analog output inversion
l/O-expander board (opt.)
(
board (opt.)
analog output minimum
1
2-22
I
2-22
(
2-22
1 C-1 /
I
I
3.25
analog output scale
I/O-expander board (opt.)
1
l&1000%
1
1
I
100%
1
Note! m =
Parameter value can be changed only when the drive is stopped
HV9000
Local/Remote Control Application
Page 2-11
Group 4, Drive control parameters
>O = S-curve . time
0 = Brake chopper not in use
1 = Brake chopper in use
Group 5, Prohibit frequency parameters
Note!m=
Parameter value can be changed only when the drive is stopped.
Page 2-l 2
Local/Remote Control ADDlication
HV9000
Group 6, Motor control parameters
code I Parameter
I
I
Default ICustcm
I
Description
Note!
m =
Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
Cc&
7.1
Parameter
Response to
reference fault
Local/Remote Control Application
Page 2-l 3
Range
O-3
step
Default
1 0
Custom Description
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3 = Fault, always coasting stop
0 = No action
1 = Warning
2 = Fault. stoo accordina to
I oar. 4.7
”
3 = kault, always coasting stop
Page
2-30
7.2
Response to
external fault
o-3
1 0
2-31
l-
7.3
7.4
7.5
Phase supervision of
the motor
Ground fault protection
Motor thermal protection
&2
&2
g#Jgq-
1.0%
1 .O%
0.5
mix
1 Hz
100.0%
45.0%
17.0
min.
35 Hz
Default value is set
according
to motor nominal current
/ I
_I
7.0
7.9
7.10
Motor thermal protection
time constant
Motor thermal protection
break point frequency
Stall protection
0.5-300.0
minutes
1 O-500 Hz
&2
7.11
7.12
7.13
7.14
Stall current limit
Stall time
Maximum stall frequency
Underload protection
5.0-200.0%
x l”MOTOR
2.0-120.0 s
2-32
2-32
2-33
2-33
2= Fault -
1 .O%
(
130.0%
2-34
1
I 2-4
t-fIllax
O-2
7.15
7.16
7.17
Underload pmt., field
weakening area load
Underload protection,
zero frequency load
Underload time
10.0-l 50.00,
I
1 .O%
10.0%
I
XT~MOTOR
5.0-150.0%
I
I
2-35
Paae 2-l 4
Local/Remote COntrOl ADDhCatiOn
HV9000
Group 8, Autorestart parameters
Table 2.5 7
Special
parameters,
Groups
2-8.
HV9000
Local/Remote Control Application
Page 2-15
2.5.2 Description of Groups 2-9
2.1
parameters
Start/Stop logic selection
0:
DIAl:
closed contact = start forward
DIA2: closed contact = start reverse,
See figure 2.5-l.
Figure 2.5 7
Start forward/Start reverse.
0
0
0
1:
The first selected direction has the highest priority
When DlAl contact opens, the direction of rotation starts to change
If Start forward (DIAl) and Start reverse (DIA2) signals are active
simultaneously, the Start forward signal (DIAl) has priority.
DlAl : closed contact = start
DIA2: closed contact = reverse
See figure 2.5-2.
open contact = stop
open contact = forward
Figure 2.5-2
Start,
Stop, reverse.
Page 2-16
Local/Remote Control Application HV9000
2:
DlAl : closed contact = start
open contact = stop
DIA2:
closed contact = start enabled open contact = start disabled
3:
3-wire connection (pulse control):
DlAl : closed contact = start pulse
DIA2: closed contact = stop pulse
(DIA3 can be programmed for reverse command)
See figure 2.5-3.
4: DIAl: closed contact = start forward
DIA2: closed contact = reference increases (motor potentiometer
reference, par. 2. 1 is automatically set to 4 if
par. 1. 5 is set to 3 or 4).
Figure 2.5-3
Sfafi
pulse /Stop pulse.
2. 2
DIA3 function
1: External
fault, closing contact = Fault is shown and motor is stopped when
the contact is closed
2: External fault, opening contact = Fault is shown and motor is stopped when
the input is open
3: Run enable
contact open = Start of the motor disabled
contact closed
= Start of the motor enabled
4: Act. I Dee
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5: Reverse
contact open
= Forward Can be used for reversing if
contact closed
= Reverse
II
parameter 2. 1 has value 3
6: Jogfreq.
contact closed
= Jog frequency selected for freq. refer.
7: Fault reset
contact closed
= Resets all faults
8: Acc./Dec. operation prohibited
contact closed
= Stops acceleration and deceleration until
the contact is opened
9: DC-braking command
contact closed
= In the stop mode, the DC-braking operates
until the contact is opened, see figure 2.5-4.
DC-brake current is set with parameter 4. 8.
10:
Motor pot. meter down
contact closed = Reference decreases until the contact is
opened
Page 2-20
Local/Remote Control Application
HV9000
2.13 Source B Start/Stop logic selection
See parameter 2. 1, settings O-3.
2.14, Source A reference scaling, minimum value/maximum value
2.15
Setting limits: 0 < par. 2. 14 < par. 2. 15 < par. 1. 2.
If par. 2. 15 = 0 scaling is set off. See figures 2.5-11 and 2.512.
(h the figures below voltage input Vin with signal range O-70 V selected for source A
reference)
Figure 2.5- 7 1
Reference scaling. Figure 2.5-12 Reference scaling,
par. 2. 15 = 0.
2.16,
Source B reference scaling,
2.17
minimum value/maximum value
See parameters 2.14 and 2. 15.
2. 18 Free analog input signal
Selection of input signal of
a free
analog input (an input not used for reference signal):
0 = Not in use
1 = Voltage signal V,,
2 = Current signal I,,
2.19
Free analog input signal
function
Use this parameter to select a
function for a free analog input
signal:
0 = Function is not used
1 = Reducing motor
current limit (par. 1. 7)
This signal will adjust the
maximum motor current between
0 and ,par. 1.7 set max. limit. See
figure 2.5-l 3.
Figure 2.5- 13
Scaling of max. motor current.
HV9000
Local/Remote Control Application
2 = Reducing DC brake
current.
The DC braking current can be
reduced with the free analog input
signal between current 0.15 x InHvS
and the current set by parameter
4.8. See figure 2.5-14.
Page
2-21
Figure 2.5 14
3 = Reducing acceleration
and deceleration
times.
The acceleration and deceleration
times can be reduced with the free
analog input signal according to
the following formulas:
Reduced time = set act./
(par. 1. 3, 1. 4; 4. 3,
4. 4) divided by the factor R from
figure 2.5-l 5.
Reducing DC brake current.
Figure 2.5- 15 Reducing acceleration and
deceleration times
4 = Reducing torque
supervision limit.
Torque supervision limit can be
reduced with a free analog input
signal between 0 and the set
supervision limit (par. 3. 14). See
figure 2.5-l 6.
te
figure 2.5 16 Reducing torque supervision limit
Paoe 2-22
Local/Remote Control Audication
Motor potentiometer ramp
HV9000
2.20
time
Defines how fast the electronic
motor potentiometer value
changes.
3.1
Analog
output Content
See
table for parameter 3.1 on
page 2-9.
3.2
Analog output filter
time
Filters the analog output signal.
See figure 2.5-i 7.
-I
Par. 3.2
Figure
2.5- 17
Analog output Wering.
3.3 Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
3. 4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4 mA.
See figure 2.5-l 9.
3.5
Analog output
scale
Scaling factor for analog output.
Figure 2.5- 18
Analog output invert.
See figure 2.5-19.
I
Sianal
1 Max. value
of the signal
output fre-
Max. frequency (p. 1. 2)
quency
Motor speed Max. speed (n,xf,,JfJ
Output
2x1
current
nnvs
Motor torque 2 xT,~,,,
Motor power 2 x PnMot
Motor voltage
100% x
VnMof
DC-link volt. 1000 V
Figure2.5-19Analog outputscale
HV9000 Local/Remote Control Application
Page 2-23
3.6
3.7
3.6
Digital output function
Relay output 1 function
Relay output 2 function
Setting value
0 = Not used
Signal content
Out of operation
Diaital outout DO1 sinks current and oroarammable
relav (ROl, R021 is activated when:
The drive is ready to operate
The drive operates (motor is running)
A fault trip has occurred
A fault trip h&n&t occurred
The heat-sink temperature exceeds +7O”C
Fault or warning depending on parameter 7. 2
Fault or warning depending on parameter 7. 1
-
if analog reference is 4-20 mA and signal is c4mA
0 = Warning
Always if a warning exists
9 = Reversed
The reverse command has been selected
1 O= Jog speed
Jog speed has been selected with digital input
1 1 =
At speed
The output frequency has reached the set reference
12= Motor regulator activated
Overvoltage or overcurrent regulator was activated
13= Output frequency supervision 1
The output frequency goes outside of the set supervision
Low limit! High limit (par. 3. 9 and 3. 10)
14 = Output frequency supervision 2
The output frequency goes outside of the set supervision
Low limit/ High limit (par. 3. 11 and 3. 12)
15 = Torque limit supervision
The motor torque goes outside of the set supervision
Low limit/ High limit (par. 3. 13 and 3. 14)
16 = Active reference Active reference goes outside of the set supervision
limit supervision
Low limit/ High limit (par. 3. 15 and 3. 16)
17= External brake control External brake ON/OFF control with programmable
delay (par 3. 17 and 3. 18)
18= Control from I/O terminals External control mode selected with prog. pushbutton #2
19= Drive
Temperature on drive is outside the set
temperature limit supervision supervision limits (par. 3. 19 and 3. 20)
20= Unrequested rotation direction Rotation direction of the motor shaft is different from the
requested one
21= External brake control inverted External brake ON/OFF control (par. 3.17 and 3.18).
output active when brake control is OFF
Table 2.52 Output signals via DO 7 and output relays RO 7 and ROZ.
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
Page 2-24
Local/Remote Control Application
HV9000
3.9
Output frequency limit 1, supervision function
3.11
Output frequency limit 2, supervision function
0 = No
supervision
1 = Low limit supervision
2 =
High limit supervision
If the output frequency goes under/over the set limit (3. 10, 3. 12) this function
generates a warning message via the digital output DO1 or via a relay output ROl
or R02 depending on the settings of the parameters 3. 6-3. 8.
3.10
Output frequency limit 1, supervision value
3.12
Output frequency limit 2, supervision value
The frequency value to be supervised by the parameter 3. 9 (3. 11). See figure
2.5-20.
3.13
Torque limit
,
supervision
function
0 = No
supervision
1 = Low limit supervision
2 = High limit supervision
If the calculated torque value goes
under/over the set limit (3.14) this
function generates a warning
message via the digital output
DO1 or via a relay output ROl or
Figure 2.5-20 Output frequency supervision.
R02 depending on the settings of
the parameters 3. 6-3.8.
3.14
Torque limit
,
supervision value
The calculated torque value to be supervised by the parameter 3. 13. Torque
supervision value can be reduced below the setpoint with a free analog input signal,
see parameters 2. 18 and 2. 19.
3.15
Reference limit , supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3. 16) this function generates a
warning message via the digital output DO1 or via a relay output ROl or R02
depending on the settings of the parameters 3. 6-3. 8. The supervised reference
is the current active reference. It can be source A or B reference depending on DIB6
input or panel reference if panel is the active control source.
3.16
Reference limit , supervision value
The frequency value to be supervised by the parameter 3.15.
HV9000 Local/Remote Control Application
Page 2-25
3.17
3.18
External brake-off delay
External brake-on delay
The function of the external brake can be delayed from the start and stop control
signals with these parameters. See figure 2.521.
Figure
2.52 1 Ext.
brake controf; a) Start&top logic selection par 2. 7 = 0, 1 or 2
b) StarCStop logic selection par 2. 7 = 3.
The brake control signal can be programmed via the digital output DO1 or via
one of the relay outputs ROl and R02, see parameters 3. 6-3.8.
3.19
Drive temperature limit supervision
0 = No supervision
1 =
Low limit supervision
2 = High limit supervision
If temperature of the unit goes under/over the set limit (par. 3. 20) this function
generates a warning message via the digital output DO1 and via a relay output ROl
or R02 depending on the settings of the parameters 3. 6-3. 8.
3.20
Drive temperature supervision limit value
The set temperature value to be supervised with the parameter 3. 19.
Page 2-26 Local/Remote Control Application
HV9000
4.1
Acc/Dec ramp 1 shape
4.2
AcclDec ramp 2 shape
The acceleration and deceleration ramp shape can be programmed with these
parameters.
Setting the value = 0 gives you a linear ramp shape. The output frequency immediately
follows the input with a ramp time set by parameters 1.3, 1.4 (4.3,4.4 for Acc/Dec
time 2).
Setting 0.1-10 seconds for 4.1
(4.2) causes an S-shaped ramp.
t
f [Hz1
The speed changes are smooth.
Parameter 1.3/ 1.4 (4.3/ 4.4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure
: ~
(4.3,4.4) :
2.5-22.
+T-
I’
1.3.1.4_
I-;
4. 1 (4. 2)
/,
Figure 2.5-Z
S-shaped acceleration/deceleration
4.3
Acceleration time 2
4.4
Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possible to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2. 2. Acceleration/deceleration times can be reduced
with a free analog input signal. See parameters 2. 18 and 2. 19.
4.5
Brake chopper
0 = No brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor,
the energy stored in the inertia of the motor
and the load is fed into the external brake resistor. If the brake resistor is selected
correctly the drive is able to decelerate the load with a torque equal to that of
acceleration, See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may cause prolonged
acceleration times).
HV9000
Local/Remote Control Application
Page 2-27
Flying start:
1 The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7
Stop function
Coasting:
The motor coasts to an uncontrolled stop with the HV9000 off, after the Stop
0
command.
Ramp:
1 After the Stop command, the speed of the motor is decelerated based on
the deceleration ramp time parameter.
If the regenerated energy is high, it may be necessary to use an external
braking resistor for faster deceleration.
4.8
DC
braking current
Defines the current injected into the motor during DC braking.
The DC braking current can be reduced from the setpoint with a external free
analog input signal, see parameters 2. 18 and 2. 19.
4.9
DC
braking time at stop
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4.7. See figure 2.5-23.
0
SO
DC-brake is not used
DC-brake is in use and its function depends of the stop function,
(parameter 4. 7), The time is set by the value of parameter 4. 9:
Stoo-function = 0 (coastina):
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .l l), the value
of parameter 4.9 determines the braking time. When the frequency is c 10%
of the nominal, the braking time is 10% of the set value of parameter 4.9. See
figure 2.5-13.
Stop-function = 1 (ramp):
After a Stop command, the speed of the motor is reduced based on the
deceleration ramp parameter. If no regeneration occurs due to load inertia DC-
braking starts at a speed defined by parameter 4. 10.
Page 2-28
Local/Remote Control Application HV9000
Figure 2.5-23 DC-braking time when par. 4. 7 = 0.
The braking time is defined
by par. 4.9. If the load has a
high inertia, use an external
braking resistor for faster
decelerationSee figure 2.5-
24.
4.10 Execute frequency of DC-
brake during ramp Stop
Figure 2.5-24 DC-braking time when par. 4. 7
= 1.
See figure 2.524.
4.11
DC-brake time at start
fom
WI
0 DC-brake is not used
>O
The DC-brake is activated
by the start command
given. This parameter
defines the time before the
brake is released. After the
brake is released the output
t
frequency increases
I
: par4.11:
according to the set start
,-
function parameter 4.6
RUN
and the acceleration
STOP
“D012Kz2
parameters (1. 3, 4. 1 or 4.
‘igore2.5-25 DC-braking time
2,4.3). See figure 2.5-25.
at start.
HWOOO
Local/Remote Control Application Page 2-29
4.12 Jog speed reference
This parameter value defines the jog speed if the DIA3 digital input is programmed
for Jog and is selected. See parameter 2.2.
5. l- 5.6
Prohibit frequency area
Low limit/High limit
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance
problems.
With these parameters it is
possible to set limits for three “skip
frequency” regions between 0 Hz
and 500 Hz. The accuracy of the
setting is 0.1 Hz. See figure 2.5-26
frequency
reference
Reference [HZ,
*
Figure 2.5-26
Example of prohibit frequency
area setting.
6.1
Motor control mode
0 = Frequency control:
(V/Hz)
1 = Speed control:
(sensorless vector)
The I/O terminal and panel references are frequency
references and the drive controls the output frequency
(output freq. resolution 0.01 Hz)
The l/O terminal and panel references are speed
references and the drive controls the motor speed (control
accuracy * 0.5%).
6.2
Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHz >40 Hp) check
the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter 5.2 of the
User’s Manual.
6.3
6.4
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage reaches
the set maximum value (parameter 6. 4). Above that frequency the output voltage
remains constant at the set maximum value. Below that frequency the output voltage
depends on the setting of the V/Hz curve parameters 1.8, 1.9, 6.5,6.6 and 6.7.
See figure 1.5-l 8.
When the parameters 1.10 and 1.11, nominal voltage and nominal frequency of the
motor, are set, parameters 6.3 and 6.4 are also set automatically to the same values.
If you need different values for the field weakening point and the maximum output
voltage, change these parameters after setting parameters 1. 10 and 1. 11.
Page 2-30
Local/Remote Control Application
HV9000
6.5 V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle frequency point of the curve. See figure 2.5-27.
6.6 V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the middle point voltage (% of motor nominal voltage) of the curve. See figure
2.5-27.
6.7 Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this parameter
defines the zero frequency voltage (% of motor nominal voltage) of the curve. See
figure 2.5-27.
Parameter 6.5
Parameter 6.3 qHz]
(Default 5 Hz)
Figure 2.5-27
Programmable V/Hz cwve.
6.8 Overvoltage controller
6.9 Undervoltage controller
These parameters allow the over/undervoltage controllers to be switched ON or OFF.
This may be useful in cases where the utility supply voltage varies more than -15%-
+1 0% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/under-voltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undervoltage trips may occur when controllers are not used.
7. 1
Response to the reference fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA. The information can also be
programmed via digital output DO1 and via relay outputs ROl and R02.
HV9000
Local/Remote Control Application
Page 2-31
7.2
Response to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault detection
A warning or a fault action and message is generated from the external fault signal
on digital input DIA3. The information can also be programmed into digital output
and into relay
DO1
outputs ROl and R02.
7.3
Phase supervision
0 = No action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
7.4 Ground fault protection
0 = No action
2 = Fault message
Ground fault protection ensures that the sum of the motor phase currents is zero.
The standard overcurrent protection is always present and protects the frequency
converter from ground faults with high current levels.
Parameters 7.5-7.9 Motor thermal protection
of the motor
General
Motor thermal protection protects the motor from overheating. The HV9000 drive is
capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that motor will be thermally overloaded. This is true
especially at low frequencies. With low frequencies the cooling effect of the motor
fan is reduced and the capacity of the motor is reduced. If the motor is equipped
with a separately powered external fan, the load derating at low speed is small.
Motor thermal protection is based on a calculated model and it uses the output cur-
rent of the drive to determine the load on the motor. When the motor is powered
from the drive, the calculated model uses the heatsink temperature to determine
the initial thermal state of the motor. The calculated model assumes that the ambi-
ent temperature of the motor is 40°C.
Motor thermal protection can be adjusted by setting several parameters. The thermal
current IT specifies the load current above which the motor is overloaded. This cur-
rent level is a function of the output frequency. The curve for IT is set with param-
eters 7.6, 7. 7 and 7. 9. See figure 2.5-28. The default values of these parameters
are set from the motor nameplate data.
With the output current at IT the thermal state will reach the nominal value (100%).
The thermal state changes by the square of the current. With output current at 75%
of IT the thermal state will reach 56% and with output current at 120% of $ the thermal
stage would reach 144%. The function will trip the drive (refer par. 7.5) If the thermal
state reaches a value of 105%. The response time of the thermal model is deter-
mined by the time constant parameter 7.8. The larger the motor, the longer it takes
to reach the final temperature.
Page 2-32
Local/Remote Control Application
HV9000
The thermal state of the motor can be monitored through the display. Refer to the
table for monitoring items. (User’s Manual, table 7.3-l).
CAUTION!
The calculated mode/ does not protect the motor if the cooling of
A
!
the motor is reduced either by blocking the airflow or due to dust or
dirt.
7. 5 Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection by setting this parameter to 0, will reset the thermal stage
of the motor to 0%.
7.6 Motor thermal protection, break point current
This current can be set between 50.0-150.0% x InMatar.
This parameter sets the value for thermal current at frequencies above the break
point on the thermal current curve. Refer to the figure 2.5-28.
The value is set as a percentage of the motor nameplate nominal current, parameter
1. 13, not the drive’s nominal output current.
The motor’s nominal current is the current which the motor can withstand in direct
online use without being overheated.
If parameter 1. 13 is adjusted, this parameter is automatically restored to the default
value.
Setting this parameter (or
I
parameter 1. 13) does not affect
the maximum output current of the
drive. Parameter 1.7 alone
determines the maximum output
current of the drive.
Par. 7. 6
---------
Overload area
IT
Par. 7.7
Figure 2.5-28 Motor thermal current, I,
curve.
7.7
Motor thermal protection, zero frequency current
This current can be set between lO.O-150.0% x InMotor
This parameter sets the value for thermal current at zero frequency. Refer to the
figure 2.5-28.
The default value is set assuming that there is no external fan cooling the motor. If
an external fan is used this parameter can be set to 90% (or higher).
HV9000
Local/Remote Control Application Page 2-33
The value is set as a percentage of the motor’s nominal nameplate current,
parameter 1.13, not the drive’s nominal output current. The motor’s nominal current
is the current which the motor can stand in direct on-line use without being
overheated.
If you change parameter 1.13, this parameter is automatically restored to the default
value.
Setting this parameter (or parameter 1. 13) does not affect to the maximum output
current of the drive. Parameter 1.7 alone determines the maximum outout current
of the drive.
7.8
Motor thermal protection, time constant
This time can be set between 0.5-300 minutes.
This is the thermal time constant of the motor. The larger the motor the greater
the time constant. The time constant is defined as the time that it takes the calcu-
lated thermal stage to reach 63% of its final value.
The motor thermal time is specific to a motor design and it varies between different
motor manufacturers.
The default value for the time constant is calculated based on the motor
nameplate data from parameters 1. 12 and 1. 13. If either of these parameters is
reset, then this parameter is set to default value.
If the motor’s t6 -time is known (given by the motor manufacturer) the time
constant parameter could be set based on ts -time. As a rule of thumb, the motor
thermal time constant in minutes equals to 2xts (t6 in seconds is the time a motor
can safely operate at six times the rated current). If the drive is stopped the time
constant is internally increased to three times the set parameter value. Cooling in
the stop stage is based on convection with an increased time constant
7.9
Motor thermal protection, break point frequency
This frequency can be set between 10-500 Hz.
This is the frequency break point of the thermal current curve. With frequencies
above this point the thermal capacity of the motor is assumed to be constant.
Refer to the figure 2.528.
The default value is based on the motor’s nameplate data, parameter 1. 11. It is 35
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the
frequency at the field weakening point (parameter 6.3). Changing either parameter
1. 11 or 6.3, will restore this parameter to its default value.
f Changed v&l
ad,“sted with
parameter
7.8
motor
s,.z* and
“MC”7
.
92
figure
25-29
Calculafing
motor
temperature.
Page 2-34
Local/Remote Control Application HV9000
Parameters 7.1 O- 7.13, Stall protection
General
Motor stall protection protects the motor from short time overload situations like a
stalled shaft. The reaction time of stall protection can be set shorter than with motor
thermal protection. The stall state is defined with two parameters, 7.11, Stall Current
and 7.13., Stall Frequency. If the current is higher than the set limit and output
frequency is lower than the set limit the stall state is true. There is no true detection
of rbtation. Stall protection is a type of overcurrent protection.
7.10
Stall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is set on, the drive will stop and generate a fault. Deactivating the stall
protection by setting the parameter to 0 will reset the stall time counter to zero.
7.11 Stall current limit
The current can be set between
o.O-200% x InMotor.
In a stall the current has to be
above this limit. See figure 2.5
30. The value is set as a
I
Stall area
percentage of the motor name-
plate nominal current, parameter
1. 13. If parameter 1.13 is
adjusted, this parameter is
Par.7.11
automatically restored to its
default value.
f [Hz1
Pk7. 13 "MCH7_11
i
7.12
Stall time
Figure 2.5-30 Setring the
stall characterisfics.
The time can be set between
2.0-120 s.
A!
Stall time counter
1
This is the maximum allowed
time for a stall. There is an
Trip area
internal up/down counter to
Par. 7. 12
count the stall time. See figure
2.5-31. If the stall time counter
value goes above this limit, this
protection will cause a trip (refer
to the parameter 7. 10).
7.13
Maximum stall frequency
This frequency can be set
between l-f,,X (param. 1. 2). In
the stall state the ouput frequency
has to be smaller than this limit.
See figure 2.5-30.
Figure 2.5-37
Counting the stall time.
HV9000
Parameters 7.14-
General
Local/Remote Control Application
7.17, Underload protection
Page 2-35
The purpose of motor underload protection is to ensure there is a load on the motor
while the drive is running. If the motor load is reduced, there might be a problem in
the process, e.g. broken belt or dry pump.
Motor underload protection can be adjusted by setting the underload curve with
parameters 7.15 and 7. 16. The underload curve is a squared curve set between
zero frequency and the field weakening point. The protection is not active below
5Hz (the underload counter value is stopped). See figure 2.5-32.
The torque values for setting the underload curve are set with percentage values
which refer to the nominal torque of the motor. The motor’s nameplate data,
parameter 1 .13, the motor’s nominal current and the drive’s nominal current Icr
are used to create the scaling ratio for the internal torque value. If other than a
standard motor is used with the drive, the accuracy of the torque calculation is
decreased.
7.14
Underload protection
Operation:
0 = Not in use
1 = Warning message
2 = Fault message
Tripping and warning will give a display indication with the same message code. If
tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection, by setting this parameter to 0, will reset the underload
time counter to zero.
7.15
Underload protection, field weakening area load
The torque limit can be set
between 20.0-l 50 % x TnMotor.
This parameter is the value for
the minimum allowed torque
when the output frequency is
above the field weakening point.
Refer to the figure 2.5-32.
If parameter 1. 13 is adjusted,
this parameter is automatically
restored to its default value.
t
Torque
F
5 Hz
Field weak&fling
point par. 6. 3
Setting
of minimum load.
7.16
Underload protection, zero
frequency load
Figure 25-32
The torque limit can be set between
10.0-150 % x
TnMotor.
This parameter is the value for the minimum allowed torque with zero frequency.
See figure 2.5-32. If parameter 1. 13 is adjusted, this parameter is automatically
restored to its default value.
Page 2-36
Local/Remote Control Application
HV9000
7.17
Underload time
Underload time counter
This time can be set between 2.0-
t
600.0 s.
This is the maximum allowed time
Par. 7. 17 --
for an underload state. There is an
internal up/down counter to
accumulate the underload time.
See figure 2.533.
If the underload counter value
goes above this limit, the
underload protection will cause a
trip (refer to the parameter 7. 14).
If the drive is stopped the
underload counter is reset to zero.
figure 2.533
Counting the underload time.
8.1
Automatic restart: number of tries
8.2 Automatic restart: trial time
The Automatic restart function restarts the drive after the faults selected with
parameters 8.4-8.8. The Start type for Automatic restart is selected with parameter
8.3. See figure 2.5-34.
A
Number of faults
during
t = ttllal
‘trial
‘trial
I
4 --
I
3--
’
2 -- l-l
:
Par. 8.1 = 3
: ttria, = par. 8.
2
1 ~~
t
.
Figure 25-34
Automatic restart.
Parameter 8. 1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The count time starts from the first autorestart. If the number of restarts does not
exceed the value of parameter 8.1 during the trial time, the count is cleared after the
trial time has elapsed. The next fault starts the counting again.
HV9000
8.3
Local/Remote Control Application
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
Page 2-37
8.4 Automatic restart after undervoltage
0 = No
automatic restart after undervoltage fault
1 = Automatic restart after undervoltage fault condition returns to normal.
(DC-link voltage returns to the normal level)
8.5
Automatic restart after overvoltage
0 = No
automatic restart after overvoltage fault
1 = Automatic restart after overvoltage fault condition returns to normal
(DC-link voltage returns to the normal level)
8.6 Automatic restart after overcurrent
0 = No automatic restart after overcurrent fault
1 = Automatic restart after overcurrent faults
8.7
Automatic restart after reference fault
0 = No automatic restart after reference fault
1 = Automatic restart after analog current reference signal (4-20 mA)
returns to the normal level (24 mA)
8.8
Automatic restart after over-/undertemperature fault
0 = No automatic restart after temperature fault
1 = Automatic restart after heatsink temperature has returned to its normal
level
between -1 O”C-+75”C.
Page 2-38
Local/Remote Control Application
HV9000
Notes:
HV9000
Multi-steu SDeed
COtItrOl
ADDliCatiOn
Page 3-l
MULTI-STEP SPEED CONTROL APPLICATION
(par. 0.1 = 4)
CONTENTS
3 Multi-step Speed Control Appl. ....... .3-l
3.1 General ....................................... .3-2
3.2 Control I/O.. ................................. .3-2
3.3 Control signal logic.. .................... .3-3
3.4 Parameters Group 1 .................... 3-4
3.4.1 Parameter table ................. .3-4
3.4.2 Description of 3- 5
3.5 Special parameters, Groups 2-8 .3-8
3.51 Parameter tables .................. 3-8
3.52 Description of Groups.. ...... .3-14
Page 3-2
3.1 GENERAL
Multi-step Speed Control Application
HV9000
The Multi-step Speed Control Application can
be used in applications where fixed speeds are
needed. in total 9 different speeds can be
programmed: one basic speed, 7 multi-step
speeds and one jog speed. The speed steps
are selected with digital signals DIB4, DIB5 and
DIB6. If jog speed is used, DIA3 can be
programmed
select.
from fault reset to jog speed
The basic speed reference can be either a
voltage or a current signal via analog input
terminals (Z/3 or 4/5). The other analog input
can be programmed for other purposes
All outputs are freely programmable
3.2 CONTROL
Reference
I/O
y--_+_
I-
-__;_
,____
----
I
-
--- I-
-
I/- _
Jl_
-
‘l--J-
-
I---$
k
FAULT
220 -----
--
Figure 3.2- 1 Default //O configuration and connection example of the
Multi-step speed Control Application.
HV9000
Multi-steD SDeed Control ADDliCatiOn
Page 3-3
3.3
Control signal logic
PROGRAMMABLE
PUSH-BUTTON 2
frequency
reference
)
Internal
I
Multi-step speed selection 1
-.-.-.-.-.-.-.-.-.-.-.
Multi-step speed selection 2
.-.-.-.-.-.-.-
_tu&i-_s*.zeed
.-.-.-.-.-.-.-
selection 3
m
B
D
I
-
Internal
fault reset
Jog speed reference selection (programmable input)
Fault reset (prowammable input)
Reverse signal
- =sigx4line
Figure 3.3- 1
Control signal logic of the Multi-step Speed Control Application
Switch positions shown are based on the factory settings.
Page 3-4
Multi-step Speed Control Application
HV9000
3.4 Basic parameters, Group 1
Parameter
Minimum frequency
I I
Description
3-5
fmi,-120/500Hz
0.1-3000.0
0.1-3000.0
1 Hz
Time from f,,, (1.
1) to f,,, (1.21
Time from f,,, (1.2) to f,,, (1. lj
0 = Analog voltage input (term.2)
1 = Analog current Input (term 4)
5.0 Hz
3-5
3-5
-
3-5
3-5
Maximum frequency
Acceleration time 1
Deceleration time 1
s
/
0.1 s
s
1
0.1 s
&l
Jog speed
reference
Current limil
1.6
V/Hz ratio selection O-2
1
1
0.1 Hz
fin,” -fmax
(1.1) (1.2)
3-5
1
*“Output curr. limit [A] of the unit
0 = Linear
1 = Squared
2 = Programmable V/Hz ratio
0 = None
1 = Automatic torque boost
Voltage code 2
Voltage code 4
Voltage code 5
Voltaae code 6
3-5
3-6
3-7
3-7
1.11
Nominal frequent
of the motor
3&500 Hz
1 Hz
f, from the nameplate of
the motor
I720 rpm
I
n, from the nameplate of
the motor
3-7
3-7
In
from the nameplate of
the motor
Supply voltage
230V
Voltaae code 2
Voltaae code 4
1 36&500
3-7
3-7
I
Voltaoe code 5
Voltage code 6
Visibility of the parameters:
0 = all parameter groups visible
1 = only group 1 is visible
3-7
1.16
Pararneterval”elock
1
%l
)
1
Disables parameter
changes:
0 =
changes enabled
1 = changes disabled
3-7
Note! m =
Parameter value can be changed
only wnen tne frequency converter is
stopped.
.
’ If 1.
2 >
motor synchr. speed, check suitability
for motor and drive system
Selecting 120/500 Hz range see page 3-5.
** Default value for a four pole motor and a
nominal size HV9000.
‘** Up to Ml 0. Bigger classes case by case.
HV9000
Multi-sten Steed Control ADDlication
Page 3-5
reference 6
1.23
Multi-step speed
reference 7
(l.l)(l.Z)
fm-fmx
(1.1)(1.2)
0.1 Hz 50.0 Hz
3-7
Tab/e 3.4-l Group 1 basicparameters.
3.4.2 Description of Group 1 parameters
1. 1, 1.2
Minimum/maximum frequency
Defines the frequency limits of the HV9000.
The default maximum value for parameters 1.1 and 1.2 is 120 Hz. By setting 1.2 =
120 Hz in the when the drive is stopped (RUN indicator not lit) parameters 1. 1 and
1.2 are changed to 500 Hz. At the same time the resolution of the panel reference is
changed from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting parameter
1. 2 to 119 Hz while the drive is stopped.
1.3,l. 4 Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to
accelerate from the set minimum frequency (par. 1. 1) to the set maximum
frequency (par. 1. 2). Acceleration/deceleration times can be reduced with a free
analog input signal, see parameters 2. 18 and 2. 19.
1.5
Basic reference selection
0:
1:
Analog
voltage reference from terminals 2-3, e.g. a potentiometer
Analog current reference trom terminals 4-5, e.g. a transducer
1.6 Jog speed refrence
The value of this parameter defines the jog speed selected with the DIA3 digital input
which if it is programmed for Jog speed. See parameter 2. 2.
Parameter value is automatically limited between minimum and maximum frequency
(par 1.1,1.2)
1.7 Current limit
This parameter determines the maximum motor current that the HV9000 will provide
short term. Current limit can be set lower with a free analog input signal, see
parameters 2. 18 and 2. 19.
Paae 3-6
Multi-step Speed Control Application
HV9000
1.8 V/Hz ratio selection
Linear:
The voltage of the motor changes linearly with the frequency in
the constant flux area from 0 Hz to the field weakening point
0
(par. 6.3) where a constant voltage (nominal vaue) is supplied to
the motor. See figure 3.4-l.
A linear V/Hz ratio should be used in constant torque applications
This default setting should be used if there is no special
requirement for another setting.
Squared:
The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1
point (par. 6. 3), where the nominal voltage is supplied to
the motor. See figure 3.4-i.
The motor runs undermagnetized below the field weakening point and
produces less torque and electromechanical
noise. A squared V/Hz ratio
can be used in applications where the torque demand of the load is
proportional to the square of the speed, e.g. in centrifugal fans and
v
[VI
1
Default: Nominal voltage of
7
Field weakening point
the motor
Default: Nominal
frequency of the
motor
- Wzl
Figure
3.4- 7
Linearand squared V/Hz curves.
Programm. The V/Hz curve can be programmed with three different points.
V/Hz curve The parameters for programming are explained in chapter 35.2.
2
A programmable V/Hz curve can be used if the standard settings do
not satisfy the needs of the application. See figure 3.4-2.
Parameter 6.6
Default 10%
Default: nominal frequency
Parameter 6.7
of the motor
/
Default 1.3 % 4
Parameter 6.5
I
Parameter 6.3
I/
qHz]
1
(Default 5 Hz)
Figure 3.4-2
Programmable V/Hz curve.
HV9000
1.9
Multi-step
V/Hz optimization
Automatic
torque
boost
Speed Control Application
Page 3-7
The voltage to the motor changes automatically which
allows the motor to produce enough torque to start and
run at low frequencies. The voltage increase depends on the motor type
and horsepower. Automatic torque boost can be used in applications
where starting torque due to starting friction is high, e.g. in conveyors.
In high torque - low speed applications - it is likely the motor will
overheat.
If the motor has to run for a prolonged time under these conditions,
special attention must be paid to cooling the motor. Use external
cooling for the motor if the temperature rise is too high.
NOTE!
A
1.10
!
Nominal voltage of the motor
Find this value V, from the nameplate of the motor.
This parameter sets the voltage at the field weakening
-
point, parameter
6.4, to 100% x V,,,tor
1.11 Nominal frequency of the motor
Find then nominal frequency f, from the nameplate of the motor.
This parameter sets the field weakening point, parameter 6.3, to the same value.
1.12
Nominal speed of the motor
Find this value nn from the nameplate of the motor.
1.13 Nominal current of the motor
Find the value In from the nameplate of the motor.
The internal motor protection function uses this value as a reference value.
1.14 Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2,4, 5, and 6. See table 3.4-l.
1.15 Parameter conceal
Defines which parameter groups are available:
0 = all parameter groups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
Page 3-6
Multi-step Speed Control Application
HV9000
1. 17 - 1. 23 Multi-step speed reference l-7
These parameter values define the Multi-step speeds selected with the DIA4, DIB5
and DIB6 digital inputs
These values are automatically limited between minimum and maximum frequency
(par. 1.1,1.2).
Speed Multi-step speed select
Multi-step speed select
:
Multi-step speed select 3
reference DIB4
DIB5
DIB6
Par. 1. 6 0
0
0
Par. 1. 17
1
0
0
Par. 1. 18
0 1
0
Par. 1.19 1
1
0
Par. 1. 20
0
0
1
1
0 1
0
1
1
1
1
1
Table 3.4-Z Selection
of multi-step speed reference
l-7.
HV9000
Multi-step Speed Control Application
Page 3-9
3.5 Special parameters, Groups 2-9
3.5.1 Parameter tables
Input signal parameters, Group 2
1=4--20mA
3 = Reduces act. and decel. times
4 = Reduces torque supervision limit
Note! u =
P
arameter value can be changed only when the drive is stopped.
Page 3-10
Multi-step Speed Control Application
HV9000
Group 3, Output and supervision parameters
code 1 Parameter
Range 1
Default Custom
1
Description
I
Paal
overheat warning
ad rotation direction
Note! m =
P
arameter value can be changed only when the drive is stopped.
HV9000
Multi-step Speed Control Application
Page 3-l 1
analog output inversion
3.24
3.25
l/O-expander board (opt.)
analog output minimum
l/O-expander board (opt.)
analog output scale
lo-1000% 1 1 Own
See parameter 3.5
3-22
O-l 1 0
See parameter 3.4
3-22
Group 4, Drive control parameters
code
4.1
4.2
4.3
4.4
4.5
Parameter
Acc./Dec. ramp 1 shape
Acc./Dec. ramp 2 shape
Acceleration time 2
Deceleration time 2
Brake chopper
Raw
0.6-10.0
0.0-10.0
Step
S
s
0.1 s
0.1 S
0.1 s
0.1 s
1
Default
0.0 s
0.0 s
10.0s
10.0s
0
Ct.&cm Description
0 = Linear
10 = S-curve acc./dec. time
0 = Linear
>O = S-curve acc./dec. time
Page
3-25
3-25
3-25
3-25
0.1-3000.0s
0.1-3000.0s
O-2
0 = Brake chopper
not in use
1 = Brake chopper in use
2 = External brake chopper
0 = Ramp
1 = Flying start
3-26
4.6
Start function
O-l
1
0
3-26
Note!m =
P
arameter value can be changed only when the drive is stopped.
Page 3-12
Multi-step Speed Control Application
HV9000
Page
3-26
3-26
code
4.7
4.6
4.9
4.10
Parameter
Stop function
DC-braking current
DC-braking time at Stop
Range
O--l
0.1+1.5x
lnw (A)
0.00-250.00s
Hz
step
1
0.1 A
0.01 s
0.1 Hz
0.01 s
Default
0
Custom Description
0 = Coasting
1 =
Ramp
0.5 x InHVc
0.00 s
1.5 Hz
0.00 s 0 = DC-brake is off at Start
0 = DC-brake is off at stop
3-26
3-26
3-26
t-
4.11
Turn on frequency of DC 0.1-10.0
brake durino ramo Stoo
DC-brake time at Start 0.0&25.00
Group 5, Prohibit frequency parameters
Cede
5.1
5.2
5.3
5.4
5.5
5.6
Parameter
Prohibitfrequency
ranoe 1 low limit
Prohibitfrequency
ranae 1 hiah limit
Prohibitfrequency
range 2 low limit
Prohibit frequency
range 2 high limit
Prohibit frequency
range 3 low limit
Pmhibit frequency
range 3 high limit
Range
frnm-
oar. 5.2
Step
0.1 Hz
Defauil
0.0H.z
Custom Description Page
3-26
1 fm;4,2j
1
f,,,-
par. 5.4
fnv-fInax
(1. 1) (1.2)
frnn-
par. 5.6
fnwrfnw
(1.1) (1.2)
1
1 I
O=Prohibitrangelisoff
I
3-261
1
0.1 Hz
/
0.1 Hz
0.1 Hz
0.1 Hz
0.0 Hz
l /
0 = Prohibit range 2 is off
I I
3-26
3-26
3-26
3-28 0 = Prohibit range 3 is of
Grou
6, Motor control parameters
Parameter
6.1
Motor control mode
m
Switching frequency 6.0 kHz 0.1 kHz 10/3.6 kHz
Range
C-l
Step
1
Default
0
Custom Description
0 = Frequency control
1 = Speed control
Dependant on Hp rating
Page
3-29
3-29
t=
1 6.2
6.3
1 6.4
V/Hz-curve. midpoin
6.7
6.6
6.9
Overvoltagecontroller
Undervoltagecontroller
&l
&l
Parameter maximum value =
0 = Controller is turned off
1 = Controller is operating
0 = Controller is turned off
1 = Controller is operating
Note! m = Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
Multi-step Speed Control Application
Page
3-l 3
2 = Fault, stop according to
Paae 3-l 4
Multi-step Speed Control Application
HV9000
Group 8, Autorestart parameters
Cc&
8.1
6.2
6.3
a.4
6.5
6.6
Parameter
Automatic restart:
number of tries
Automatic restart: multi
e
attempt maximum trial tims
Automatic restart:
start function
Automatic restart after
undelvoltage trip
Automatic restart after
overvoltage trip
Automatic restart after
overcurrent trip
Automatic restart after
reference fault trip
Automatic restart after
overlundertemperature
fault trip
0 = Ramp
1 = Flying start
O=No
1 =Yes
O=No
Iefault
I Qstom
Description
0 = not in use 3-36
1 =yes
O=No
1 = Yes
O=No
1 =Yes
O=No
1 =Yes
a.
7
a. a
Tab/e 3.5 1 Special parameters, Groups 2-8.
HV9000
Multi-step Speed Control Application
Page 3-15
3.5.2 Description of Groups 2-9 parameters
2.1 Start/Stop logic selection
0:
DIAl: closed contact = start forward
DIA2: closed contact = start reverse,
See figure 3.5-l.
Figure 3.5 1
Start forward/Start reverse.
0
0
0
1:
The first selected direction has the highest priority
When DlAl contact opens, the direction of rotation starts to change
If Start forward (DIAI) and start reverse (DIA2) signals are active
srmultaneously, the start forward signal (DIAI) has priority.
DIAl : closed contact = start
DIA2: closed contact = reverse
See figure 3.5-2.
open contact = stop
open contact = forward
Page
3-l 6
Multi-step Speed Control Application
HV9000
2:
DIAI : closed contact = start open contact = stop
DIA2:
closed contact = start enabled
open contact = start disabled
3:
3-wire connection
DIAl : closed contact = start pulse
DIA2: closed contact = stop pulse
(DIA3 can be programmed for reverse command)
See figure 3.53.
Figure 3.5-3
Start pulse /Stop pulse.
2. 2
DIAL3 function
1:
External fault. closina contact = Fault is shown and motor is stopped when
the contact is closed
2:
External fault, opening contact = Fault is shown and motor is stopped when
the input is open
3: Run enable
contact open
= Start of the motor disabled
contact closed
= Start of the motor enabled
4: Act. / Dee
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5:
Reverse
contact open
= Forward Can be used for reversing if
contact closed
= Reverse
II
parameter 2. 1 has value 3
6:
Jog speed
contact closed
= Jog speed selected for freq. refer.
7:
Fault reset
contact closed
= Resets all faults
8:
Acc./Dec. operation prohibited
contact closed
= Stops acceleration or deceleration until
the contact is opened
9:
DC-braking command
contact closed
= In Stop mode, the DC-braking operates
until the contact is opened, see figure 3.54.
DC-brake current is set with parameter 4.8.
See also param. 7.2!
HWOOO
Multi-steD SDeed Control
ADDkatiOII
Page
3-l 7
T
output
frequency
aram.
4. IO
RUN
STOP
“D009K32
DIA3 as DC-brake
4
command input and stop-mode = Ramp
I
D/A3 as DC-brake
UDO09K32
command input and stop-mode = Coasting
i
Figure 3.5-4
D/A3 as DC-brake command input:
a) Stop mode = Ramp,
b) Stop mode = Coasting.
2.3
V,” signal range
0 = Signal range 0-i 0
V
1 = Custom setting range from custom minimum (par. 2. 4) to custom
maximum (par. 2. 5)
2.4
2.5
V,” custom setting minimum/maximum
These parameters set Vi, for any input signal span within O-10 V.
Minimum setting:
Maximum setting:
Set the Vi, signal to its minimum level, select parameter 2.4,
press the Enter button
Set the Vi, signal to its maximum level, select parameter 2.5,
press the Enter button
Note!
The parameter values can only be set with this procedure (not with arrow up/
Page 3-l
a
Multi-step Speed Control Application
HV9000
arrow down buttons).
2.6
V,”
signal inversion
1:
V,,, is source B frequency
reference, par. 1. 6 = 1 (default)
Parameter 2. 6 = 0, no inversion
of analog V,” signal
Parameter 2. 6 = 1, inversion
of analog V,” signal
Parameter
max. V,” signal = minimum set
2 16
speed
i_ ~ i
I
$+
min. V,n signal = maximum set
0
Param. 2.4
Param. 2.5
io v
ChOlPMS
speed
Vgure
3.5-5
Vi0 no signal inversion
nput frequency
1
Par 24
Figure 3.5-6
V, signal inversion.
2.7
V,” signal filter time
%
.
Filters out disturbances from the
signal
incoming analog V,, signal. A
long filtering time makes drive
response slower. See figure 3.5-
7.
63%
!
t
F
L
Figure 3.5-7
I
Unfiltered
yn signal filtering.
HV9000
Multi-step Speed Control Application
Page
3-19
2.8 Analog input Ii, signal range
O=O-20mA
I= 4-20 mA
2 = Custom signal span
See figure 3.5-8.
2.9
2.10
Analog input I,, custom
setting minimum/maximum
With these parameters you can
scale the input current to
correspond to a minimum and
maximum frequency range. See
figure 3.5-8.
Minimum setting: Set the 1,” signal
to its minimum level, select
parameter 2. 9, press the Enter
button
Maximum setting:
Set the lin signal to its maximum
level, select parameter 2.10,
press the Enter button
Note! The parameter values can
only be set with this procedure
(not with arrow up/arrow down
buttons).
I
I
Figure 3.5-8 Analog inpuf I, scaling.
2.11 Analog input Iin inversion
1,” is source A frequency
reference, par. 1. 5 = 0 (default)
Parameter 2. 11 = 0, no
inversion of I,“input
Parameter 2. 11 = 1, inversion
of I,“input, see figure 3.5-9.
max. 1,” signal = minimum set
speed
min. 1,” signal = maximum set
speed
Figure 3.5-9
I, signal inversion.
2.12 Analog input 1,” filter time
Filters out disturbances from the
incoming analog lin signal. A long
filtering time makes drive response
slower. See figure 3.5-l 0.
-I
Par. 2. 12
figure 3.5 10
Analog input /in filter time.
Page 3-22
Multi-step Speed Control Application
HV9000
3.1
Analog output function
See
table for parameter 3.1 on
page 3-9.
UnfWxed signal
3.2
Analog output filter time
Filters the analog output signal.
See figure 3.5-17.
3.3
Analog output invert
Inverts analog output signal:
max. output signal = minimum
set value
min. output signal = maximum
set value
-I
Par. 3.2
Figure
3.5- 17
Analog output filtering.
3.4
Analog output minimum
Defines the signal minimum to
be either 0 mA or 4 mA (living
zero). See figure 3.5-l 9.
Figure 3.5 18 Analog output invert.
3.5
Analog output scale
Scaling factor for analog output.
See figure 3.5-19.
Max. speed (n~xf,JfJ
2 x Tm,
2 x pm,
100% x v”M,
1000v
Figure
3.&i- 19
Analog output scale.
Page 3-24
Multi-step Speed Control Application
HV9000
3.13
Torque limit
,
supervision function
0 = No
supervision
1 = Low limit supervision
Par.
3.9 =
2
2 =
High limit supervision
f
f[W
If the calculated torque value goes
under/over the set limit (3.14) this
function generates a warning
message via the digital output
DO1 or via a relay output
ROl or
R02 depending on the settings of
the parameters 3. 6-3.8.
Figure 3.5-20 Output frequency supervision
3.14
Torque limit
,
supervision value
The calculated torque value to be supervised by the parameter 3.13.
Torque supervision value can be reduced below the setpoint with al free analog input
signal, see parameters 2.18 and 2.19.
3.15
Reference limit
,
supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3. 16) this function generates a
warning message via the digital output DO1 and via a relay output ROI or R02
depending on the settings of the parameters 3.6-3.8. The supervised reference is
the current active reference. It can be the source A or B reference depending on DIB6
input or the panel reference if the panel is the active control source.
3.16
Reference limit
,
supervision value
The frequency value to be supervised bv the oarameter 3. 15.
3.17
External brake-off delay
3.18
External brake-on delay
The function of the external brake
can be delayed from the start and
stop control signals with these
parameters. See figure 3.5-21.
YDDlN
The brake control signal can be
w
programmed via the digital output
DO1 or via one of the relay outputs
ROl and R02, see parameters 3.
6-3.8.
Figure 3.5-21
External brake control:
a) StarVStop logic selection par.
2.1=0, lor2
b) Start/Stop logic selection par.
2. 1 = 3.
HV9000
Multi-step Speed Control Application
Page 3-25
3.19
Drive temperature limit supervision
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the unit goes under/over the set limit (3. 20) this function
generates a warning message via the digital output DO1 or
via
a relay output ROI or
R02 depending on the settings of the parameters 3. 6-3.8.
3.20 Drive temperature limit value
The temperature value to be supervised by the parameter 3. 19.
4.1
4.2
AcclDec ramp 1 shape
AcclDec ramp 2 shape
The acceleration and deceleration ramp shape can be programmed with these
parameters.
Setting the value = 0 gives you a linear ramp shape. The output frequency immediately
follows the input with a ramp time
set by parameters 1. 3,l. 4 (4. 3,
4. 4 for Acc/Dec time 2).
t
[Hz1
Setting 0.1-10 seconds for 4. 1
(4.2) causes an S-shaped ramp.
The speed changes are smooth.
Parameter 1. 3/ 1. 4 (4. 3/ 4. 4)
determines the ramp time of the
acceleration/deceleration in the
middle of the curve. See figure 3.5-
22.
~+I-
8’
/’
1
1.3.1.4 _
(4.3.4.4)
:
I
~
1-I
4. 1 (4.2)
,
‘d
4. 1 (4. 2)
I
hl
"DM)OKzO
Figure 3.5-22
S-shapedacceleration/
4.3
4.4
Acceleration time 2
Deceleration time 2
These values correspond to the time required for output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.
2). With this parameter it is possibile to set two different acceleration/deceleration
times for one application. The active set can be selected with the programmable
signal DIA3. See parameter 2.2. Acceleration/deceleration times can be reduced
with a free analog input signal. See parameters 2. 18 and 2. 19.
deceleration
Page 3-26
Multi-step Speed Control Application
HV9000
4.5 Brake chopper
0 = No
brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the drive is decelerating the motor, the energy stored in the inertia of the motor
and the load is fed into the external brake resistor. If the brake resistor is selected
correctly the drive is able to decelerate the load with a torque equal to that of
acceleration. See the separate Brake resistor installation manual.
4.6
Start function
Ramp:
0
The drive starts from 0 Hz and accelerates to the set reference frequency within
the set acceleration time. (Load inertia or starting friction may cause prolonged
acceleration times).
Flying start:
1
The drive starts into a running motor by first finding the speed the motor is
running at. Searching starts from the maximum frequency down until the actual
frequency reached. The output frequency then accelerates/decelerates to the
set reference value at a rate determined by the acceleration/deceleration ramp
parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short utility voltage interruptions.
4.7
Stop function
Coasting:
0
The motor coasts to an uncontrolled stop with the HV9000 off, after the Stop
command.
Ramp:
1
After the Stop command, the speed of the motor is decelerated according
to the deceleration ramp time parameter. If the regenerated energy is high it
may be necessary to use an external braking resistor for faster
deceleration.
4.8
DC braking current
Determines whether DC braking is ON or OFF. It also determines the braking duration
time of the DC-brake when the motor is stopping. The function of the DC-brake
depends on the stop function, parameter 4. 7. See figure 3.5-23.
0
DC-brake is not used
ro
DC-brake is in use depending on the setup of the stop function
(param. 4. 7). The time is set by the value of parameter 4. 9:
HV9000
Stop-function
Multi-steo Weed Control
ADDkatiOn
= 0 (coastinak
Page
3-27
After the stop command, the motor will coast to a stop with the HV9000 off.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC- braking
starts. If the frequency is 2 nominal frequency of the motor (par. 1 .ll), the value of
parameter 4.9 determines the braking time. When the frequency is I 10% of the
nominal, the braking time is 10% of the set value of parameter 4.9.
Stop-function = 1 (ramp):
After a Stop command, the speed of the motor is reduced based on the deceleration
ramp parameter. If no regeneration occurs due to load inertia DC-braking starts at a
speed defined by parameter 4. 10.
output frequency
, Motor speed
fn
I /
output frequency
, = 1 Y par 4.9
Figure 3.5-23
DC-braking
time when stop = coasting.
The braking time is defined with
parameter 4.9.
If a high inertia exists it is
recommended to use an external
braking resistor for faster
deceleration. See figure 3.5-24.
4.10
Execute frequency of DC-
brake during ramp Stop
See
figure 3.5-24.
Figure 3.5-24
DC-braking time when stop
function = ramp.
Page 3-26
Multi-step Speed Control Application
HV9000
4.11
DC-brake time at start
0
DC-brake
is not used
ro
DC-brake is active when the
start command is given. This
parameter defines the time
before the brake is released.
After the brake is released,
the output frequency
increases according to the
set start function parameter
! Par4.11:
4. 6 and the acceleration
I-
parameters (1.3,4.1 or 4.2,
4.3). See figure 3.5-25.
Figure 3.525 DC-braking time at start
5. l- 5.6 Prohibit frequency area
Low limit/High limit
I
4
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance
problems.
With these parameters it is
possible to set limits for three “skip
frequency” regions between 0 Hz
and 500 Hz. The accuracy of the
setting is 0.1 Hz. See figure 3.5-26.
Figure 3.526 Example of prohibit frequency
area setting.
HV9000
6.1
Multi-step Speed Control Application
Page 3-29
Motor control mode
0 = Frequency control: The I/O terminal and panel references are frequency
(V/Hz) references and the drive controls the output frequency (output
freq. resolution 0.01 Hz)
1 = Speed control: The I/O terminal and panel references are speed references
(sensortess vector) and the drive controls the motor speed (control accuracy *
0.5%).
6.2 Switching frequency
Motor noise can be minimized by using a high switching frequency. Increasing the
switching frequency reduces the current capacity of the HV9000.
Before changing the frequency from the factory default 10 kHz (3.6 kHz ~-40 Hp) check
the drive derating in the curves shown in figures 5.2-2 and 5.2-3 in chapter 5.2 of the
User’s Manual.
6.3
6.4
Field weakening point
Voltage at the field weakening point
The field weakening point is the output frequency where the output voltage
reaches the set maximum value. Above that frequency the output voltage remains
at the set maximum value.
Below that frequency output voltage depends on the setting of the V/Hz curve
parameters 1.8, 1.9, 6.5, 6. 6 and 6. 7. See figure 3.5-27.
When the parameters 1. 10 and 1. 11, nominal voltage and nominal frequency of
the motor are set, parameters 6. 3 and 6.4 are also set automatically to the
corresponding values. If you need different values for the field weakening point
and the maximum output voltage, change these parameters after setting
parameters 1. 10 and 1. 11.
6.5
V/Hz curve, middle point frequency
If the programmable V/Hz curve has been selected with parameter 1. 8, this
parameter defines the middle frequency point of the curve. See figure 3.5-27.
6.6
V/Hz curve, middle point voltage
If the programmable V/Hz curve has been selected with parameter 1.8, this
parameter defines the middle point voltage (% of motor nominal voltage) of the
curve. See figure 3.527.
6.7
Output voltage at zero frequency
If the programmable V/Hz curve has been selected with parameter 1.8, this
parameter defines the zero frequency voltage of the curve. See figure 3.5-27.
Page 3-30
Multi-step Speed Control Application
HV9000
I
Parameter
“”
UM
6.4
i
Parameter 6.6
Default 10%
Parameter 6.7
Default 1.3 %
Parameter 6.5 Parameter 6.3 qHz]
(Default 5 Hz)
Figure 3.5-27 Programmable V/Hz curve.
6.6
Overvoltage controller
6.9
Undervoltage controller
These
parameters allow the ovedundervoltage controllers to be switched ON or
OFF.
This may be useful in
cases where the utility
supply voltage varies
more than -15%-
+10% and the application requires a constant speed. If the controllers are ON, they
will change the motor speed in over/undervoltage cases. Overvoltage = faster,
undervoltage = slower.
Over/undetvoltage trips may occur when controllers are not used.
7.
1 Response to the reference fault
0 = No
response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, always coasting stop mode after fault
A warning or a fault action and message is generated if the 4-20 mA reference
signal is used and the signal falls below 4 mA. The information can also be
programmed via digital output DO1 and via relay outputs R01 and
R02.
7.2 Response to external fault
0 = No
response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3. The information can also be programmed into digital output
DO1 and into relay outputs ROl and R02.
7.3
Phase supervision of the motor
0 = No
action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
HV9000
Multi-step Speed Control Application
Page 3-31
7.4
Ground fault protection
0 = No
action
2 =
Fault
Ground fault protection ensures that the sum of the motor phase currents is zero.
The standard overcurrent protection is always working and protects the frequency
converter from ground faults with high current levels.
Parameters 7.5-7.9
General
Motor thermal protection
Motor thermal protection is to protect the motor from overheating. The HV9000 drive
is capable of supplying higher than nominal current to the motor. If the load requires
this high current there is a risk that motor will be thermally overloaded. This is true
especially at low frequencies. With low frequencies the cooling effect of the motor
fan is reduced and the capacity of the motor is reduced. If the motor is equipped
with a separately powered external fan, the load derating at low speed is small.
Motor thermal protection is based on a calculated model and it uses the output
current of the drive to determine the load on the motor. When the motor is powered
from the drive, the calculated model uses the heatsink temperature to determine
the initial thermal state of the motor. The calculated model assumes that the ambient
temperature of the motor is 40°C.
Motor thermal protection can be adjusted by setting several parameters. The thermal
current IT specifies the load current above which the motor is overloaded. This
current limit is a function of the output frequency. The curve for IT is set with
parameters 7.6,7.7 and 7.9, refer to the figure 3.5-28. The default values of these
parameters are set from the motor nameplate data.
With the output current at IT the thermal stage will reach the nominal value (100%).
The thermal stage changes with the square of the current. With output current at
75% of IT the thermal stage will reach 56% and with output current at 120% of IT the
thermal stage would reach 144% The function will trip the drive (refer par. 7. 5) if
the thermal state reaches a value of 105%. The response time of the thermal stage
is determined by the time constant parameter 7.8. The larger the motor, the longer
it takes to reach the final temperature.
The thermal state of the motor can be monitored through the display. Refer to the
table for monitoring items. (User’s Manual, table 7.3-1).
CAUTION!
A
!
The calculated
mode/ does not protect the motor if the cooling of the
motor is reduced either by blocking the airflow or due to dust or dirt.
Motor thermal protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is selected, the drive will stop and activate the fault stage.
7.5
HV9000
7.8
Multi-step Speed Control Application
Motor thermal protection, time constant
Page
3-33
This time can be set between 0.5-300 minutes. This is the thermal time constant
of the motor. The larger the motor the greater the time constant. The time constant
is defined as the time that it takes the calculated thermal stage to reach 63% of its
final value.
The motor thermal time is specific to a motor design and it varies between different
motor manufacturers.
The default value for the time constant is calculated based on the motor nameplate
data from parameters 1 .12 and 1 .13. If either of these parameters is reset, then this
parameter is set to default value.
If the motor’s ts -time is known (given by the motor manufacturer) the time constant
parameter could be set based on ts -time. As a rule of thumb, the motor thermal
time constant in minutes equals to 2xte (te in seconds is the time a motor can safely
operate at six times the rated current). If the drive is stopped the time constant is
internally increased to three times the set parameter value. Cooling in the stop
stage is based on convection with an increased time constant.
7.9
Motor thermal protection, break point frequency
The frequency can be set between IO-500 Hz. This is the frequency break point of
the thermal current curve. With frequencies above this point, the thermal capacity of
the motor is assumed to be constant. See figure 3.5-28.
The default value is based on the motor’s nameplate data, parameter 1. 11. It is 35
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally it is 70% of the
frequency at the field weakening point (parameter 6.3). Changing either parameter
1. 11 or 6. 3 will restore this parameter to its default value.
7.10
Stall protection
Operation:
0 =
Not in use
1 = Warning
2 = Trip function
Tripping and warning will give a display indication with the same message code. If
tripping is set on, the drive will stop and activate the fault stage. Setting the parameter
to 0 will deactivate the protection and will reset the stall time counter to zero.
Figure 3.5-29
Calculating motor temperature.
Paoe 3-34
Multi-steD SDeed Control Awlication
HV9000
Parameters 7. lo- 7.13, Stall protection
General
Motor stall protection protects the motor from short time overload situations like a
stalled shaft. The reaction time of stall protection can be set shorter than with motor
thermal protection. The stall state is defined with two parameters, 7.11. Stall Current
and 7.13. Stall Frequency. If the current is higher than the set limit and output
frequency is lower than the set limit the stall state is true. There is actually no real
indication of the shaft rotation. Stall protection is a type of overcurrent protection.
7.11
Stall current limit
The current can be set between O.O-200% x InMotor.
In a stall the current has to be above this limit. See figure 3.5-30. The value is set as
a percentage of the motor’s nameplate nominal current, parameter 1.13. If parameter
1. 13 is adjusted, this parameter is automatically restored to its default value.
7.12
Stall time
t1
1
The time can be set between
2.0-l 20 s. This is the maximum
allowed time for a stall. There is
an internal up/down counter to
count the stall time. See figure
Stall area
I
3.5-31. If the stall time counter
value goes above this limit the
protection will cause a trip (refer
Par. 7.
11
to parameter 7. 10).
7.13 Maximum stall frequency
The frequency can be set
between l-f,,X (parameter 1.
2).
In a stall, the output frequency
Figure 3.5-30 Setting the stall
characteristics.
has to be smaller than this
figure 3.530.
Stall time counter
1
Parameters 7.14- 7.17
Underload protection, General
Trip area
The purpose of motor underload
Par. 7. 12
protection is to ensure that there
I
is load on the motor while the
Tripiwarnlng
par. 7.
10
drive is running. If the motor load
is reduced, there might be a
problem in the process, e.g.
I-
broken belt or dry pump.
Motor underload protection can
be adjusted by setting the
underload curve with parameters
7.15 and 7.16. The underload
curve is a squared curve set
F@ure 3.5-31
Counting the stall time.
between zero frequency and the
HWOOO
Multi-step Speed Control Application
Page
3-35
field weakening point. The protection is not active below 5Hz (the underload
counter value is stopped). See figure 3.5-32.
The torque values for setting the underload curve are set with percentage values
which refer to the nominal torque of the motor. The motor’s nameplate data,
parameter 1. 13, the motor’s nominal current and drive’s nominal current Icr are
used to find the scaling ratio for the internal torque value. If other than a standard
motor is used with the drive, the accuracy of the torque calculation is decreased.
7.14
Underload protection
Operation:
0 = Not in use
1 = Warning
2 = Fault
Tripping and warning will give a display indication with the same message code. If
tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection, by setting this parameter to 0, will reset the underload
time counter to zero.
7.15
Underload protection, field weakening area load
The torque limit can be set between 20.0-l 50 % x TnMotor.
This parameter is the value for the minimum allowed torque when the output
frequency is above the field weakening point. See figure 3.5-32. If parameter 1.13 is
adjusted, this parameter is automatically restored to its default value.
7.16
Underload protection, zero frequency load
50 % x TnMotor. The torque limit can be set between 10.0-l
This parameter is the value for the minimum allowed torque with zero frequency.
Refer to the figure 3.5-32. If parameter 1.13 is adjusted this parameter is automatically
restored to its default value.
7.17
Underload time
s. This time can be set between 2.0-600.0
This is the maximum allowed time for an underload state. There is an internal up/
down counter to accumulate the underload time. Refer to the figure 3.5-33.
If the underload counter value goes above this limit, the protection will cause a trip
(refer to the parameter 7. 14). If the drive is stopped, the underload counter is reset
to zero.
Figure
3.5-32 Setting
of minimum load.
Figure 3.5-33 Counting the underload time
Page 3-36
Multi-step Speed Control Application
HV9000
8.1
Automatic restart: number of tries
8.2
Automatic restart: trial time
The Automatic restart function restarts the drive after the faults selected with
parameters 8. 4 - 8. 8. The Start function for Automatic restart is selected with
parameter 8.3. See figure 3.5-34.
f
Number of faults
4
I
I
kil
,
I
Three faults
Four faults
Figure 3.5-34 Automatic restart.
Parameter 8.1 determines how many automatic restarts can be made during the
trial time set by the parameter 8.2.
The time counting starts from the first autorestart. If the number of restarts does not
exceed the value of the parameter 8.1 during the trial time, the count is cleared after
the trial time has elapsed. The next fault starts the counting again.
8.3
Automatic restart, start function
The parameter defines the start mode:
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
8.4
Automatic restart after undervoltage trip
0 = No automatic restart after undervoltage fault
1 = Automatic restart after undervoltage fault condition returns to the
normal condition (DC-link voltage returns to the normal level)
8.5
Automatic restart
after overvoltage trip
0 = No
automatic restart after overvoltage fault
1 = Automatic restart after overvoltage fault condition returns to the
normal condition (DC-link voltage returns to the normal level)
8.6
Automatic restart after overcurrent trip
0 = No automatic restart after overcurrent fault
1 = Automatic restart after overcurrent faults
HWOOO
8.7
Multi-step Speed Control Application
Automatic restart after reference fault trip
Page 3-37
0 = No automatic restart after reference fault
1 = Automatic restart after analog current reference signal (4-20 mA)
returns to the normal level (24 mA)
a.8
Automatic restart after over-/undertemperature fault trip
0 = No automatic restart after temperature fault
1 = Automatic restart after heatsink temperature has returned to its
normal level between -1 O”C-+75”C.
Notes:
Page 3-38
Multi-step Speed Control Application
HV9000
Notes:
HV9000
PI-control Application
Page 4-1
PI-CONTROL APPLICATION
(par. 0.1 = 5)
CONTENTS
4 PI-control Application
......................
.4-l
4.1 General
.......
.
................................
4-2
4.2 Control l/O..
.................................
.4-2
4.3
Control signal logic.. ..................... 4-3
4.4
Parameters Group 1
...................
.4-4
4.4.1 Parameter table
.................
.4-4
4.4.2 Description of 4- 5
4.5
Special parameters, Groups 2-8.. 4-8
4.5.1 Parameter tables .................. 4-8
4.5.2 Description of Groups..
......
.4-l 5
4.6
Panel reference ........................... .4-36
4.7
Monitoring data. ............................ 4-36
Page 4-2
PI-control Application
HWOOO
4.1 General
In PI-control application there are two I/O-
terminal control sources. Source A is the PI-
controller and source B is the direct frequency
reference. The control source is selected with
DIB6 input.
The PI-controller reference can be selected
from an analog input, motorized (digital)
potentiometer or panel reference. The actual
4.2 Control I/O
value can be selected from the analog inputs
or from mathematical functions of the analog
inputs.
The direct frequency reference can be used
for control without the PI-controller. The
frequency reference can be selected from
analog inputs or panel reference.
l
NOTE! Remember to connect CMA and
CMB inputs.
PI-controller
--
Figure 4.2- 1 Default I/O configuration and connecfion example of the
PI-Control Application with Z-wire transmirter.
Page 4-4
4.4 Basic parameters, Group 1
4.4.1 Parameter table, Group 1
code
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
V/Hz ratio selection
+2
Deceleration time 1
PI-control Application HV9000
Default
OH.?
Custom Description IPee
Time from f,,, (1.1) to f,,, (1.2)
I
4-5
1
0.1-3000.0 s
1
0.1 s Time from f,,, (1.2) to f,,, (1. 1)
1
1
dl
“‘Output con limit [A] of the unit 4-5
4-5
1.9 4-6
1.10
,:
1.11
f, from the nameplate of
the motor
n, from the nameplate of
the motor
I, from the nameplate of
the motor
Supply
voltage
mI=+
360-400
366-500
525-690
Parameterconceal
230 V
36OV
460 v
575v
( 1
4-7
1.12
4-7
4-7
I
I
I
I
I
Voltage code 2
Voltage code 4
I
4-7
I
Voltage code 5
Voltage code 6
Visibility of the parameters:
0 = All parameter groups visible
1 = Only group 1 is visible
Disables parameter changes:
0 = Changes enabled
1 = Changes disabled
I
1
-1
O
0
I
4-7
1.16 Parametervaluelock
/
(tl
/
1
4-7
Tab/e 4.4- 1 Group 1 basic parameters.
* If 1. 2 > motor synchr. speed, check suitability
for motor and drive system.
Selecting 120 Hz/500 Hz range see page 4-5.
** Default value for a four pole motor and a
nominal size HV9000.
*** Up to MlO. Bigger classes case by case
Note! m =
Parameter value can
be
changed
only when the drive is stopped.
HV9000 PI-control Aoolication
Page 4-5
4.4.2 Description of Group 1 parameters
1.1,1.2
Minimum
I
maximum frequency
Defines frequency limits of the HV9000.
The default maximum value for parameters 1. 1 and 1.2 is 120 Hz. By setting 1.2
= 120 Hz when the drive is stopped (RUN indicator not lit) parameters 1.1 and 1.
2 are changed to 500 Hz. At the same time the resolution of the panel is changed
from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting parameter 1.2
= 119 Hz while the drive is stopped.
1.3,1.4
Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to acceler-
ate from the set minimum frequency (par. 1. 1) to the set maximum frequency
(par. 1.2).
1.5
PI-controller gain
This parameter defines the gain of the PI-controller.
If this parameter is set to 1 OO%, a 10% change in error value causes the controller
output to change by 1 .O Hz.
If the parameter value is set to 0, the PI-controller operates as an l-controller.
1.6
1.7
PI-controller I-time
Defines the integration time of the PI-controller
Current limit
This parameter determines the maximum motor current that the HV9000 will pro-
vide short term.
A
0
1.8
V/Hz ratio selection
Linear:
0
The voltage of the motor changes linearly with the frequency in the con-
stant flux area from 0 Hz to the field weakening point
(par. 6.3) where a constant voltage (nominal value) is supplied to the
motor. See figure 4.4-2.
A linear V/Hz ratio should be used in constant torque applications.
This default setting should be used if there is no special requirement for
another setting.
Squared:
The voltage of the motor changes following a squared curve form with
1
the frequency in the area from 0 Hz to the field weakening
point (par. 6.3) where the nominal voltage is supplied to the motor. See
figure 4.4-2.
The motor runs undermagnetized below the field weakening point and produces
less torque and electromechanical noise. A squared V/Hz ratio can be used in
applications where the torque demand of the load is proportional to the square of
the speed, e.g. in centrifugal fans and pumps.
Page
4-6
PI-control Application
HV9000
Default: Nominal voltage of
Field weakening point
the motor
Default: Nominal
frequency of the
motor
- WI
1
Figure
4.4-2
Linear and squared V/Hz curves
Programm.
The V/Hz curve can be programmed with three different points.
V/Hz curve
The parameters for programming are explained in chapter 4.5.2.
2
A programmable V/Hz curve can be used if the standard settings do
not satisfy the
needs of the application. See figure 4.4-3.
UM
Parameter
“”
f
Default: nominal /I
6.4
voltage of the mot
Parameter 6.6
Default 10%
Parameter 6.7
Default 1.3 %
Parameter 6.5 Parameter 6.3 f[Hz]
(Default 5 Hz)
Figure 4.4-3
Programmable V/Hz curve.
1.9
V/Hz optimization
Automatic
The voltage to the motor changes automatically which makes the
torque
motor produce enough torque to start and run at low frequencies.
boost
The voltage increase depends on the motor type and horsepower.
Automatic torque boost can be used in applications where starting torque due to
starting friction is high, e.g. in conveyors.
NOTE!
In
high torque -low speedapplications - it is likely the motor will overheat.
If the motor has to run for a prolonged time under these conditions, special
attention must be paid to cooling the motor. Use external cooling for the
motor if the temperature rise is too high.
HV9000 PI-control
Nominal voltage of the motor
ADDfication
Paae 4-7
1.10
Find
this value V”from the nameplate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6. 4, to
100% x Vnmotor.
1.11
Nominal frequency of
the
motor
Find the nominal frequency f,, from the nameplate of the motor.
This parameter sets the frequency of the field weakening point, parameter 6. 3, to
the same value.
1.12
1.13
Nominal speed of the motor
Find this value nn from the nameplate of the motor.
Nominal current of the motor
Find the value In from the nameplate of the internal motor protection
function uses this value as a reference value.
1.14
Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for voltage codes 2, 4, 5 and 6. See table 4.4-l
1.15
Parameter conceal
Defines which parameter groups are available:
0 = all parametergroups are visible
1 = only group 1 is visible
1.16
Parameter value lock
Defines access to the changes of the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
To adjust more of the functions of the PI-Control application, see chapter 4.5 to
modify the parameters of Groups 2-6.
Page 4-8
PI-control ADDlication
HV9000
4.5 Special parameters, Groups 2-9
4.5.1 Parameter tables
Group 2, Input signal parameters
-
code
!. 1
ammeter
ilA2 function
erminal9)
m
-
)efault
1
Iescription
PZ
w
4
I= Not used
I =
Ext. fault, closing contact
! = External fault, opening contact
3 = Run enable
1 =Acceler./deceler. time selectior
I
j = Reverse
3 = Jog speed
7 = Fault reset
3 = . operation prohibit
3 = DC-braking command
IO = Motor (digital) pot. UP
I= Not used
I =
Ext. fault, closing contact
! = External fault, opening contact
3= Run enable
1= Acc./dec. time selection
5 = Reverse
3 = Jog speed
7 = Fault reset
3 = . operation prohibit
3 = DC-braking command
10 = Motor (digital) pot. DOWN
3=&1OV
1 = Custom setting range
Range
O-10
3?p
-
1
-15
2.2
bIA3function
erminall0)
&lo
1 7
4 -16
2.3
2.4
-
IIn signal range
rln custom setting min.
I,” custom sethng max
I,, signal inversion
I,, signal filter time
,” signal range
4 -1c
4 -1f
-
4 .-lf
0 = Not inverted
1 = Inverted
0 = No filtering
O=&-20mA
1=4_20mA
2 = Custom setting range
4 .-lf
-
4 .-li
4 .-li
-
.-1;
4
4 .-1;
,” custom setting min.
,” custom
setting max.
1,” signal inversion
I” signal filter time
)IB5function
terminal 15)
•I
.Ol -10.00
o-9
3.01S
1
0 = Not inverted
1 = Inverted
0.10s
6
0 = No filtering
4 ,1;
4 I-11
-
4
I-lf
0 =
Not used
1 = Ext. fault, closing contact
2 = External fault, opening contac
t
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jog speed
7 = Fault reset
6 = Act idec. operation prohibit
9 = DC-braking command
-
Note! m =
P
arameter value can be changed only when the drive is stopped
HV9000
PI-control Application
Page 4-9
3 = Signal from internal motor pot.
reference, source B
1 = Analog current input (term. 4)
2 = Sat
reference
from the panel
3 = Signal from internal motor pot.
4 = Signal from internal motor pot.
Note! m =
P arameter
value can be changed only when the drive is stopped
Page
4-l 0
PI-control Application
HV9000
Group 3, Output and supervision parameters
3ustm
I
Analog output function
1111111
Description
( )= Not used
1
I =
O/P frequency
! =
Motor speed
:
3 = O/P current
1
1= Motor torque
5 = Motor power
t
j = Motor voltage
7 = DC-linkvolt.
PZ
cle
4. .21 Scale 100%
(c+f,&
(0-max. speed)
(o-2.0 x t”Hv9)
(o-2 x T,,u.,,)
(&2 x P,,&
(O-100% xVnMb
,)
(0-1000 V)
4 -21
0 = Not inverted
1 = Inverted
O=OmA
1=4mA
4 -21
4 -21
4 -21
(
3 = Not used
-
4nalog output filter time
Analog output inversion
Analog output minimum
4naloq output scale
3.6
3igital output function
I
1 = Ready
2=Run
3 = Fault
4 = Fault inverted
5 = HV9000 overheat warning
,
6 = External fault or warning
7 = Reference fault or warning
6 = Warning
9 = Reversed
10 = Jog speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 =Torque limit supervision
16 = Reference limit supervision
17 = External brake control
16 = Control from I/O terminals
19 = Drive temperature limit
supervision
20 = Unrequested rotation directior
21 = External brakecontrol invelte ;
O-21
&21
o-2
1
4 m
3.7
3.6
3.9
Relay output 1 function
I
Relay output 2 function
I
Outputfreq. limit 1
supervwon function
Output freq. limit 1
supervision value
2
3
0
As parameter 3.6
As parameter 3.6
O=No
1 = Low limit
2 = High limit
4 t-2:
4 .-2:
1-2:
4
1
1
3.1c
0.6-f,,
(par. 1.2)
1.1 H
-
0.0 Hz
-
1
1-2:
-
Note! a =
P arameter value can be changed only when the drive is stopped.
HV9000
PI-control Application Page 4-11
3.12
0
I I
I I
O=No
1 = Low limit
2 = Hiah limit
Torque limit 00.0%
I I
4-23
I I
4-23
3.23
3.24
3.25
0
0
100%
See parameter 3.2
See parameter 3.3
See parameter 3.4
See parameter 3.5
4-21
4-21
4-21
4-21
Group 4, Drive control parameters
Note! m =
P
arameter value can be changed only when the drive is stopped.
Page 4-l 2
PI-control Awlication
I
I
Ranae
-
0.15-1.5x
I~HVS (A)
HV9000
I
code
I
Parameter
I steo I
Default
I custom
Description
I ’ I O I
0 = Coasting
1 =
Ramp
Page
4-25
4-25
I
4.7
I
4.6
4.9
4.10
Stop function
DC-braking current
I
0.01 s
0.00 s
15Hz
I
0 = DC-brake is off at Stop 4-25
4-26
DC-braking timeat stop
Turn on frequency of
DC-brake at rams Stoo
0.00-250.00s
I I
/ 4.11
4.12
I
1
-25.00s
/
/
0.01 s 1 0.00s
I
1
0 = DC-brake is off at Start 4-27
4-27
1
DC-braketimeatStart
Jog speed reference
I I
5. 1
5.2
5.3
0.1 Hz 1
Group 5, Prohibit frequency parameters
I code1
Parameter
Prohibitfrequency
range 1 low limit
Prohibitfrequency
range2 high limit
Prohibit frequency
range 2 low limit
Prohibitfrequency
range 2 high limit
Prohibitfrequency
ranae 3 low limit
Prohibit frequency
range 3 high limit
I Range
f,,,-
par. 5. 2
fnNrfln,x
(1.1)(1.2)
fInI”_
par. 5.4
fnw-f,,x
(1.1) (1.2)
frlw-
par. 5. 6
fnw-fmax
(1.1)(1.2)
0.1 Hz 0.0H.z
Description
I Page I
1 4-27
1
3 = no prohibit frequency range
:
I I
I 4-271
5.4
5.5
5.6
I 1
41
41
1
Descriptum
0 = no prohibit frequency range
0 = no prohibit frequency range
Group 6, Motor control parameters
I
code/
Parameter
6.1
6.2
6.3
6.4
6.5
Motor control mode
Switchinq freauencv
Field weakening
Voltage at field
weakening point
V/Hz-curve
;;,:/;,Enid
Output voltage at
mid
a
fl
poi
1 ~anae 1 Steo
I
Default
I
Custom
I
Paael
4-27
427
0 = Frequency control
1 = Speed control
1.0-16.0 kHz
3&500
1%200%
11111 x V,,,t
o.(Mm=
;,O%
0.1 Hz
0.01%
0.0 Hz
0.00%
Parameter maximum value =
param.
6.4
Hz
0.1 kHz 10/36kHz
1 Hz
1%
Param.
1.11
100%
Depends on HP ratinq
4-28
4-28
4-26
4-28
4-28
0 = Controller is not operating
1 = Controller is in operation
4-28
4-28
point frequency
6.6
6.7
6.8
6.9 Undervoltagecontroller C&l 1 1 0 = Controller is not operating
1 = Controller IS in operation
Note!m=
Parameter value can be changed only when the drive is stopped.
HV9000
Group 7, Protections
code
7.1
Parameter
Response to
reference fault
PI-control Application
Page 4-l 3
Step
1
I
Lefault
0
2
2
2
2
CUStCfll
Description
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3 = Fault, always coasting stop
0 = No action
1 = Warning
2 = Fault, stop according to
par. 4.7
3= Fault, always coasting stop
7.2 Response to
external fault
7.3
7.4
7.5
Phase supervision of
the motor
Ground fault protection
Motorthermal protection
O--2
&2
c-2
1
4
t
%
0.5
min.
1 Hz 35 Hz
s
1 Hz
25Hz
0 = No action
2 = Fault
0 = No action
2 = Fault
0 = No action
1 = Warning
2 = Fault
1
Page
4-29
4-29
4-29
4-29
4-30
i
4-30
4-30
Motorthermal protection
breakpoint current
Motorthermal protection
zero frequency current
Motorthermal protection
time constant
Motorthermal protection
break point frequency
Stall protection
io.+150.0
5.0-150.0%
x
hOTOR
x I”MOTOR
0.5-300.0
minutes
1 o--500 Hz
O-2
Default value is set according
to motor nominal current
4-31
4-31
0 = No action
1 = Warning
2 = Fault
Stall current limit
Stall time
5.+200.0%
x t”MOTOR
2.c-120.0
t-fInax
&2
1
0 = No action
1 = Warning
2 = Fault
7.15
7.1E
7.17
Underload pmt., field
weakening area load
Underload protection,
zero
frequency load
Underload time
0.&150,.09
x T~MOTOR
5.&-150.0%
~T,MOTOR
2.&-600.0 s
1 .O%
1.0%
1.0s 20.0s
I
50.0%
10.0%
-I
4-33
4-34
4-34
/
4-34J
Page4-14
PI-control Application
HV9000
Group 8, Autorestart parameters
a.7 Automatic restart after
reference fault trip
overhndeltemperature
fault trip
O-1
&l
1
1
0
0
O=No
1 =Yes
O=No
1 =Yes
4-35
4-35
a.8
Automatic restart after
Table 4.5- 7
Special
parameters,
Groups 2-8.