最新消息: USBMI致力于为网友们分享Windows、安卓、IOS等主流手机系统相关的资讯以及评测、同时提供相关教程、应用、软件下载等服务。

PowerFlex 700S 和 700H 框架 11 替换电源结构安装指南说明书_

IT圈 admin 33浏览 0评论

2024年9月24日发(作者:柴湛芳)

Introduction

What You Need to Do

Installation Instructions

PowerFlex

®

700S and 700H Frame 11

Replacement Power Structures

Use this document to install a replacement power structure on a PowerFlex

700S or 700H frame 11 drive. This document covers the following

replacement power structures:

Spare Module Catalog PowerFlex 700HPowerFlex 700HPowerFlex 700SPowerFlex 700S

StringAC InputDC InputAC InputDC Input

SK-H1-PWRMOD-E46020CE46020CK46020DE46020DK460

20CF46020CM46020DF46020DM460

SK-H1-PWRMOD-E50220CE50220CK50220DE50220DK502

20CF50220CM50220DF50220DM502

SK-H1-PWRMOD-E59020CE59020CK59020DE59020DK590

20CF59020CM59020DF59020DM590

SK-H1-PWRMOD-D59020CC59020CH59020DC59020DH590

20CD59020CJ59020DD59020DJ590

SK-H1-PWRMOD-D65020CC65020CH65020DC65020DH650

20CD65020CJ65020DD65020DJ650

SK-H1-PWRMOD-D73020CC73020CH73020DC73020DH730

20CD73020CJ73020DD73020DJ730

❐ Step 1: Configure new power structure

❐ Step 2: Remove power from existing drive

❐ Step 3: Remove old power structure

❐ Step 4: Install new power structure

❐ Step 5: Connect new power structure to components in drive

❐ Step 6: Install product identification label on new power structure

❐ Step 7: Start drive

2PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Step 1:Configuring the

New Power Structure

Before configuring the power structure you must remove the protective

covers from the drive. Refer to publication PFLEX-IN006… , Installation

Instructions - PowerFlex 700S and 700H High Power Drives, for assistance

in removing these covers.

Configuring a DC Input Drive

Power structures are shipped from the factory pre-configured for DC input

operation.

Connecting an AC Input Drive

Power structures are shipped from the factory pre-configured for DC input

operation. When installing a replacement power structure on a drive with

AC input, you must remove the X2 plug from it’s protective sleeve and plug

the cable into the ASIC and Rectifier board(s).

Task

A

B

C

D

E

F

Description

Remove the cover from the ASIC board assembly.

Disconnect the ASIC fan from the assembly by unplugging the cable from X1 on the ASIC

board (see Figure 1on page3

for location).

Remove the cover from the connector on the loose cable (bundled with the flat gate driver

board cables) and connect the cable to the X2 connector on the ASIC board (see Figure

1on page3 for location).

Connect the other end of the cable connected to X2 on the ASIC board to the X13

connector for the Rectifier board(s) on the V Phase and W Phase (if present) power stack

(see Figure 2on page3

for location).

Connect the fan cable to the X1 connector on the ASIC board.

Install the cover on the ASIC board assembly.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures3

Figure 1 ASIC Board Connections

X6

X9X15

H1H2H3H4H5H6H7

Connect cable to

X2 connector

X2

X1

X1 connector

H8H9H10H11H12H13

X3X4X5

Figure 2 Rectifier Board Connectors

Cable connected to

X2 on ASIC board

X13

connectors

for Rectifier

boards

4PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Configuring the EMC Filter

Frame 11 size drives are equipped with common mode capacitors. To guard

against drive damage, these capacitors should be disconnected depending

upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground

If you are installing a 400/480V AC input drive on an ungrounded

distribution system or high resistive ground, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Should insulate terminal X4 on the Rectifier circuit board- refer to

Insulate Terminal X4 on the Rectifier Circuit Boardon page7.

If you are installing a 600/690V AC input drive on an ungrounded

distribution system or high resistive ground, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Must insulate terminal X4 on the Rectifier circuit board- refer to Insulate

Terminal X4 on the Rectifier Circuit Boardon page7.

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Must insulate terminal X4 on the Rectifier circuit board- refer to Insulate

Terminal X4 on the Rectifier Circuit Boardon page7.

Note:Refer to Wiring and Grounding Guidelines for Pulse Width

Modulated (PWM) AC Drives - Installation Instructions,

publication DRIVES-IN001…, for additional information on an

ungrounded distribution system or high resistive ground

installation.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures5

The jumper is located on the Rectifying Module(s). For drives with one

Rectifying Module, it is located on the upper-right side of the middle power

stack (V Phase). For drives with two Rectifying Modules, they are located

on the upper-right side of the middle (V Phase) and right-side (W Phase)

power stacks.

Voltage Class

400/480V AC

Amps

590

650

730

460

502

590

Number of Rectifying Modules

2

2

2

1

1

2

600/690V AC

Figure 3 Common Mode Jumper and Rectifier Circuit Board Location

Common

Mode jumper

There is one jumper located on each Rectifying

Module. The Rectifying Modules are located on

the upper-right side of the center and right side

power stack of the drive’s power structure.

Front View

of Assembly

Rectifier Circuit Board

6PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Move the Common Mode Jumper to the Disconnected Position

the lettered steps below to move the common mode jumper to the

disconnected position (refer to Figure 3on page5 for jumper location).

Task

A

B

C

D

Description

Loosen the upper screw.

Remove the lower screw.

Move the jumper to the horizontal position.

Install and tighten the screws.

A

Front View of

Power Structure

D

C

B

Rectifying Circuit Board

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures7

Insulate Terminal X4 on the Rectifier Circuit Board

the lettered steps below to insulate terminal X4 on the Rectifier

circuit board (refer to Figure 3on page5 for jumper location).

Task

A

B

Description

Remove the screw from the X4 connection on the Rectifier circuit board.

Insulate the top and bottom of the X4 connection on the Rectifier circuit board.

Important:Do not install the screw and washer that was removed from this

connection.

A

Side View of Power Structure

B

X4

X1

X41

X4

X1

X41

Rectifier Circuit Board

8PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Step 2:Removing Power

From the Existing Drive

Step 3:Removing the Old

Power Structure

Step 4:Installing the New

Power Structure

!

ATTENTION: To avoid an electric shock hazard, verify that

the voltage on the bus capacitors has discharged before servicing

the drive. Check the DC bus voltage at the Power Terminal

Block by measuring between the +DC and -DC terminals,

between the +DC terminal and the chassis, and between the -DC

terminal and the chassis. The voltage must be zero for all three

measurements.

Remove power before making or breaking cable connections.

When you remove or insert a cable connector with power

applied, an electrical arc may occur. An electrical arc can cause

personal injury or property damage by:

•sending an erroneous signal to your system’s field devices,

causing unintended machine motion

•causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the

module and its mating connector. Worn contacts may create

electrical resistance.

off and lock out input power. Wait five minutes.

that there is no voltage at the drive’s input power terminals.

e between the +DC and -DC terminals, between the +DC

terminal and the chassis, and between the -DC terminal and the chassis.

The voltage must be zero for all three measurements.

L1L2L3

I

O

Refer to the PowerFlex 700H/S Frame 11 Hardware Service Manual,

publication PFLEX-TG003…, for information about removing the power

structure.

Refer to the PowerFlex 700H/S Frame 11 Hardware Service Manual,

publication PFLEX-TG003…, for information about installing the power

structure.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures9

Step 5:Connecting the

Power Structure to

Components in the Drive

You must connect the power structure to control components on the control

frame. If the drive has DC input, you must also connect the precharge

circuit.

Connections to the 700S Control Frame

When installing a power structure in a PowerFlex 700S drive, you must

make the following connections between the ASIC and Fiber Optic

Interface, Power Supply Voltage Feedback, Common Mode Filter and

Rectifier boards.

Connect this component: termination

point in the Power Structure to …

ASIC Board: H1 (fiber optic connector)

ASIC Board: H2 (fiber optic connector)

ASIC Board: H3 (fiber optic connector)

ASIC Board: H4 (fiber optic connector)

ASIC Board: H5 (fiber optic connector)

ASIC Board: H6 (fiber optic connector)

ASIC Board: H7 (fiber optic connector)

ASIC Board: X10

ASIC Board: X2

Power Supply Voltage Feedback Board: J8

Power Supply Voltage Feedback Board: J5

(fiber optic connector)

Power Supply Voltage Feedback Board: J4

(fiber optic connector)

…this component : termination point on the

Control Frame

Fiber Optic Interface Board: J8 (fiber optic connector)

Fiber Optic Interface Board: J9 (fiber optic connector)

Fiber Optic Interface Board: J10 (fiber optic connector)

Fiber Optic Interface Board: J11 (fiber optic connector)

Fiber Optic Interface Board: J12 (fiber optic connector)

Fiber Optic Interface Board: J14 (fiber optic connector)

Fiber Optic Interface Board: J13 (fiber optic connector)

Insulate and do not connect

Rectifier Board: X13 (AC input drives only)

Common Mode Filter Board: J5

Fiber Optic Interface Board: J6

Fiber Optic Interface Board: J7

Figure 4 Connections for 700S Drives with Phase II Control

Make and verify these connections

To X13 Connector for Rectifier Board (AC Input Drives Only)

X2

ASIC Board

H1 (Gate Enable)

RJ45

Connector

Embedded

P2

P1

EtherNet I/P

Option Board

TX

RX

P1

H2 (U Gate)

H3 (V Gate)

H4 (W Gate)

H5 (ADconv)

H6 (Vbus Tx)

RS232

P3

P7

P9

H7 (Vbus Rx)

SynchLink

Option Board

CompactFlash

Memory

Compact I/O

80

Comm

Input

P1

Fiber Optic Cables

X10

P2

P2

P3

Logix

Expansion

Board

120

P1

P10

J8J9J10J11J12J14J13

+24 V Iso

J1

40

P11

P1

J2

Common Mode Filter Board

Inside Power Structure

30

P2

J5

2

J1

J5

2

J8

+24V

NetLinx

Daughtercard

Feedback

Inputs

34

P2

P1

Feedback

Option

Board

Fiber Optic

Interface

Board

+12 V

-12 V

+5V

J6 Tx

J7 Rx

80W

Power

Supply

J2

DC-

DC+

J1

-U

-V

-W

8

Fiber

9

9

9

8

J5 Rx

J4 Tx

P3

34

P12

Main

Control

Board

P6

Power Supply

Voltage

Feedback

J3

10

J17

2

J16

2

DriveLogix

Battery

J18

J15

2

External

24V DC

1 = 24V

3 = Common

(75W min)

X4

J4

X2

20-VB00601

Second Encoder

P3

or

Safe Off Option Board

16

P13

P4

TB1

P5

TB2

P21

DPI

Interface

X1

Board

X3

20

J2

DPI

Bezel

J3

J1

HIM

DOOR

EXAMPLE:

20-HIM-A3

2

PWR

STS

PORT

MOD

NET A

NET B

700S Control Assembly (Phase II)

M6

Control

Pan Fan

M

DPI

Comm

Option

DPI Assembly

HIM

EXTERNAL DPI

10PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Figure 5 Termination Points on the ASIC Board

Fiber Optic connections to the

Fiber Optic Interface board

X6

X9X15

H1H2H3H4H5H6H7

Connect to Pre-charge

circuitry on DC input drives

X2

X1

Connects to X13

connector for the Rectifier

boards on the center and

right side power stacks on

AC input drives

Connects to fan on

ASIC assembly cover

H8H9H10H11H12H13

X3X4X5

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures11

Figure 6 Termination Points on 700S Boards

Fiber Optic Interface Board

J8

J9

J10

J11

J12

J14

J13

J6

J7

J5

Power Supply Voltage Feedback Board

J4J5

J8

Common Mode Filter Board

J1

J5

12PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Connections to the 700H Control Frame

When installing a power structure in a PowerFlex 700H drive, you must

make eight connections between the ASIC and Fiber Optic Adapter and

Rectifier boards.

Connect this component: termination point in …this component : termination point on the

the Power Structure to …Control Frame

ASIC Board: H1 (fiber optic connector)Fiber Optic Adapter Board: H1

(fiber optic connector)

ASIC Board: H2 (fiber optic connector)Fiber Optic Adapter Board: H2

(fiber optic connector)

ASIC Board: H3 (fiber optic connector)Fiber Optic Adapter Board: H3

(fiber optic connector)

ASIC Board: H4 (fiber optic connector)Fiber Optic Adapter Board: H4

(fiber optic connector)

ASIC Board: H5 (fiber optic connector)Fiber Optic Adapter Board: H5

(fiber optic connector)

ASIC Board: H6 (fiber optic connector)Fiber Optic Adapter Board: H6

(fiber optic connector)

ASIC Board: H7 (fiber optic connector)Fiber Optic Adapter Board: H7

(fiber optic connector)

ASIC Board: X10Fiber Optic Adapter Board: X2

ASIC Board: X2Rectifier Board: X13

Figure 7 Connections Between the Power Structure and Control Frame (700H Drives)

Make and verify these connections

X10

H1

H2

H3

H4

H5

H6

H7

To X13 Connector for Rectifier Board (AC Input Drives Only)

X2

ASIC

Board

Fiber Optic Cables

X2H1H2H3H4H5H6H7

Inside Power Structure

X3

+24V1

Common2

Fiber Optic Adapter Board

X1

37

X1

X2

X7

(RS-232

Programming

Port)

700H Control Board

X2

(Slot A)

20C-DA1-A

(24V dc Digital Input

w/ Analog I/O)

or

20C-DA1-B

(115V ac Digital Input

w/ Analog I/O)

10

Analog

I/O

8 / 10

Digital

Inputs

X3

(Slot B)

X4

(Slot C)

X5

(Slot D)

X6

(Slot E)

X1

20C-DPI1

(DPI Communications

Option)

DPI

Interface

X1J2

X4

HIM

Bezel

J3

J1

HIM

X3

20

20C-DO1

(Digital Output

Option)

PWR

STS

PORT

MOD

NET A

NET B

DPI Assembly

Option

Board

Option

Board

DPI

COMM

(Option)

HIM

X3

33

DigitalDigital

OutputsOutputs

X2

700H Control Assembly

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures13

Figure 8 Termination Points on Fiber Optic Adapter Board (700H Drives)

Back View

H7

H6

H5

H4

H3

H2

H1

X2

14PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Pre-Charge Connections on Drives with DC Input

You must connect the ASIC board connectors X9 and X15 to the X50

terminal block for the pre-charge circuit. The X50 terminal block is located

on the Control Frame. Refer to the Installation Instructions - PowerFlex

700S and 700H High Power Drives, publication PFLEX-IN006…, for

information regarding the pre-charge circuit.

X50 Terminal Block Connections

ASIC Board

ConnectorTerminal

X925

26

X1521

23

toX50 TerminalPre-Charge Circuit Connection Description

. . . 1Pre-charge Complete Signal (+24V DC)

. . . 2Pre-charge Complete Signal (Common)

. . . 3Charge Relay Contact

. . . 4Charge Relay Contact

Figure 9 Sample Pre-charge Wiring Diagram

Customer Connections - External precharge

circuitry is shown as dashed lines.

M

DC+

Terminal BlockDrive Connections

X50

X9

1

M

2

26

21

23

X15

CR1

Pilot Relay

25

ASIC Board

Precharge

Complete

F1R1CR2

DC Source

3

4

Charge

Relay*

M

DC-

CR1

M

Main DC Contactor

F2R2CR2

*Refer to the “ASIC Board

Charge Relay Contact

Ratings” table below.

Important: For DC Input Only.

Do Not Install on AC Input Drives

M

CR2

Precharge

ASIC Board Charge Relay Contact Ratings

Load

Rated load

Rated carry current

Max. switching voltage

Max. switching current

Max. switching power

Failure rate (reference value)

Resistance load (cos φ = 1)

8 A at 250 VAC: 5 A at 30 VDC

8 A

250 VAC; 30 VDC, (400 VAC)

AC 8 A; DC 5 A

2,000 VA; 150 W

5 VDC 10 mA (for gold plating 0.35 µ min.)

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures15

All frame 11 replacement power structures are shipped from the factory

Step 6:Installing the

Product Identification Label

without a product identification label on the drive. If you are installing the

power structure in a 700S drive, you should label it with the accompanying

on New Power Structure

PowerFlex 700S label. If you are installing the power structure in a 700H

drive, you should label it with the accompanying PowerFlex 700H label.

!

D

A

N

G

E

R

OR

Step 7:Starting the Drive

l the protective covers on the drive. Refer to publication

PFLEX-IN006…, Installation Instructions - PowerFlex 700S and 700H

High Power Drives, for assistance in installing these covers.

up the drive. Refer to the Start Up procedures in the appropriate

publication:

–User Manual - PowerFlex 700S Drives with Phase II Control,

20D-UM006….

–Programming Manual - PowerFlex 700H Drives, 20C-PM001….

Reference Materials

Allen-Bradley publications are available on the internet at

/literature.

The following manuals are recommended for general drive information:

Title

Wiring and Grounding Guidelines for Pulse Width Modulated Drives

Industrial Automation Wiring and Grounding Guidelines

Preventive Maintenance of Industrial Control and Drive System Equipment

Safety Guidelines for the Application, Installation and Maintenance of Solid

State Control

A Global Reference Guide for Reading Schematic Diagrams

Guarding Against Electrostatic Damage

Publication

DRIVES-IN001…

1770-4.1

DRIVES-TD001…

SGI-1.1

0100-2.10

8000-4.5.2

The following manuals are recommended for detailed PowerFlex 700H and

700S information:

Title

Reference Manual - PowerFlex 700S Drives with Phase II Control

User Manual - PowerFlex 700S Drives with Phase II Control

Programming Manual - PowerFlex 700H Drives

Installation Instructions - PowerFlex 700S and 700H High Power Drives

Hardware Service Manual - PowerFlex 700S and 700H Frame 11 Drives

Publication

PFLEX-RM003…

20D-UM006…

20C-PM001…

PFLEX-IN006…

PFLEX-TG003…

For Allen-Bradley Drives Technical Support:

Title

Allen-Bradley Drives Technical Support

/support/abdrives

Power, Control and Information Solutions Headquarters

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444

Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640

Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Publication PFLEX-IN011C-EN-P - August 2008

Supersedes PFLEX-IN011B-EN-P - March 2006

16 360399-P03

Copyright © 2008 Rockwell Automation. All rights reserved. Printed in the U.S.A.

2024年9月24日发(作者:柴湛芳)

Introduction

What You Need to Do

Installation Instructions

PowerFlex

®

700S and 700H Frame 11

Replacement Power Structures

Use this document to install a replacement power structure on a PowerFlex

700S or 700H frame 11 drive. This document covers the following

replacement power structures:

Spare Module Catalog PowerFlex 700HPowerFlex 700HPowerFlex 700SPowerFlex 700S

StringAC InputDC InputAC InputDC Input

SK-H1-PWRMOD-E46020CE46020CK46020DE46020DK460

20CF46020CM46020DF46020DM460

SK-H1-PWRMOD-E50220CE50220CK50220DE50220DK502

20CF50220CM50220DF50220DM502

SK-H1-PWRMOD-E59020CE59020CK59020DE59020DK590

20CF59020CM59020DF59020DM590

SK-H1-PWRMOD-D59020CC59020CH59020DC59020DH590

20CD59020CJ59020DD59020DJ590

SK-H1-PWRMOD-D65020CC65020CH65020DC65020DH650

20CD65020CJ65020DD65020DJ650

SK-H1-PWRMOD-D73020CC73020CH73020DC73020DH730

20CD73020CJ73020DD73020DJ730

❐ Step 1: Configure new power structure

❐ Step 2: Remove power from existing drive

❐ Step 3: Remove old power structure

❐ Step 4: Install new power structure

❐ Step 5: Connect new power structure to components in drive

❐ Step 6: Install product identification label on new power structure

❐ Step 7: Start drive

2PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Step 1:Configuring the

New Power Structure

Before configuring the power structure you must remove the protective

covers from the drive. Refer to publication PFLEX-IN006… , Installation

Instructions - PowerFlex 700S and 700H High Power Drives, for assistance

in removing these covers.

Configuring a DC Input Drive

Power structures are shipped from the factory pre-configured for DC input

operation.

Connecting an AC Input Drive

Power structures are shipped from the factory pre-configured for DC input

operation. When installing a replacement power structure on a drive with

AC input, you must remove the X2 plug from it’s protective sleeve and plug

the cable into the ASIC and Rectifier board(s).

Task

A

B

C

D

E

F

Description

Remove the cover from the ASIC board assembly.

Disconnect the ASIC fan from the assembly by unplugging the cable from X1 on the ASIC

board (see Figure 1on page3

for location).

Remove the cover from the connector on the loose cable (bundled with the flat gate driver

board cables) and connect the cable to the X2 connector on the ASIC board (see Figure

1on page3 for location).

Connect the other end of the cable connected to X2 on the ASIC board to the X13

connector for the Rectifier board(s) on the V Phase and W Phase (if present) power stack

(see Figure 2on page3

for location).

Connect the fan cable to the X1 connector on the ASIC board.

Install the cover on the ASIC board assembly.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures3

Figure 1 ASIC Board Connections

X6

X9X15

H1H2H3H4H5H6H7

Connect cable to

X2 connector

X2

X1

X1 connector

H8H9H10H11H12H13

X3X4X5

Figure 2 Rectifier Board Connectors

Cable connected to

X2 on ASIC board

X13

connectors

for Rectifier

boards

4PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Configuring the EMC Filter

Frame 11 size drives are equipped with common mode capacitors. To guard

against drive damage, these capacitors should be disconnected depending

upon the type of ground system on which the drive is installed.

Installation on an Ungrounded Distribution System or High Resistive Ground

If you are installing a 400/480V AC input drive on an ungrounded

distribution system or high resistive ground, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Should insulate terminal X4 on the Rectifier circuit board- refer to

Insulate Terminal X4 on the Rectifier Circuit Boardon page7.

If you are installing a 600/690V AC input drive on an ungrounded

distribution system or high resistive ground, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Must insulate terminal X4 on the Rectifier circuit board- refer to Insulate

Terminal X4 on the Rectifier Circuit Boardon page7.

Installation on a Grounded B Phase Delta System

If you are installing a drive on a grounded B phase Delta system, you:

•Must move the common mode jumper to the disconnected position -

refer to Move the Common Mode Jumper to the Disconnected

Positionon page6.

•Must insulate terminal X4 on the Rectifier circuit board- refer to Insulate

Terminal X4 on the Rectifier Circuit Boardon page7.

Note:Refer to Wiring and Grounding Guidelines for Pulse Width

Modulated (PWM) AC Drives - Installation Instructions,

publication DRIVES-IN001…, for additional information on an

ungrounded distribution system or high resistive ground

installation.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures5

The jumper is located on the Rectifying Module(s). For drives with one

Rectifying Module, it is located on the upper-right side of the middle power

stack (V Phase). For drives with two Rectifying Modules, they are located

on the upper-right side of the middle (V Phase) and right-side (W Phase)

power stacks.

Voltage Class

400/480V AC

Amps

590

650

730

460

502

590

Number of Rectifying Modules

2

2

2

1

1

2

600/690V AC

Figure 3 Common Mode Jumper and Rectifier Circuit Board Location

Common

Mode jumper

There is one jumper located on each Rectifying

Module. The Rectifying Modules are located on

the upper-right side of the center and right side

power stack of the drive’s power structure.

Front View

of Assembly

Rectifier Circuit Board

6PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Move the Common Mode Jumper to the Disconnected Position

the lettered steps below to move the common mode jumper to the

disconnected position (refer to Figure 3on page5 for jumper location).

Task

A

B

C

D

Description

Loosen the upper screw.

Remove the lower screw.

Move the jumper to the horizontal position.

Install and tighten the screws.

A

Front View of

Power Structure

D

C

B

Rectifying Circuit Board

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures7

Insulate Terminal X4 on the Rectifier Circuit Board

the lettered steps below to insulate terminal X4 on the Rectifier

circuit board (refer to Figure 3on page5 for jumper location).

Task

A

B

Description

Remove the screw from the X4 connection on the Rectifier circuit board.

Insulate the top and bottom of the X4 connection on the Rectifier circuit board.

Important:Do not install the screw and washer that was removed from this

connection.

A

Side View of Power Structure

B

X4

X1

X41

X4

X1

X41

Rectifier Circuit Board

8PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Step 2:Removing Power

From the Existing Drive

Step 3:Removing the Old

Power Structure

Step 4:Installing the New

Power Structure

!

ATTENTION: To avoid an electric shock hazard, verify that

the voltage on the bus capacitors has discharged before servicing

the drive. Check the DC bus voltage at the Power Terminal

Block by measuring between the +DC and -DC terminals,

between the +DC terminal and the chassis, and between the -DC

terminal and the chassis. The voltage must be zero for all three

measurements.

Remove power before making or breaking cable connections.

When you remove or insert a cable connector with power

applied, an electrical arc may occur. An electrical arc can cause

personal injury or property damage by:

•sending an erroneous signal to your system’s field devices,

causing unintended machine motion

•causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the

module and its mating connector. Worn contacts may create

electrical resistance.

off and lock out input power. Wait five minutes.

that there is no voltage at the drive’s input power terminals.

e between the +DC and -DC terminals, between the +DC

terminal and the chassis, and between the -DC terminal and the chassis.

The voltage must be zero for all three measurements.

L1L2L3

I

O

Refer to the PowerFlex 700H/S Frame 11 Hardware Service Manual,

publication PFLEX-TG003…, for information about removing the power

structure.

Refer to the PowerFlex 700H/S Frame 11 Hardware Service Manual,

publication PFLEX-TG003…, for information about installing the power

structure.

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures9

Step 5:Connecting the

Power Structure to

Components in the Drive

You must connect the power structure to control components on the control

frame. If the drive has DC input, you must also connect the precharge

circuit.

Connections to the 700S Control Frame

When installing a power structure in a PowerFlex 700S drive, you must

make the following connections between the ASIC and Fiber Optic

Interface, Power Supply Voltage Feedback, Common Mode Filter and

Rectifier boards.

Connect this component: termination

point in the Power Structure to …

ASIC Board: H1 (fiber optic connector)

ASIC Board: H2 (fiber optic connector)

ASIC Board: H3 (fiber optic connector)

ASIC Board: H4 (fiber optic connector)

ASIC Board: H5 (fiber optic connector)

ASIC Board: H6 (fiber optic connector)

ASIC Board: H7 (fiber optic connector)

ASIC Board: X10

ASIC Board: X2

Power Supply Voltage Feedback Board: J8

Power Supply Voltage Feedback Board: J5

(fiber optic connector)

Power Supply Voltage Feedback Board: J4

(fiber optic connector)

…this component : termination point on the

Control Frame

Fiber Optic Interface Board: J8 (fiber optic connector)

Fiber Optic Interface Board: J9 (fiber optic connector)

Fiber Optic Interface Board: J10 (fiber optic connector)

Fiber Optic Interface Board: J11 (fiber optic connector)

Fiber Optic Interface Board: J12 (fiber optic connector)

Fiber Optic Interface Board: J14 (fiber optic connector)

Fiber Optic Interface Board: J13 (fiber optic connector)

Insulate and do not connect

Rectifier Board: X13 (AC input drives only)

Common Mode Filter Board: J5

Fiber Optic Interface Board: J6

Fiber Optic Interface Board: J7

Figure 4 Connections for 700S Drives with Phase II Control

Make and verify these connections

To X13 Connector for Rectifier Board (AC Input Drives Only)

X2

ASIC Board

H1 (Gate Enable)

RJ45

Connector

Embedded

P2

P1

EtherNet I/P

Option Board

TX

RX

P1

H2 (U Gate)

H3 (V Gate)

H4 (W Gate)

H5 (ADconv)

H6 (Vbus Tx)

RS232

P3

P7

P9

H7 (Vbus Rx)

SynchLink

Option Board

CompactFlash

Memory

Compact I/O

80

Comm

Input

P1

Fiber Optic Cables

X10

P2

P2

P3

Logix

Expansion

Board

120

P1

P10

J8J9J10J11J12J14J13

+24 V Iso

J1

40

P11

P1

J2

Common Mode Filter Board

Inside Power Structure

30

P2

J5

2

J1

J5

2

J8

+24V

NetLinx

Daughtercard

Feedback

Inputs

34

P2

P1

Feedback

Option

Board

Fiber Optic

Interface

Board

+12 V

-12 V

+5V

J6 Tx

J7 Rx

80W

Power

Supply

J2

DC-

DC+

J1

-U

-V

-W

8

Fiber

9

9

9

8

J5 Rx

J4 Tx

P3

34

P12

Main

Control

Board

P6

Power Supply

Voltage

Feedback

J3

10

J17

2

J16

2

DriveLogix

Battery

J18

J15

2

External

24V DC

1 = 24V

3 = Common

(75W min)

X4

J4

X2

20-VB00601

Second Encoder

P3

or

Safe Off Option Board

16

P13

P4

TB1

P5

TB2

P21

DPI

Interface

X1

Board

X3

20

J2

DPI

Bezel

J3

J1

HIM

DOOR

EXAMPLE:

20-HIM-A3

2

PWR

STS

PORT

MOD

NET A

NET B

700S Control Assembly (Phase II)

M6

Control

Pan Fan

M

DPI

Comm

Option

DPI Assembly

HIM

EXTERNAL DPI

10PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Figure 5 Termination Points on the ASIC Board

Fiber Optic connections to the

Fiber Optic Interface board

X6

X9X15

H1H2H3H4H5H6H7

Connect to Pre-charge

circuitry on DC input drives

X2

X1

Connects to X13

connector for the Rectifier

boards on the center and

right side power stacks on

AC input drives

Connects to fan on

ASIC assembly cover

H8H9H10H11H12H13

X3X4X5

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures11

Figure 6 Termination Points on 700S Boards

Fiber Optic Interface Board

J8

J9

J10

J11

J12

J14

J13

J6

J7

J5

Power Supply Voltage Feedback Board

J4J5

J8

Common Mode Filter Board

J1

J5

12PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Connections to the 700H Control Frame

When installing a power structure in a PowerFlex 700H drive, you must

make eight connections between the ASIC and Fiber Optic Adapter and

Rectifier boards.

Connect this component: termination point in …this component : termination point on the

the Power Structure to …Control Frame

ASIC Board: H1 (fiber optic connector)Fiber Optic Adapter Board: H1

(fiber optic connector)

ASIC Board: H2 (fiber optic connector)Fiber Optic Adapter Board: H2

(fiber optic connector)

ASIC Board: H3 (fiber optic connector)Fiber Optic Adapter Board: H3

(fiber optic connector)

ASIC Board: H4 (fiber optic connector)Fiber Optic Adapter Board: H4

(fiber optic connector)

ASIC Board: H5 (fiber optic connector)Fiber Optic Adapter Board: H5

(fiber optic connector)

ASIC Board: H6 (fiber optic connector)Fiber Optic Adapter Board: H6

(fiber optic connector)

ASIC Board: H7 (fiber optic connector)Fiber Optic Adapter Board: H7

(fiber optic connector)

ASIC Board: X10Fiber Optic Adapter Board: X2

ASIC Board: X2Rectifier Board: X13

Figure 7 Connections Between the Power Structure and Control Frame (700H Drives)

Make and verify these connections

X10

H1

H2

H3

H4

H5

H6

H7

To X13 Connector for Rectifier Board (AC Input Drives Only)

X2

ASIC

Board

Fiber Optic Cables

X2H1H2H3H4H5H6H7

Inside Power Structure

X3

+24V1

Common2

Fiber Optic Adapter Board

X1

37

X1

X2

X7

(RS-232

Programming

Port)

700H Control Board

X2

(Slot A)

20C-DA1-A

(24V dc Digital Input

w/ Analog I/O)

or

20C-DA1-B

(115V ac Digital Input

w/ Analog I/O)

10

Analog

I/O

8 / 10

Digital

Inputs

X3

(Slot B)

X4

(Slot C)

X5

(Slot D)

X6

(Slot E)

X1

20C-DPI1

(DPI Communications

Option)

DPI

Interface

X1J2

X4

HIM

Bezel

J3

J1

HIM

X3

20

20C-DO1

(Digital Output

Option)

PWR

STS

PORT

MOD

NET A

NET B

DPI Assembly

Option

Board

Option

Board

DPI

COMM

(Option)

HIM

X3

33

DigitalDigital

OutputsOutputs

X2

700H Control Assembly

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures13

Figure 8 Termination Points on Fiber Optic Adapter Board (700H Drives)

Back View

H7

H6

H5

H4

H3

H2

H1

X2

14PowerFlex® 700S and 700H Frame 11 Replacement Power Structures

Pre-Charge Connections on Drives with DC Input

You must connect the ASIC board connectors X9 and X15 to the X50

terminal block for the pre-charge circuit. The X50 terminal block is located

on the Control Frame. Refer to the Installation Instructions - PowerFlex

700S and 700H High Power Drives, publication PFLEX-IN006…, for

information regarding the pre-charge circuit.

X50 Terminal Block Connections

ASIC Board

ConnectorTerminal

X925

26

X1521

23

toX50 TerminalPre-Charge Circuit Connection Description

. . . 1Pre-charge Complete Signal (+24V DC)

. . . 2Pre-charge Complete Signal (Common)

. . . 3Charge Relay Contact

. . . 4Charge Relay Contact

Figure 9 Sample Pre-charge Wiring Diagram

Customer Connections - External precharge

circuitry is shown as dashed lines.

M

DC+

Terminal BlockDrive Connections

X50

X9

1

M

2

26

21

23

X15

CR1

Pilot Relay

25

ASIC Board

Precharge

Complete

F1R1CR2

DC Source

3

4

Charge

Relay*

M

DC-

CR1

M

Main DC Contactor

F2R2CR2

*Refer to the “ASIC Board

Charge Relay Contact

Ratings” table below.

Important: For DC Input Only.

Do Not Install on AC Input Drives

M

CR2

Precharge

ASIC Board Charge Relay Contact Ratings

Load

Rated load

Rated carry current

Max. switching voltage

Max. switching current

Max. switching power

Failure rate (reference value)

Resistance load (cos φ = 1)

8 A at 250 VAC: 5 A at 30 VDC

8 A

250 VAC; 30 VDC, (400 VAC)

AC 8 A; DC 5 A

2,000 VA; 150 W

5 VDC 10 mA (for gold plating 0.35 µ min.)

PowerFlex® 700S and 700H Frame 11 Replacement Power Structures15

All frame 11 replacement power structures are shipped from the factory

Step 6:Installing the

Product Identification Label

without a product identification label on the drive. If you are installing the

power structure in a 700S drive, you should label it with the accompanying

on New Power Structure

PowerFlex 700S label. If you are installing the power structure in a 700H

drive, you should label it with the accompanying PowerFlex 700H label.

!

D

A

N

G

E

R

OR

Step 7:Starting the Drive

l the protective covers on the drive. Refer to publication

PFLEX-IN006…, Installation Instructions - PowerFlex 700S and 700H

High Power Drives, for assistance in installing these covers.

up the drive. Refer to the Start Up procedures in the appropriate

publication:

–User Manual - PowerFlex 700S Drives with Phase II Control,

20D-UM006….

–Programming Manual - PowerFlex 700H Drives, 20C-PM001….

Reference Materials

Allen-Bradley publications are available on the internet at

/literature.

The following manuals are recommended for general drive information:

Title

Wiring and Grounding Guidelines for Pulse Width Modulated Drives

Industrial Automation Wiring and Grounding Guidelines

Preventive Maintenance of Industrial Control and Drive System Equipment

Safety Guidelines for the Application, Installation and Maintenance of Solid

State Control

A Global Reference Guide for Reading Schematic Diagrams

Guarding Against Electrostatic Damage

Publication

DRIVES-IN001…

1770-4.1

DRIVES-TD001…

SGI-1.1

0100-2.10

8000-4.5.2

The following manuals are recommended for detailed PowerFlex 700H and

700S information:

Title

Reference Manual - PowerFlex 700S Drives with Phase II Control

User Manual - PowerFlex 700S Drives with Phase II Control

Programming Manual - PowerFlex 700H Drives

Installation Instructions - PowerFlex 700S and 700H High Power Drives

Hardware Service Manual - PowerFlex 700S and 700H Frame 11 Drives

Publication

PFLEX-RM003…

20D-UM006…

20C-PM001…

PFLEX-IN006…

PFLEX-TG003…

For Allen-Bradley Drives Technical Support:

Title

Allen-Bradley Drives Technical Support

/support/abdrives

Power, Control and Information Solutions Headquarters

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444

Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640

Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Publication PFLEX-IN011C-EN-P - August 2008

Supersedes PFLEX-IN011B-EN-P - March 2006

16 360399-P03

Copyright © 2008 Rockwell Automation. All rights reserved. Printed in the U.S.A.

发布评论

评论列表 (0)

  1. 暂无评论