df-60334:A1 • A1-100

MS-9600LS(E)/MS-9600UDLS(E)

Intelligent Addressable FACP

with Optional 2nd Loop

Addressable

General

Fire•Lite’s MS-9600LS(E) and MS-9600UDLS(E) are compact,

cost effective, intelligent addressable FACPs (Fire Alarm Con-

trol Panels) with an extensive list of powerful features. The

combination of Fire•Lite’s newer series devices and legacy

300 Series devices, along with the MS-9600LS(E) or

MS-9600UDLSE FACP, offer the latest in fire protection tech-

nology. LiteSpeed™ is a patented technology that polls 10

devices at a time looking for new or different information.

When new information is found at a specific address, the sys-

tem polls that device several times for any new data. This

improvement allows a fully loaded panel with up to 636

devices to report an incident and activate the notification cir-

cuits in under 10 seconds. With this new polling scheme,

devices can be wired on standard twisted, unshielded wire up

to a distance of 10,000 feet per loop. Each Signaling Line Cir-

cuit (SLC) loop supports up to 159 addressable detectors

including photoelectric, photoelectric with heat, beam, ioniza-

tion, photoelectric duct, fixed heat, fixed heat with rate-of-rise,

and fixed high-heat detectors. It also supports up to 159

addressable modules including monitor (two-wire detector,

normally open devices), dual-monitor functions (two monitor

circuits from one module, two addresses used), multimonitor

(multiple monitor circuits from one module, multiple addresses

used), control (for Notification Appliance Circuits), and relay

(two Form-C) modules.

The FLPS-7 power supply is a separate board while all other

electronics are contained on a single main circuit board. Both

boards are mounted to a quick-removable chassis and housed

in a metal cabinet. The backbox can be installed allowing field

wiring to be pulled. When construction is completed, the chas-

sis with the electronics can be quickly installed with two bolts.

The MS-9600UDLS(E) includes a factory-installed DACT-UD2

Digital Alarm Communicator Transmitter. The DACT transmits

system status (alarm, troubles, AC loss, etc.) to a Central Sta-

tion via internet (optional IPDACT installed) or the public

switched telephone network.

Optional modules, which plug into the main circuit board, are

available for special functions. Available accessories include

LED, graphic and LCD annunciators, reverse polarity/city box

transmitter, digital alarm communicator/transmitter, SLC

expansion module, local and remote upload/download soft-

ware and remote power expansion.

FM APPROVED to UL ANSI 864.

MEMBRANE SWITCH CONTROLS

ACKNOWLEDGE/STEP

ALARM SILENCE

DRILL

SYSTEM RESET (lamp test)

12-key pad with full alphabet

4 cursor keys

ENTER

Special Features

Easy mount chassis.

7 amp switching power supply.

Large enclosure allows 18 amp-hour batteries

DACT-UD2 plug-in communicator standard with

MS-9600UDLS/E.

Optional IPDACT Internet Protocol Digital Alarm

Communicator/Transmitter

Four Style Y (Class B) or two Style Z (Class A)

NAC circuits.

Selectable strobe synchronization per NAC for

System Sensor, Wheelock, and Gentex devices.

Automated control of ACC-25/50(ZS/T) audio speaker cir-

cuits

ANN-BUS for connection to following optional modules

Note: cannot be used if ACS annunciators are used.

•ANN-80(-W) Remote LCD Annunciator

•ANN-I/O LED Driver Module

•ANN-S/PG Serial/Parallel Printer Module

•ANN-RLY Relay Module

•ANN-LED Annunciator Module

•ANN-RLED Annunciator Module (alarms only)

Controls And Indicators

LED INDICATORS

AC POWER (green)

FIRE ALARM (red)

SUPERVISORY (yellow)

ALARM SILENCED (yellow)

SYSTEM TROUBLE (yellow)

MAINTENANCE/PRESIGNAL (yellow)

DISABLED (yellow)

BATTERY FAULT (yellow)

GROUND FAULT (yellow)

df-60334:A1 • 03/26/2009 — Page 1 of 6

5

2

4

1

2

c

o

v

.

j

p

g

Standard Features

SLC LOOP

•SLC can be configured for NFPA Style 4, 6, or 7 operation.

•SLC supports up to 318 addressable devices per loop (159

detectors and 159 monitor, control, or relay modules).

•SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG

(3.1 mm²) using twisted, unshielded wire (see Wire Table on

page 5).

•Optional 4XTMF module (conventional reverse polarity/city

box transmitter).

Field-programming Features

Off-line Programming: Create the entire program in your

office using a Windows®-based software package (order pro-

gramming kit PK-CD, containing PS-TOOLS, separately).

Upload/download system programming locally to the

MS-9600LS/E in less than one minute.

Autoprogramming: Command the MS-9600LS(E) to program

itself (takes less than 30 seconds). In the Auto-Program mode,

the MS-9600LS(E) scans for all possible devices at all

addresses, stores the device types, and addresses found, and

then loads default values for all options (General Alarm). It

also checks for two or more devices set to the same address.

Online Editing: While still providing fire protection, the

MS-9600LS/E may be programmed from the front panel. Sim-

ple menu trees displayed on the LCD allow the trained user to

perform all functions without referring back to the programming

manual.

English Label Library: Quickly select labels from a standard

library of more than 50 adjectives/nouns, such as “FLR 3

HALLWAY,” or enter custom labels letter-by-letter. Use recall

function to repeat previously used label.

Program Check: Automatically catch common errors, such as

control modules not linked to any zone or input point.

NOTIFICATION APPLIANCE CIRCUITS (NACS):

•Four onboard NACs with additional NAC capability using

output control modules (CMF-300 or CMF-300-6). The four

Class B NACs can be converted to two Class A NACs with

the NACKEY (included).

•Silence Inhibit and Auto Silence timer options.

•Continuous, March Time, Temporal or California code for

main circuit board NACs with two-stage capability.

•Selectable strobe synchronization per NAC.

•3.0 amps maximum per each NAC circuit

Note: Maximum 24 VDC system power output is shared

among all NAC circuits and 24 VDC special application aux-

iliary power outputs. Total available output is 7.0 amps.

ADVANCED FIRE TECHNOLOGY:

•Sensitivity testing with printable results, onsite or offsite.

•Automatic drift compensation.

PROGRAMMING AND SOFTWARE:

•Autoprogram (learn mode) reduces installation time.

•Fully programmable from local keypad, local PS/2 keyboard

or PC (using the standard PS-TOOLS Windows® utility).

•Two-level user-programmable passwords.

•Custom English labels (per point) may be manually entered

or selected from an internal library file.

•Three Form-C relay outputs (two programmable).

•99 software zones.

Maintenance Alert

The MS-9600LS(E) continuously monitors each smoke detec-

tor and is capable of reporting maintenance conditions. This

reduces the risk of false alarms due to dust accumulation.

Refer to the control panel installation manual for more informa-

tion.

Automatic Test Operation

The MS-9600LS(E) performs an automatic test of each detec-

tor every two hours. Failure to meet the test limits causes an

AUTO TEST FAIL trouble type. System Reset clears this trou-

ble.

USER INTERFACE:

•Optional plug-in DACT-UD2 communicator (standard with

MS-9600UDLS(E) with USB port for local upload/download.

•Remote Acknowledge, Silence, Reset and Drill via address-

able monitor modules, ACS Series annunciators, LCD-80F

remote annunciator, or ANN-80 Series Annunciators.

•EIA-232 printer/PC interface (variable baud rate) on main

circuit board.

•Integral 80-character LCD display with backlighting.

•Real-time clock/calendar with automatic daylight savings

adjustments.

•History file with 1,000-event capacity.

•EIA-485/ANN-BUS supporting up to 8 ANN Series Annunci-

ators or 32 ACS Series annunciators.

•EIA-485 supporting up to 32 ACS annunciators.

•Maintenance alert warns when smoke detector dust accu-

mulation is excessive.

•Automatic device type-code verification.

•One person audible or silent walk test with walk-test log and

printout.

•Point trouble identification.

•Local piezo sounder.

•Waterflow (nonsilenceable) selection per monitor point.

•System alarm verification selection per detector point.

•PAS (Positive Alarm Sequence) and presignal delay per

point (NFPA 72 compliant).

Page 2 of 6 — df-60334:A1 • 03/26/2009

Terminal Blocks

AC Power – TB1: 120 VAC, 60 Hz, 3.0 amps or 240 VAC, 50

Hz, 1.5 amps. Wire size: minimum 14 AWG (2.00 mm²) with

600 V insulation.

Battery (lead acid only) – TB2: Maximum charging circuit:

******************************.Maximumbattery

charger capacity: 26 AH. Minimum battery 12 AH. MS-

9600LS(E) cabinet holds maximum of two 18 AH batteries. For

26 – 120 AH batteries, use the CHG-120F or CHG-75 Battery

Charger and BB-55F Battery Box.

NOTE: Jumper JP3, on the FACP main circuit board, must be cut

to disable the FACP battery charger when using the CHG-120F or

CHG-75.

Communication Loop – (standard) TB8: 24 VDC nominal,

27.6 VDC maximum. Maximum length: 10,000 ft. (3048 m)

total twisted, unshielded pair length. Maximum loop current:

400 mA (short circuit) or 100 mA (normal). Maximum loop

resistance: 40 ohms. Supervised and power-limited.

Notification Appliance Circuits – TB4: Power-limited cir-

cuitry. Nominal operating voltage: 24 VDC. Current limit: fuse-

less, electronic, power-limited circuitry. Maximum signaling

current per circuit: 3.0 amps. End-of-Line Resistor: 4.7K ohm,

1/2 watt (P/N 71252 UL listed) for NACs. Refer to Fire•Lite

Device Compatibility Document for listed compatible devices.

Programmable and Trouble Output Relays – TB5: Contact

rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC

(resistive). Form-C relays.

Four-Wire Resettable Smoke Detector Power

(24 VDC nominal) – TB3, Terminals 1(+) & 2(–):

Maximum ripple voltage: 10 mV

RMS

. Up to 1.5 amps for pow-

ering four-wire smoke detectors. Power-limited circuit. Refer to

Fire•Lite Device Compatibility Document for listed compatible

devices.

Nonresettable Power #1 (24 VDC Nominal) –TB3, Termi-

nals 3 (+) & 4 (–): Maximum ripple voltage: 10 mV

RMS

. Up to

1.5 amps total DC current available from each output. Power-

limited circuit. TB3, Terminals 5 (+) & 6 (–): non-resettable

power #2.

Nonresettable Special Application Power #2 (24 VDC Nom-

inal) - TB3, Terminals 5 (+) & 6 (-): Maximum ripple voltage:

10mVRMS. Total DC current available from each output is up

to 1.5 amps. Power-limited circuit, nonsupervised.

EIA-485 (ACS/ANN) – TB6: Annunciator connector, program-

mable for type ANN or ACS. Terminal 1 (+) and Terminal 2 (–).

EIA-485 (TERM) – TB7: Terminal mode annunciator connec-

tor, Terminal 1 (Out +), 2 (In +), 3 (Out –), 4 (In –).

EIA-232 – TB8: PC/printer connector, Terminal 1 (Transmit), 2

(Receive), 3 (DTR), 4 (Ground).

BB-26: Battery backbox, holds up to two 25 AH batteries.

CHG-120F: Remote battery charging system for lead-acid bat-

teries with a rating of 25 to 120 AH. CHG-120F or CHG-75

required for charging greater than 25 AH batteries.

CHG-75: Battery charger for lead-acid batteries with a rating

of 25 to 75 AH. CHG-120F or CHG-75 required for charging

greater than 25 AH batteries.

BAT Series: Batteries, see data sheet DF-52397.

PRT/PK-CABLE: Cable printer/personal computer interface

cable.

PRN-6F: UL listed compatible event printer which uses tractor-

fed paper.

Compatible Addressable Devices

All feature a polling LED and rotary switches for addressing.

CP355: Addressable low-profile ionization smoke detector.

SD355: Addressable low-profile photoelectric smoke detector.

SD355T: Addressable low-profile photoelectric smoke detector

with thermal sensor.

H355: Fast-response, low-profile heat detector.

H355R: Fast-response, low-profile heat detector with rate-of-

rise option.

H355HT: Fast-response, low-profile heat detector that acti-

vates at190° F (88°C).

AD355: Low-profile, intelligent, “Adapt” multi-sensor detector;

B350LP base included.

BEAM355: Intelligent beam smoke detector.

BEAM355S: Intelligent beam smoke detector with integral

sensitivity test.

D350PL: Photoelectric low-flow duct smoke detector.

D350RPL: Photoelectric low-flow duct smoke detector with

relay option.

MMF-300: Addressable Monitor Module for one zone of nor-

mally-open dry-contact initiating devices. Mounts in standard

4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-

line resistor. Module may be configured for either a Style B

(Class B) or Style D (Class A) IDC.

MDF-300: Dual Monitor Module. Same as MMF-300 except it

provides two Style B (Class B) only IDCs.

MMF-301: Miniature version of MMF-300. Excludes LED and

Style D option. Connects with wire pigtails. May mount in

device backbox.

MMF-302: Similar to MMF-300, but may monitor up to 20 con-

ventional two-wire detectors. Requires resettable 24 VDC

power. Consult factory for compatible smoke detectors.

CMF-300: Addressable Control Module for one Style Y/Z

(Class B/A) zone of supervised polarized Notification Appli-

ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.

Notification Appliance Circuit option requires external 24 VDC

to power notification appliances.

CRF-300: Addressable relay module containing two isolated

sets of Form-C contacts, which operate as a DPDT switch.

Mounts directly to a 4.0" (10.16 cm.) box, surface mount using

the SMB500.

BG-12LX: Addressable manual pull station with interface mod-

ule mounted inside.

I300: This module isolates the SLC loop from short circuit con-

ditions (required for Style 6 or 7 operation).

SMB500: Used to mount all modules except the MMF-301 and

M301.

df-60334:A1 • 03/26/2009 — Page 3 of 6

Ordering Options

MS-9600LS(E): 318-point addressable Fire Alarm Control

Panel, one SLC loop. Includes 80-character LCD display, sin-

gle printed circuit board, and cabinet.

MS-9600UDLS(E): 318-point addressable Fire Alarm Control

Panel, one SLC loop. Includes DACT-UD2, 80-character LCD

display, single printed circuit board, and cabinet.

DACT-UD2: Optional communicator for remote monitoring

(standard with MS-9600UDLS).

4XTMF: Optional Transmitter Module provides a supervised

output for local energy municipal box transmitter, alarm and

trouble reverse polarity. It includes a disable switch and dis-

able trouble.

IPDACT-2/2UD, IPDACT Internet Monitoring Module:

Mounts in bottom of enclosure with optional mounting kit (P/N:

IPBRKT). Connects to primary and secondary DACT tele-

phone output ports for internet communications over customer

provided ethernet internet connection. Requires compatible

Teldat VisorALARM Central Station Receiver. Can use DHCP

or static IP. (See data sheet DF-60407 or DF-52424 for addi-

tional information.

IPBRKT: Optional mounting bracket kit consisting of screws

and battery shield with standoffs required when mounting the

IPDACT in lower enclosure section of FACP.

IPSPLT: Optional Y-Adaptor which allows connection of both

panel dialer outputs to one cable input to IPDACT (sold sepa-

rately).

ACM-8RF: Optional plug-in relay module provides 8 Form-C

5.0 amp relays.

PK-CD: Contains PS-TOOLS programming software for Win-

dows®-based PC computer (cable not included).

SLC-2LS: Optional expander module, enables second SLC

loop.

DP-9296: Dress panel for MS-9600LS(E) (included with unit).

TR-CE: Optional Trim Ring for semi-flush mounting.

BB-55F: Battery box, required to house two 25 AH batteries

and one CHG-120F battery charger. For batteries greater than

25 AH, consult factory for housing/mounting arrangements.

DACT-UD2

Page 4 of 6 — df-60334:A1 • 03/26/2009

MMF-300-10: Ten-input monitor module. Mount one or two

modules in a BB-2F cabinet (optional). Mount up to six mod-

ules on a CHS-6 chassis in a BB-6F.

MMF-302-6: Six-zone interface module. Mount one or two

modules in a BB-2F cabinet (optional). Mount up to six mod-

ules on a CHS-6 chassis in a BB-6F.

CMF-300-6: Six-circuit supervised control module. Mount one

or two modules in a BB-2F cabinet (optional). Mount up to six

modules on a CHS-6 chassis in a BB-6F.

CRF-300-6: Six Form-C relay control module. Mount one or

two modules in a BB-2F cabinet (optional). Mount up to six

modules on a CHS-6 chassis in a BB-6F.

Compatible Annunciators

ANN-80(-W): Remote LCD annunciator that mimics the infor-

mation displayed on the FACP’s LCD display. Recommended

wire type is unshielded. (Basic model is red; order -W version

for white; see DF-52417).

ANN-LED: Annunciator Module provides three LEDs for each

zone: Alarm, Trouble and Supervisory. Ships with red enclo-

sure (see DF-60241).

ANN-RLED: Provides alarm (red) indicators for up to 30 input

zones or addressable points (see DF-60241).

ANN-RLY: Relay Module, which can be mounted inside the

cabinet, provides 10 programmable Form-C relays (see DF-

52431).

ANN-S/PG: Serial/Parallel Printer Gateway module provides a

connection for a Serial or Parallel printer (see DF-52429).

ANN-I/O: I/O Driver Module provides connections to a user

supplied graphic annunciator (see DF-52430).

ACS-LED Zone Series: LED-type fire annunciators capable of

providing up to 99 software zones of annunciation. Available in

increments of 16 or 32 points to meet a variety of applications.

ACS-LDM Graphic Series: Lamp Driver Module series for

use with custom graphic annunciators.

TERM MODE LCD-80F (Liquid Crystal Display) point

annunciator: 80-character, backlit LCD-type fire annunciators

capable of displaying English-language text. Up to 32 LCD-

80F annunciators may be connected to the EIA-485 terminal

mode serial interface on the MS-9600LS(E) motherboard.

NOTE: For more information on Compatible Annunciators for

use with the MS-9600LS(E), see the following data sheets (docu-

ment numbers) ACM-8RF (DF-51555), ACS/ACM Series (DF-

52378), LDM Series (DF-51384), LCD-80F (DF-52185).

Wiring Requirements

While shielded wire is not required, it is recommended that all

SLC wiring be twisted-pair to minimize the effects of electrical

interference. Refer to the panel manual for wiring details.

df-60334:A1 • 03/26/2009 — Page 5 of 6

SYSTEM SPECIFICATIONS

System Capacity

Intelligent Signalling 1 expandable to 2

159 per loop

Addressable monitor/159 per loop

Programmable 99

8

32

32

Cabinet Specifications

Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x

0.67" (1.70 cm.) deep. Backbox: 19.00" (48.26 cm.) high x

16.65" (42.29 cm.) wide x 5.21" (13.23 cm.) deep. Trim Ring

(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping Specifications

Dimensions: 20.00” (50.80 cm) high, 22.5” (57.15 cm) wide,

8.5” (21.59 cm) deep. Weight: 27.3 lbs (12.38 kg).

Electrical Specifications

•Primary input power:

120 VAC, 50/60 Hz, 3.0 A.

240 VAC, 50 Hz, 1.5 A.

•Battery:************(max).

Maximum battery charger capacity: 26 AH.

Minimum battery: 12 AH.

MS-9600LS cabinet holds maximum of two 18 AH batteries.

•Communication Loop: 24 VDC nominal, supervised and

power-limited.

•Notification Appliance Circuits: terminal block provides con-

nections for four Style Y (Class B) or two Style Z (Class A)

NACs.

Maximum signaling current per circuit: 3.0 A.

End-of-Line Resistor: 4.7 K ohms, ½ watt (P/N 71252 UL

listed) for Style Y (Class B) NAC.

Supervised and power-limited.

Refer to panel documentation and Fire-Lite Device Compat-

ibility Document for listed compatible devices.

•Two Programmable Form-C Relays and One Fixed Trouble

Form-C Relay: Contact rating: 2.0 A @ 30 VDC (resistive)

0.5 A @ 30 VAC (resistive).

•Four-wire Resettable Special Application Power (24 VDC

nominal): Up to 1.5 A for powering four-wire smoke detec-

tors. Power-Limited, nonsupervised.

Refer to Fire-Lite Device Compatibility Document for listed

compatible devices.

•Nonresettable Special Application Power #1 (24VDC nomi-

nal) TB3, Terminals 3 (+) & 4 (-):

Maximum ripple voltage: 10 mV

RMS

Total DC current available from each output is up to 1.5 A.

Power-limited, nonsupervised.

•Nonresettable Special Application Power #2 (24VDC nomi-

nal) TB3, Terminals 5 (+) & 6 (-):

Maximum ripple voltage: 10 mV

RMS

Total DC current available from each output is up to 1.5 A.

Power-limited, nonsupervised.

NOTE: Although each Special Application power output can

deliver 1.5 A individually, the total power output from these circuits

cannot exceed 1.5 A in standby. The total Alarm output for all Spe-

cial Application power and NAC circuits cannot exceed 7 A.

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 –

49°C/32 – 120°F and at a relative humidity 93% ± 2% RH

(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the

useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme tempera-

ture ranges and humidity. Therefore, it is recommended that

this system and its peripherals be installed in an environment

with a normal room temperature of 15 – 27°C/60 – 80°F.

Agency Listings and Approvals

The listings and approvals below apply to the MS-9600LS(E)

and MS-9600UDLS(E) control panels. In some cases, certain

modules may not be listed by certain approval agencies, or list-

ing may be in process. Consult factory for latest listing status.

ULC: S624 (MS-9600LSC only; see DF-60438)

FM APPROVED: to UL ANSI 864

CSFM: 7170-0075:220

MEA: 87-08-E

NFPA Standards

The MS-9600LS(E) and MS-9600UDLS(E) control panels

comply with the following NFPA 72 Fire Alarm Systems

requirements:

–LOCAL (Automatic, Manual, Waterflow and Sprinkler

Supervisory).

–AUXILIARY (Automatic, Manual and Waterflow) (requires

4XTMF).

–REMOTE STATION (Automatic, Manual and Waterflow)

(Requires 4XTMF where DACT-UD2 is not accepted.)

–PROPRIETARY (Automatic, Manual and Waterflow).

–CENTRAL STATION (Automatic, Manual and Waterflow,

and Sprinkler Supervised).

–OT (Other Technologies-PSDN) For use with IPDACT.

LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark

of Honeywell International Inc.

©2009 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

Made in the U.S. A.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.

Page 6 of 6 — df-60334:A1 • 03/26/2009

2024年9月28日发(作者:悉安翔)

df-60334:A1 • A1-100

MS-9600LS(E)/MS-9600UDLS(E)

Intelligent Addressable FACP

with Optional 2nd Loop

Addressable

General

Fire•Lite’s MS-9600LS(E) and MS-9600UDLS(E) are compact,

cost effective, intelligent addressable FACPs (Fire Alarm Con-

trol Panels) with an extensive list of powerful features. The

combination of Fire•Lite’s newer series devices and legacy

300 Series devices, along with the MS-9600LS(E) or

MS-9600UDLSE FACP, offer the latest in fire protection tech-

nology. LiteSpeed™ is a patented technology that polls 10

devices at a time looking for new or different information.

When new information is found at a specific address, the sys-

tem polls that device several times for any new data. This

improvement allows a fully loaded panel with up to 636

devices to report an incident and activate the notification cir-

cuits in under 10 seconds. With this new polling scheme,

devices can be wired on standard twisted, unshielded wire up

to a distance of 10,000 feet per loop. Each Signaling Line Cir-

cuit (SLC) loop supports up to 159 addressable detectors

including photoelectric, photoelectric with heat, beam, ioniza-

tion, photoelectric duct, fixed heat, fixed heat with rate-of-rise,

and fixed high-heat detectors. It also supports up to 159

addressable modules including monitor (two-wire detector,

normally open devices), dual-monitor functions (two monitor

circuits from one module, two addresses used), multimonitor

(multiple monitor circuits from one module, multiple addresses

used), control (for Notification Appliance Circuits), and relay

(two Form-C) modules.

The FLPS-7 power supply is a separate board while all other

electronics are contained on a single main circuit board. Both

boards are mounted to a quick-removable chassis and housed

in a metal cabinet. The backbox can be installed allowing field

wiring to be pulled. When construction is completed, the chas-

sis with the electronics can be quickly installed with two bolts.

The MS-9600UDLS(E) includes a factory-installed DACT-UD2

Digital Alarm Communicator Transmitter. The DACT transmits

system status (alarm, troubles, AC loss, etc.) to a Central Sta-

tion via internet (optional IPDACT installed) or the public

switched telephone network.

Optional modules, which plug into the main circuit board, are

available for special functions. Available accessories include

LED, graphic and LCD annunciators, reverse polarity/city box

transmitter, digital alarm communicator/transmitter, SLC

expansion module, local and remote upload/download soft-

ware and remote power expansion.

FM APPROVED to UL ANSI 864.

MEMBRANE SWITCH CONTROLS

ACKNOWLEDGE/STEP

ALARM SILENCE

DRILL

SYSTEM RESET (lamp test)

12-key pad with full alphabet

4 cursor keys

ENTER

Special Features

Easy mount chassis.

7 amp switching power supply.

Large enclosure allows 18 amp-hour batteries

DACT-UD2 plug-in communicator standard with

MS-9600UDLS/E.

Optional IPDACT Internet Protocol Digital Alarm

Communicator/Transmitter

Four Style Y (Class B) or two Style Z (Class A)

NAC circuits.

Selectable strobe synchronization per NAC for

System Sensor, Wheelock, and Gentex devices.

Automated control of ACC-25/50(ZS/T) audio speaker cir-

cuits

ANN-BUS for connection to following optional modules

Note: cannot be used if ACS annunciators are used.

•ANN-80(-W) Remote LCD Annunciator

•ANN-I/O LED Driver Module

•ANN-S/PG Serial/Parallel Printer Module

•ANN-RLY Relay Module

•ANN-LED Annunciator Module

•ANN-RLED Annunciator Module (alarms only)

Controls And Indicators

LED INDICATORS

AC POWER (green)

FIRE ALARM (red)

SUPERVISORY (yellow)

ALARM SILENCED (yellow)

SYSTEM TROUBLE (yellow)

MAINTENANCE/PRESIGNAL (yellow)

DISABLED (yellow)

BATTERY FAULT (yellow)

GROUND FAULT (yellow)

df-60334:A1 • 03/26/2009 — Page 1 of 6

5

2

4

1

2

c

o

v

.

j

p

g

Standard Features

SLC LOOP

•SLC can be configured for NFPA Style 4, 6, or 7 operation.

•SLC supports up to 318 addressable devices per loop (159

detectors and 159 monitor, control, or relay modules).

•SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG

(3.1 mm²) using twisted, unshielded wire (see Wire Table on

page 5).

•Optional 4XTMF module (conventional reverse polarity/city

box transmitter).

Field-programming Features

Off-line Programming: Create the entire program in your

office using a Windows®-based software package (order pro-

gramming kit PK-CD, containing PS-TOOLS, separately).

Upload/download system programming locally to the

MS-9600LS/E in less than one minute.

Autoprogramming: Command the MS-9600LS(E) to program

itself (takes less than 30 seconds). In the Auto-Program mode,

the MS-9600LS(E) scans for all possible devices at all

addresses, stores the device types, and addresses found, and

then loads default values for all options (General Alarm). It

also checks for two or more devices set to the same address.

Online Editing: While still providing fire protection, the

MS-9600LS/E may be programmed from the front panel. Sim-

ple menu trees displayed on the LCD allow the trained user to

perform all functions without referring back to the programming

manual.

English Label Library: Quickly select labels from a standard

library of more than 50 adjectives/nouns, such as “FLR 3

HALLWAY,” or enter custom labels letter-by-letter. Use recall

function to repeat previously used label.

Program Check: Automatically catch common errors, such as

control modules not linked to any zone or input point.

NOTIFICATION APPLIANCE CIRCUITS (NACS):

•Four onboard NACs with additional NAC capability using

output control modules (CMF-300 or CMF-300-6). The four

Class B NACs can be converted to two Class A NACs with

the NACKEY (included).

•Silence Inhibit and Auto Silence timer options.

•Continuous, March Time, Temporal or California code for

main circuit board NACs with two-stage capability.

•Selectable strobe synchronization per NAC.

•3.0 amps maximum per each NAC circuit

Note: Maximum 24 VDC system power output is shared

among all NAC circuits and 24 VDC special application aux-

iliary power outputs. Total available output is 7.0 amps.

ADVANCED FIRE TECHNOLOGY:

•Sensitivity testing with printable results, onsite or offsite.

•Automatic drift compensation.

PROGRAMMING AND SOFTWARE:

•Autoprogram (learn mode) reduces installation time.

•Fully programmable from local keypad, local PS/2 keyboard

or PC (using the standard PS-TOOLS Windows® utility).

•Two-level user-programmable passwords.

•Custom English labels (per point) may be manually entered

or selected from an internal library file.

•Three Form-C relay outputs (two programmable).

•99 software zones.

Maintenance Alert

The MS-9600LS(E) continuously monitors each smoke detec-

tor and is capable of reporting maintenance conditions. This

reduces the risk of false alarms due to dust accumulation.

Refer to the control panel installation manual for more informa-

tion.

Automatic Test Operation

The MS-9600LS(E) performs an automatic test of each detec-

tor every two hours. Failure to meet the test limits causes an

AUTO TEST FAIL trouble type. System Reset clears this trou-

ble.

USER INTERFACE:

•Optional plug-in DACT-UD2 communicator (standard with

MS-9600UDLS(E) with USB port for local upload/download.

•Remote Acknowledge, Silence, Reset and Drill via address-

able monitor modules, ACS Series annunciators, LCD-80F

remote annunciator, or ANN-80 Series Annunciators.

•EIA-232 printer/PC interface (variable baud rate) on main

circuit board.

•Integral 80-character LCD display with backlighting.

•Real-time clock/calendar with automatic daylight savings

adjustments.

•History file with 1,000-event capacity.

•EIA-485/ANN-BUS supporting up to 8 ANN Series Annunci-

ators or 32 ACS Series annunciators.

•EIA-485 supporting up to 32 ACS annunciators.

•Maintenance alert warns when smoke detector dust accu-

mulation is excessive.

•Automatic device type-code verification.

•One person audible or silent walk test with walk-test log and

printout.

•Point trouble identification.

•Local piezo sounder.

•Waterflow (nonsilenceable) selection per monitor point.

•System alarm verification selection per detector point.

•PAS (Positive Alarm Sequence) and presignal delay per

point (NFPA 72 compliant).

Page 2 of 6 — df-60334:A1 • 03/26/2009

Terminal Blocks

AC Power – TB1: 120 VAC, 60 Hz, 3.0 amps or 240 VAC, 50

Hz, 1.5 amps. Wire size: minimum 14 AWG (2.00 mm²) with

600 V insulation.

Battery (lead acid only) – TB2: Maximum charging circuit:

******************************.Maximumbattery

charger capacity: 26 AH. Minimum battery 12 AH. MS-

9600LS(E) cabinet holds maximum of two 18 AH batteries. For

26 – 120 AH batteries, use the CHG-120F or CHG-75 Battery

Charger and BB-55F Battery Box.

NOTE: Jumper JP3, on the FACP main circuit board, must be cut

to disable the FACP battery charger when using the CHG-120F or

CHG-75.

Communication Loop – (standard) TB8: 24 VDC nominal,

27.6 VDC maximum. Maximum length: 10,000 ft. (3048 m)

total twisted, unshielded pair length. Maximum loop current:

400 mA (short circuit) or 100 mA (normal). Maximum loop

resistance: 40 ohms. Supervised and power-limited.

Notification Appliance Circuits – TB4: Power-limited cir-

cuitry. Nominal operating voltage: 24 VDC. Current limit: fuse-

less, electronic, power-limited circuitry. Maximum signaling

current per circuit: 3.0 amps. End-of-Line Resistor: 4.7K ohm,

1/2 watt (P/N 71252 UL listed) for NACs. Refer to Fire•Lite

Device Compatibility Document for listed compatible devices.

Programmable and Trouble Output Relays – TB5: Contact

rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC

(resistive). Form-C relays.

Four-Wire Resettable Smoke Detector Power

(24 VDC nominal) – TB3, Terminals 1(+) & 2(–):

Maximum ripple voltage: 10 mV

RMS

. Up to 1.5 amps for pow-

ering four-wire smoke detectors. Power-limited circuit. Refer to

Fire•Lite Device Compatibility Document for listed compatible

devices.

Nonresettable Power #1 (24 VDC Nominal) –TB3, Termi-

nals 3 (+) & 4 (–): Maximum ripple voltage: 10 mV

RMS

. Up to

1.5 amps total DC current available from each output. Power-

limited circuit. TB3, Terminals 5 (+) & 6 (–): non-resettable

power #2.

Nonresettable Special Application Power #2 (24 VDC Nom-

inal) - TB3, Terminals 5 (+) & 6 (-): Maximum ripple voltage:

10mVRMS. Total DC current available from each output is up

to 1.5 amps. Power-limited circuit, nonsupervised.

EIA-485 (ACS/ANN) – TB6: Annunciator connector, program-

mable for type ANN or ACS. Terminal 1 (+) and Terminal 2 (–).

EIA-485 (TERM) – TB7: Terminal mode annunciator connec-

tor, Terminal 1 (Out +), 2 (In +), 3 (Out –), 4 (In –).

EIA-232 – TB8: PC/printer connector, Terminal 1 (Transmit), 2

(Receive), 3 (DTR), 4 (Ground).

BB-26: Battery backbox, holds up to two 25 AH batteries.

CHG-120F: Remote battery charging system for lead-acid bat-

teries with a rating of 25 to 120 AH. CHG-120F or CHG-75

required for charging greater than 25 AH batteries.

CHG-75: Battery charger for lead-acid batteries with a rating

of 25 to 75 AH. CHG-120F or CHG-75 required for charging

greater than 25 AH batteries.

BAT Series: Batteries, see data sheet DF-52397.

PRT/PK-CABLE: Cable printer/personal computer interface

cable.

PRN-6F: UL listed compatible event printer which uses tractor-

fed paper.

Compatible Addressable Devices

All feature a polling LED and rotary switches for addressing.

CP355: Addressable low-profile ionization smoke detector.

SD355: Addressable low-profile photoelectric smoke detector.

SD355T: Addressable low-profile photoelectric smoke detector

with thermal sensor.

H355: Fast-response, low-profile heat detector.

H355R: Fast-response, low-profile heat detector with rate-of-

rise option.

H355HT: Fast-response, low-profile heat detector that acti-

vates at190° F (88°C).

AD355: Low-profile, intelligent, “Adapt” multi-sensor detector;

B350LP base included.

BEAM355: Intelligent beam smoke detector.

BEAM355S: Intelligent beam smoke detector with integral

sensitivity test.

D350PL: Photoelectric low-flow duct smoke detector.

D350RPL: Photoelectric low-flow duct smoke detector with

relay option.

MMF-300: Addressable Monitor Module for one zone of nor-

mally-open dry-contact initiating devices. Mounts in standard

4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-

line resistor. Module may be configured for either a Style B

(Class B) or Style D (Class A) IDC.

MDF-300: Dual Monitor Module. Same as MMF-300 except it

provides two Style B (Class B) only IDCs.

MMF-301: Miniature version of MMF-300. Excludes LED and

Style D option. Connects with wire pigtails. May mount in

device backbox.

MMF-302: Similar to MMF-300, but may monitor up to 20 con-

ventional two-wire detectors. Requires resettable 24 VDC

power. Consult factory for compatible smoke detectors.

CMF-300: Addressable Control Module for one Style Y/Z

(Class B/A) zone of supervised polarized Notification Appli-

ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.

Notification Appliance Circuit option requires external 24 VDC

to power notification appliances.

CRF-300: Addressable relay module containing two isolated

sets of Form-C contacts, which operate as a DPDT switch.

Mounts directly to a 4.0" (10.16 cm.) box, surface mount using

the SMB500.

BG-12LX: Addressable manual pull station with interface mod-

ule mounted inside.

I300: This module isolates the SLC loop from short circuit con-

ditions (required for Style 6 or 7 operation).

SMB500: Used to mount all modules except the MMF-301 and

M301.

df-60334:A1 • 03/26/2009 — Page 3 of 6

Ordering Options

MS-9600LS(E): 318-point addressable Fire Alarm Control

Panel, one SLC loop. Includes 80-character LCD display, sin-

gle printed circuit board, and cabinet.

MS-9600UDLS(E): 318-point addressable Fire Alarm Control

Panel, one SLC loop. Includes DACT-UD2, 80-character LCD

display, single printed circuit board, and cabinet.

DACT-UD2: Optional communicator for remote monitoring

(standard with MS-9600UDLS).

4XTMF: Optional Transmitter Module provides a supervised

output for local energy municipal box transmitter, alarm and

trouble reverse polarity. It includes a disable switch and dis-

able trouble.

IPDACT-2/2UD, IPDACT Internet Monitoring Module:

Mounts in bottom of enclosure with optional mounting kit (P/N:

IPBRKT). Connects to primary and secondary DACT tele-

phone output ports for internet communications over customer

provided ethernet internet connection. Requires compatible

Teldat VisorALARM Central Station Receiver. Can use DHCP

or static IP. (See data sheet DF-60407 or DF-52424 for addi-

tional information.

IPBRKT: Optional mounting bracket kit consisting of screws

and battery shield with standoffs required when mounting the

IPDACT in lower enclosure section of FACP.

IPSPLT: Optional Y-Adaptor which allows connection of both

panel dialer outputs to one cable input to IPDACT (sold sepa-

rately).

ACM-8RF: Optional plug-in relay module provides 8 Form-C

5.0 amp relays.

PK-CD: Contains PS-TOOLS programming software for Win-

dows®-based PC computer (cable not included).

SLC-2LS: Optional expander module, enables second SLC

loop.

DP-9296: Dress panel for MS-9600LS(E) (included with unit).

TR-CE: Optional Trim Ring for semi-flush mounting.

BB-55F: Battery box, required to house two 25 AH batteries

and one CHG-120F battery charger. For batteries greater than

25 AH, consult factory for housing/mounting arrangements.

DACT-UD2

Page 4 of 6 — df-60334:A1 • 03/26/2009

MMF-300-10: Ten-input monitor module. Mount one or two

modules in a BB-2F cabinet (optional). Mount up to six mod-

ules on a CHS-6 chassis in a BB-6F.

MMF-302-6: Six-zone interface module. Mount one or two

modules in a BB-2F cabinet (optional). Mount up to six mod-

ules on a CHS-6 chassis in a BB-6F.

CMF-300-6: Six-circuit supervised control module. Mount one

or two modules in a BB-2F cabinet (optional). Mount up to six

modules on a CHS-6 chassis in a BB-6F.

CRF-300-6: Six Form-C relay control module. Mount one or

two modules in a BB-2F cabinet (optional). Mount up to six

modules on a CHS-6 chassis in a BB-6F.

Compatible Annunciators

ANN-80(-W): Remote LCD annunciator that mimics the infor-

mation displayed on the FACP’s LCD display. Recommended

wire type is unshielded. (Basic model is red; order -W version

for white; see DF-52417).

ANN-LED: Annunciator Module provides three LEDs for each

zone: Alarm, Trouble and Supervisory. Ships with red enclo-

sure (see DF-60241).

ANN-RLED: Provides alarm (red) indicators for up to 30 input

zones or addressable points (see DF-60241).

ANN-RLY: Relay Module, which can be mounted inside the

cabinet, provides 10 programmable Form-C relays (see DF-

52431).

ANN-S/PG: Serial/Parallel Printer Gateway module provides a

connection for a Serial or Parallel printer (see DF-52429).

ANN-I/O: I/O Driver Module provides connections to a user

supplied graphic annunciator (see DF-52430).

ACS-LED Zone Series: LED-type fire annunciators capable of

providing up to 99 software zones of annunciation. Available in

increments of 16 or 32 points to meet a variety of applications.

ACS-LDM Graphic Series: Lamp Driver Module series for

use with custom graphic annunciators.

TERM MODE LCD-80F (Liquid Crystal Display) point

annunciator: 80-character, backlit LCD-type fire annunciators

capable of displaying English-language text. Up to 32 LCD-

80F annunciators may be connected to the EIA-485 terminal

mode serial interface on the MS-9600LS(E) motherboard.

NOTE: For more information on Compatible Annunciators for

use with the MS-9600LS(E), see the following data sheets (docu-

ment numbers) ACM-8RF (DF-51555), ACS/ACM Series (DF-

52378), LDM Series (DF-51384), LCD-80F (DF-52185).

Wiring Requirements

While shielded wire is not required, it is recommended that all

SLC wiring be twisted-pair to minimize the effects of electrical

interference. Refer to the panel manual for wiring details.

df-60334:A1 • 03/26/2009 — Page 5 of 6

SYSTEM SPECIFICATIONS

System Capacity

Intelligent Signalling 1 expandable to 2

159 per loop

Addressable monitor/159 per loop

Programmable 99

8

32

32

Cabinet Specifications

Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x

0.67" (1.70 cm.) deep. Backbox: 19.00" (48.26 cm.) high x

16.65" (42.29 cm.) wide x 5.21" (13.23 cm.) deep. Trim Ring

(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping Specifications

Dimensions: 20.00” (50.80 cm) high, 22.5” (57.15 cm) wide,

8.5” (21.59 cm) deep. Weight: 27.3 lbs (12.38 kg).

Electrical Specifications

•Primary input power:

120 VAC, 50/60 Hz, 3.0 A.

240 VAC, 50 Hz, 1.5 A.

•Battery:************(max).

Maximum battery charger capacity: 26 AH.

Minimum battery: 12 AH.

MS-9600LS cabinet holds maximum of two 18 AH batteries.

•Communication Loop: 24 VDC nominal, supervised and

power-limited.

•Notification Appliance Circuits: terminal block provides con-

nections for four Style Y (Class B) or two Style Z (Class A)

NACs.

Maximum signaling current per circuit: 3.0 A.

End-of-Line Resistor: 4.7 K ohms, ½ watt (P/N 71252 UL

listed) for Style Y (Class B) NAC.

Supervised and power-limited.

Refer to panel documentation and Fire-Lite Device Compat-

ibility Document for listed compatible devices.

•Two Programmable Form-C Relays and One Fixed Trouble

Form-C Relay: Contact rating: 2.0 A @ 30 VDC (resistive)

0.5 A @ 30 VAC (resistive).

•Four-wire Resettable Special Application Power (24 VDC

nominal): Up to 1.5 A for powering four-wire smoke detec-

tors. Power-Limited, nonsupervised.

Refer to Fire-Lite Device Compatibility Document for listed

compatible devices.

•Nonresettable Special Application Power #1 (24VDC nomi-

nal) TB3, Terminals 3 (+) & 4 (-):

Maximum ripple voltage: 10 mV

RMS

Total DC current available from each output is up to 1.5 A.

Power-limited, nonsupervised.

•Nonresettable Special Application Power #2 (24VDC nomi-

nal) TB3, Terminals 5 (+) & 6 (-):

Maximum ripple voltage: 10 mV

RMS

Total DC current available from each output is up to 1.5 A.

Power-limited, nonsupervised.

NOTE: Although each Special Application power output can

deliver 1.5 A individually, the total power output from these circuits

cannot exceed 1.5 A in standby. The total Alarm output for all Spe-

cial Application power and NAC circuits cannot exceed 7 A.

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 –

49°C/32 – 120°F and at a relative humidity 93% ± 2% RH

(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the

useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme tempera-

ture ranges and humidity. Therefore, it is recommended that

this system and its peripherals be installed in an environment

with a normal room temperature of 15 – 27°C/60 – 80°F.

Agency Listings and Approvals

The listings and approvals below apply to the MS-9600LS(E)

and MS-9600UDLS(E) control panels. In some cases, certain

modules may not be listed by certain approval agencies, or list-

ing may be in process. Consult factory for latest listing status.

ULC: S624 (MS-9600LSC only; see DF-60438)

FM APPROVED: to UL ANSI 864

CSFM: 7170-0075:220

MEA: 87-08-E

NFPA Standards

The MS-9600LS(E) and MS-9600UDLS(E) control panels

comply with the following NFPA 72 Fire Alarm Systems

requirements:

–LOCAL (Automatic, Manual, Waterflow and Sprinkler

Supervisory).

–AUXILIARY (Automatic, Manual and Waterflow) (requires

4XTMF).

–REMOTE STATION (Automatic, Manual and Waterflow)

(Requires 4XTMF where DACT-UD2 is not accepted.)

–PROPRIETARY (Automatic, Manual and Waterflow).

–CENTRAL STATION (Automatic, Manual and Waterflow,

and Sprinkler Supervised).

–OT (Other Technologies-PSDN) For use with IPDACT.

LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark

of Honeywell International Inc.

©2009 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

Made in the U.S. A.