MultiPlus-II 2x120V Inverter/Charger
120/240V input and output, or 120V input and output (always 120V output when in inverter mode)
The AC input can be supplied from a split phase 120/240V source, or single phase 120V source.
When an AC source is available, the MultiPlus will feed through the AC to its output. The output will therefore mirror the
AC input.
The inverter/charger connects to the neutral and the preferred input line (L1). Power needed to charge the batteries will
therefore be drawn from L1.
The MultiPlus switches to inverter operation when no AC source is available. The inverter output is 120V single phase. In
invert mode, the MultiPlus connects both output lines (L1 and L2) together to provide 120VAC to loads on either line.
Any 240V loads will therefore be supplied only when the MultiPlus is supplied by a split phase AC source. This prevents
heavy loads such as water heaters or 240V air conditioners from discharging the battery.
PowerControl and PowerAssist - Boosting the capacity of the grid or a generator
A maximum grid or generator current can be set. The MultiPlus will then take account of other AC loads and use
whatever is extra for battery charging, thus preventing the generator or grid from being overloaded (PowerControl
function).
PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a
limited period, the MultiPlus-II will compensate insufficient generator, shore or grid power with power from the battery.
When the load reduces, the spare power is used to recharge the battery (available on L1 input only).
Two AC Outputs
The main output has no break functionality. The MultiPlus takes over the supply to the connected 120V loads in the
event of a grid failure or when shore/generator power is disconnected. The transfer time of the L1 output is less than
18 milliseconds so that computers and other electronic equipment will continue to operate without disruption.
The transfer time of the L2 output is longer: approximately 40 milliseconds.
The second (auxiliary) output is live only when AC is available on the input of the MultiPlus. Loads that should not
discharge the battery can be connected to this output.
Virtually unlimited power thanks to parallel and three phase operation
Up to 6 Multis can operate in parallel to achieve higher power output.
In addition to parallel connection, three units of the same model can be configured for three phase output.
In multi-phase setups, L2 is disabled on all units.
On-site system configuring, monitoring and control
Settings can be changed in a matter of minutes with VEConfigure software (computer or laptop and MK3-USB interface
needed).
Several monitoring and control options are available: Cerbo GX, Color Control GX, Venus GX, , CANvu GX, laptop,
computer, Bluetooth (with the optional Smart dongle), Battery Monitor, Digital Multi Control Panel.
Remote configuring and monitoring
Install a Cerbo GX or other GX product to connect to the internet.
Operational data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.
When connected to the internet, systems can be accessed remotely, and settings can be changed.
Power flow: inverter mode
Power flow, 120VAC-input
Power flow, split phase input
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
DC Input voltage range
Output when in inverter mode
Cont. output power at 25°C (3)
Cont. output power at 25°C
Cont. output power at 40°C
Cont. output power at 65°C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
Auxiliary output (5)
External AC current sensor (optional)
Programmable relay (6)
Protection (2)
VRM Portal
Our free remote monitoring website (VRM) will display all
system data in a comprehensive graphical format. System
settings can be changed remotely via the portal. Alarms can be
received by e-mail.
communication port
General purpose com. Port (7)
Remote on-off
Operating temperature range
Humidity (non-condensing)
Material & Colour
Protection category
Battery-connection
120/240 V AC-connection
Weight
Dimensions (hxwxd)
Safety
Emission, Immunity
1) Can be adjusted to 50 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 120 VAC on inverter output
g) input voltage ripple too high
Yes (on L1 input)
50 A
50A (each leg)
INVERTER
9,5 – 17 V 19-33V
Output voltage: 120 VAC ± 2%
Frequency
:
60 Hz ± 0,1% (1)
3000 VA
2400 W
2200 W
1700 W
2500 VA
5500 W
93% 94%
15W 11W
10W 8W
4W 4W
CHARGER
Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
14,4 V 28,8 V
13,8 V 27,6 V
13,2 V 26,4 V
120 A 70 A
Yes
GENERAL
50 A (each leg) See note 8
100 A
Yes
a – g
For parallel and three phase operation,
remote monitoring and system integration
Cerbo GX with GX Touch 50
Provides intuitive system control and monitoring
Besides system monitoring and control the Cerbo enables access to
our free remote monitoring website: the VRM Online Portal
Yes, 2x
Yes
-40 to +65°C (-40 -150°F) Fan assisted cooling
max 95%
ENCLOSURE
Steel, blue RAL 5012
IP22
2x2 M8 bolts 2 M8 bolts
Screw terminals 21 mm² (4 AWG)
22 kg (48 lb)
578 x 275 x 148 mm 578 x 275 x 148 mm
(23 x 11 x 6 inch) (23 x 11 x 6 inch)
STANDARDS
EN-IEC 60335-1, EN-IEC 60335-2-29, UL 458
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
3) Non-linear load, crest factor 3:1
4) Up to 75 ˚ F / 25 ˚ C ambient
5) Switches off when no external AC source available
6) Programmable relay that be set for general alarm,
DC under voltage or genset start/stop function
AC rating: 120 V/4 A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
7) A. o. to communicate with a Lithium-Ion battery BMS
8) The auxiliary output of an early production batch of this
product was rated at 35A instead of 50A. This batch has serial
numbers starting with HQ2107. Later batches, with 50A aux.
output have serial numbers starting with HQ2114 or higher.
VRM app
Monitor and manage your
Victron Energy system from
your smart phone and
tablet. Available for both
iOS and Android.
Smart Dongle
Measures battery voltage and
temperature and allows
monitoring and control with a
smart phone or other
Bluetooth enabled device.
Connection Area
Current sensor 100A:50mA
To implement PowerControl and
PowerAssist and to optimize self-
consumption with external current
sensing.
Maximum current: 50A resp. 100A.
Digital Multi Control Panel
A convenient and low-cost solution for remote
monitoring, with a rotary knob to set
PowerControl and PowerAssist levels.
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands
E-mail:***********************|
2024年10月30日发(作者:冯驰雪)
MultiPlus-II 2x120V Inverter/Charger
120/240V input and output, or 120V input and output (always 120V output when in inverter mode)
The AC input can be supplied from a split phase 120/240V source, or single phase 120V source.
When an AC source is available, the MultiPlus will feed through the AC to its output. The output will therefore mirror the
AC input.
The inverter/charger connects to the neutral and the preferred input line (L1). Power needed to charge the batteries will
therefore be drawn from L1.
The MultiPlus switches to inverter operation when no AC source is available. The inverter output is 120V single phase. In
invert mode, the MultiPlus connects both output lines (L1 and L2) together to provide 120VAC to loads on either line.
Any 240V loads will therefore be supplied only when the MultiPlus is supplied by a split phase AC source. This prevents
heavy loads such as water heaters or 240V air conditioners from discharging the battery.
PowerControl and PowerAssist - Boosting the capacity of the grid or a generator
A maximum grid or generator current can be set. The MultiPlus will then take account of other AC loads and use
whatever is extra for battery charging, thus preventing the generator or grid from being overloaded (PowerControl
function).
PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a
limited period, the MultiPlus-II will compensate insufficient generator, shore or grid power with power from the battery.
When the load reduces, the spare power is used to recharge the battery (available on L1 input only).
Two AC Outputs
The main output has no break functionality. The MultiPlus takes over the supply to the connected 120V loads in the
event of a grid failure or when shore/generator power is disconnected. The transfer time of the L1 output is less than
18 milliseconds so that computers and other electronic equipment will continue to operate without disruption.
The transfer time of the L2 output is longer: approximately 40 milliseconds.
The second (auxiliary) output is live only when AC is available on the input of the MultiPlus. Loads that should not
discharge the battery can be connected to this output.
Virtually unlimited power thanks to parallel and three phase operation
Up to 6 Multis can operate in parallel to achieve higher power output.
In addition to parallel connection, three units of the same model can be configured for three phase output.
In multi-phase setups, L2 is disabled on all units.
On-site system configuring, monitoring and control
Settings can be changed in a matter of minutes with VEConfigure software (computer or laptop and MK3-USB interface
needed).
Several monitoring and control options are available: Cerbo GX, Color Control GX, Venus GX, , CANvu GX, laptop,
computer, Bluetooth (with the optional Smart dongle), Battery Monitor, Digital Multi Control Panel.
Remote configuring and monitoring
Install a Cerbo GX or other GX product to connect to the internet.
Operational data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.
When connected to the internet, systems can be accessed remotely, and settings can be changed.
Power flow: inverter mode
Power flow, 120VAC-input
Power flow, split phase input
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
DC Input voltage range
Output when in inverter mode
Cont. output power at 25°C (3)
Cont. output power at 25°C
Cont. output power at 40°C
Cont. output power at 65°C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
Auxiliary output (5)
External AC current sensor (optional)
Programmable relay (6)
Protection (2)
VRM Portal
Our free remote monitoring website (VRM) will display all
system data in a comprehensive graphical format. System
settings can be changed remotely via the portal. Alarms can be
received by e-mail.
communication port
General purpose com. Port (7)
Remote on-off
Operating temperature range
Humidity (non-condensing)
Material & Colour
Protection category
Battery-connection
120/240 V AC-connection
Weight
Dimensions (hxwxd)
Safety
Emission, Immunity
1) Can be adjusted to 50 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 120 VAC on inverter output
g) input voltage ripple too high
Yes (on L1 input)
50 A
50A (each leg)
INVERTER
9,5 – 17 V 19-33V
Output voltage: 120 VAC ± 2%
Frequency
:
60 Hz ± 0,1% (1)
3000 VA
2400 W
2200 W
1700 W
2500 VA
5500 W
93% 94%
15W 11W
10W 8W
4W 4W
CHARGER
Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
14,4 V 28,8 V
13,8 V 27,6 V
13,2 V 26,4 V
120 A 70 A
Yes
GENERAL
50 A (each leg) See note 8
100 A
Yes
a – g
For parallel and three phase operation,
remote monitoring and system integration
Cerbo GX with GX Touch 50
Provides intuitive system control and monitoring
Besides system monitoring and control the Cerbo enables access to
our free remote monitoring website: the VRM Online Portal
Yes, 2x
Yes
-40 to +65°C (-40 -150°F) Fan assisted cooling
max 95%
ENCLOSURE
Steel, blue RAL 5012
IP22
2x2 M8 bolts 2 M8 bolts
Screw terminals 21 mm² (4 AWG)
22 kg (48 lb)
578 x 275 x 148 mm 578 x 275 x 148 mm
(23 x 11 x 6 inch) (23 x 11 x 6 inch)
STANDARDS
EN-IEC 60335-1, EN-IEC 60335-2-29, UL 458
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
3) Non-linear load, crest factor 3:1
4) Up to 75 ˚ F / 25 ˚ C ambient
5) Switches off when no external AC source available
6) Programmable relay that be set for general alarm,
DC under voltage or genset start/stop function
AC rating: 120 V/4 A
DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
7) A. o. to communicate with a Lithium-Ion battery BMS
8) The auxiliary output of an early production batch of this
product was rated at 35A instead of 50A. This batch has serial
numbers starting with HQ2107. Later batches, with 50A aux.
output have serial numbers starting with HQ2114 or higher.
VRM app
Monitor and manage your
Victron Energy system from
your smart phone and
tablet. Available for both
iOS and Android.
Smart Dongle
Measures battery voltage and
temperature and allows
monitoring and control with a
smart phone or other
Bluetooth enabled device.
Connection Area
Current sensor 100A:50mA
To implement PowerControl and
PowerAssist and to optimize self-
consumption with external current
sensing.
Maximum current: 50A resp. 100A.
Digital Multi Control Panel
A convenient and low-cost solution for remote
monitoring, with a rotary knob to set
PowerControl and PowerAssist levels.
Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands