INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
P/NO : MFL40910608
Installation
Requirements
3
Installation of Indoor,
.6
The indoor unit
9
Remote controller
24
25
Connecting Pipes to
the 27
Installation to
29
Indoor unit drain
30
• Pipes:Gas side
Liquid side
• Insulated drain hose
• Additional Drain hose
Inner Dia
32mm
25mm
• Additional drain pipe
(Convertible type)
(15.5mm)
• Flaring Tools set
• Torque Wrenches
• Hexagonal Wrench (4mm, 5mm)
• Gas-leak detector
Required PartsRequired Tools
• Connecting cable
• Four Type "A" Screw
• Hanging Bolt
(W 3/8 or M10 length 650mm)
• Level
• Screw driver
• Electric drill
• Hole core drill (ø70mm)
35
•
Owner’s Manual
• Thermometer
37
Installation guide at
.42
2Air Conditioner
Safety Precautions
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions
must be followed.
IBe sure to read before installing the air conditioner.
IBe sure to observe the cautions specified here as they include important items related to safety.
IIncorrect operation due to ignoring instruction will cause harm or seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
IThe meanings of the symbols used in this manual are as shown below.
ENGLISH
Be sure not to do.
Be sure to follow the instruction.
IInstallation
Always perform ’t use a power cord,a
plug or a loose socket which
is damaged.
• Otherwise, it may cause a fire
or electrical shock.
Always install an air leakage
breaker and a dedicated
switching board.
For installation of the product,
always contact the service
center or a professional
installation agency.
• Otherwise, it may cause a fire,
electrical shock, explosion or
injury.
Do not keep or use flammable
gases or combustibles near
the air conditioner.
• Otherwise, it may cause a fire
or the failure of product.
• Otherwise, it may cause
electrical shock.
Securely attach the electrical
part cover to the indoor unit
and the service panel to the
outdoor unit.
• If the electrical part cover of the• No installation may cause a fire
and electrical unit and the service
panel of the outdoor unit are not
attached securely, it could result
in a fire or electric shock due to
dust, water, etc.
Ensure that an installation frame of the
outdoor unit is not damaged due to use for a
long time.
• It may cause injury or an accident.
Do not disassemble or repair the product
randomly.
• It will cause a fire or electrical shock.
Installation Manual 3
Safety Precautions
Do not install the product at a place that there
is concern of falling down.
• Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
• Sharp edges may cause injury.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge.
Do not compress air or Oxygen and Do not use Flammable gases.
Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
■Operation
Do not share the outlet with
other appliances.
• It will cause an electric shock
or a fire due to heat
generation.
Take care so that the power
cord may not be pulled
during operation.
• Otherwise, it may cause a fire
or electrical shock.
Take the power plug out if
necessary, holding the head
of the plug and do not touch
it with wet hands.
• Otherwise, it may cause a fire
or electrical shock.
Do not allow water to run
into electrical parts.
Do not use the damaged
power cord.
• Otherwise, it may cause a fire
or electrical shock.
Unplug the unit if strange
sounds, smell, or smoke
comes from it.
• Otherwise, it may cause
electrical shock or a fire.
Do not use the power cord
near the heating tools.
Do not modify or extend the
power cord randomly.
• Otherwise, it may cause a fire
or electrical shock.
Keep the flames away.
• Otherwise, it may cause a fire.
Do not open the suction
inlet of the indoor/outdoor
unit during operation.
• Otherwise, it may electrical
shock and failure.
Never touch the metal parts
of the unit when removing
the filter.
• They are sharp and may
cause injury.
• Otherwise, it may cause a fire
and electrical shock.
Hold the plug by the head
when taking it out.
• Otherwise, it may cause the• It may cause electric shock
failure of machine or electricaland damage.
shock.
Do not step on the indoor/outdoor unit and
do not put anything on it.
• It may cause an injury through dropping of the
unit or falling down.
When the product is submerged into water,
always contact the service center.
• Otherwise, it may cause a fire or electrical
shock.
4Air Conditioner
Do not place a heavy object on the power
cord.
• Otherwise, it may cause a fire or electrical
shock.
Take care so that children may not step on
the outdoor unit.
• Otherwise, children may be seriously injured
due to falling down.
Safety Precautions
IInstallation
Install the drain hose to ensure that drain
can be securely done.
• Otherwise, it may cause water leakage.
Install the product so that the noise or hot
wind from the outdoor unit may not cause
any damage to the neighbors.
• Otherwise, it may cause dispute with the
neighbors.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water
leakage.
ENGLISH
Always inspect gas leakage after the
installation and repair of product.
• Otherwise, it may cause the failure of product.
IOperation
Avoid excessive cooling and perform
ventilation sometimes.
• Otherwise, it may do harm to your health.
Use a soft cloth to not use wax,
thinner,or a strong detergent.
• The appearance of the air conditioner may
deteriorate, change color, or develop surface
flaws.
Do not place obstacles around the flow inlet
or outlet.
• Otherwise, it may cause the failure of appliance
or an accident.
Do not use an appliance for special purposes
such as preserving animals vegetables,
precision machine,or art articles.
• Otherwise, it may damage your properties.
Installation Manual 5
Installation of Indoor, Outdoor Unit
Installation of Indoor,Outdoor Unit
Selection of the best location
unit
Cassette type
• There should not be any heat source or steam
near the unit.
• There should not be any obstacles to prevent
the air circulation.
• A place where air circulation in the room will
be good.
• A place where drainage can be easily
obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance
space.
Ceiling
Ceiling Board
3
0
o
r
m
o
r
e
Ceiling Board
3
0
o
r
l
e
s
s
Unit:cm
Duct type
• The place shall easily bear a load exceeding
four times the indoor unit’s weight.
• The place shall be able to inspect the unit as
the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water
drainage.(Suitable dimension “H”is necessary
to get a slope to drain as figure.)
• The place shall easily connect with the
outdoor unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will
be good .
• There should not be any heat source or steam
near the unit
Top view
(unit: mm)
Inspection hole
(600X600)
Control box
Front view
1
0
0
0
600
A
b
o
v
e
2
5
0
3
3
0
o
r
l
e
s
s
50 or
more
1
0
0
o
r
m
o
r
e
50 or
more
Floor
600
Front
H
6Air Conditioner
Installation of Indoor, Outdoor Unit
Convertible type
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in
front of the unit.
• Make sure that condensation drainage can be
conveniently routed away.
• Do not install near a doorway.
• Ensure that the interval between a wall and
the left (or right) of the unit is more than
70cm.
• Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
• There should not be any heat source or steam
near the unit.
• There should not be any obstacles to prevent
the air circulation.
• A place where air circulation in the room will
be good.
• A place where drainage can be easily
obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
(Floor/Wall installation)
More than
20cm
More than eye-level
More than
70cm
ENGLISH
More than
30cm
More than
70cm
More than
20cm
(Ceiling installation)
More than
20cm
More than
20cm
r unit
an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
that the spaces indicated by arrows
around front, back and side of the unit.
not place animals and plants in the path
of the warm air.
the air conditioner weight into account
and select a place where noise and vibration
are minimum.
a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
More than 60cm
More than
30cm
More than 30cm
More than
70cm
More
than 60cm
Installation Manual 7
Installation of Indoor, Outdoor Unit
length and the elevation
Capacity
24k Btu/h
30k Btu/h
36k Btu/h
Pipe Size
(Diameter:Ø)
GasLiquid
5/8"(15.88mm)3/8"(9.52mm)
5/8"(15.88mm)3/8"(9.52mm)
5/8"(15.88mm)3/8"(9.52mm)
Length A(m)
Standard
7.5
7.5
7.5
Max.
40
50
50
Elevation B(m)
Standard
5
5
5
Max.
30
30
30
*Additional
refrigerant(g/m)
45
45
45
Indoor unit
Outdoor unit
Outdoor unit
A
B
Outdoor unit
Indoor unit
A
B
Oil trap
A
B
Indoor unit
If piping length is more than 5m
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
8Air Conditioner
The indoor unit installation
The indoor unit installation
te type
ENGLISH
Ceiling
Ceiling board
Level gauge
TE Series
600 (Ceiling opening)
39.5
521(Hanging bolt)
39.5
45
TH/TD Series
875 (Ceiling opening)
785(Hanging bolt)
45
TM/TN/TP Series
875
(Ceiling opening)
787
(Hanging bolt)
1
0
1
.
5
6
7
2
(
H
a
n
g
i
n
g
b
o
l
t
)
1
0
1
.
5
6
7
2
(
H
a
n
g
i
n
g
b
o
l
t
)
7
5
6
0
0
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
8
7
5
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
5
7
0
U
n
i
t
s
i
z
e
8
4
0
U
n
i
t
s
i
z
e
6
7
1
570 Unit size840 Unit size
840 Unit size
8
4
0
U
n
i
t
s
i
z
e
7
5
Unit:mmUnit:mmUnit:mm
CAUTION :
• This air-conditioner uses a drain
pump.
• Install the unit horizontally using
a level gauge.
• During the installation,care should be
taken not to damage electric wires.
NOTICE
•Select and mark the position for fixing bolts and piping
hole.
•Decide the position for fixing bolts slightly tilted to the
drain direction after considering the direction of drain
hose.
•Drill the hole for anchor bolt on the wall.
• Avoid the following installation location.
places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it
may not suck oily steam.
installng air conditioner
Air conditioner
in such places where
cooking oil or iron powder is
generated.
Take enough
places where
distance
inflammable gas is generated.
Use the ventilation fan
for smoke-collecting
place where noxious gas is
hood with sufficient
capacity.
generated.
Cooking table
places near high frequency
generators.
Installation Manual 9
8
7
5
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
6
8
4
(
H
a
n
g
i
n
g
b
o
l
t
)
The Indoor Unit Installation
Ceiling
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Keep the length of the bolt
from the bracket to 40mm
Flat washer for M10
(accessory)
Ceiling board
Air Conditioner body
Ceiling board
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Paper model
for installation
Adjust the same height
Set screw of
paper model (4 pieces)
Open the ceiling board
along the outer edge of the
paper model
• The following parts is option.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
• Drill the piping hole on the wall slightly tilted to the
outdoor side using a Ø 70 hole-core drill.
Wall
IndoorOutdoor
CAUTION:Tighten the nut and bolt
to prevent unit falling.
5
~
7
m
m
10Air Conditioner
1
5
0
m
m
The Indoor Unit Installation
type
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and
duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
(Unit:mm)
Dimension
Capacity
ENGLISH
A
B
ABCDEF
30
30
(G)HI
30/36k Btu/hr45.5450
24k Btu/h93288035545.5450
87830186
87750163
I
H
Drainage hole
CASE 2
• Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
M10 NutX 4
(Local
M10 SP. washer X 4
supply)
M10 washer
X 4
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and
that can support the weight of the unit.
• A place where the unit can withstand its
vibration.
• A place where service can be easily
performed.
M10 washer X 4
(Local
M10 SP. washer
X 4
supply)
M10 NutX 4
Installation Manual 11
F
(G)
D
C
E
The Indoor Unit Installation
• Select and mark the position for fixing
bolts.
• Drill the hole for set anchor on the face
of ceiling.
• Insert the set anchor and washer onto
the suspension bolts for locking the
suspension bolts on the ceiling.
• Mount the suspension bolts to the set
anchor firmly.
• Secure the installation plates onto the
suspension bolts (adjust level roughly)
using nuts, washers and spring
washers.
Old buildingNew building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
CAUTION:Tighten the nut and bolt top
revent unit falling.
• Local supply
Set anchor
Plate washer
Spring washer
Nut
Suspension bolt
- M10
- M10
- W3/8 or M10
- W3/8 or M10
12Air Conditioner
The Indoor Unit Installation
CAUTION
ENGLISH
ldeclinationoftheindoorunitisveryimportantforthedrainoftheducttypeair
conditioner.
mthicknessoftheinsulationfortheconnectingpipeshallbe5mm.
Frontofview
•Theunitmustbehorizontalordeclinedtothedrainhoseconnectedwhenfinished
installation.
Ceiling
1
~
3
m
m
CORRECT
Drainage hole
INCORRECT
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
•Alwayslaythedrainwithdownward
inclination(1/50to1/100).
Preventanyupwardfloworreverseflow
inanypart.
•5mmorthickerformedthermalinsulator
shallalwaysbeprovidedforthedrain
pipe.
Lay the drain hose with a downward
inclination so water will drain out.
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)
Unit
Make sure to be ge hole
•Upwardroutingnot
allowed
CORRECT
INCORRECT
AppliedU-TrapDimension
•InstalltheP-Trap(orU-Trap)toprevent
awaterleakagecausedbytheblocking
ofintakeairfilter.
A 70mm
B 2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A 70mm
B 40mm
C 20mm
B
C
A
U-Trap
Installation Manual 13
The Indoor Unit Installation
tible type
Open side cover
two screws from side-cover as
shown in fig.
side-cover from side panel by slightly
pulling the edge of side cover.
the side-cover with your palm on the
backside.(Inlet grill side.)
the side-cover with other hand while
tapping to prevent it to fall down.
Drain hole is on the left side of the unit
and side cover opening is common for drain
pipe,connecting pipe and wiring diagram.
the rubber stopple in the desired
drain direction.
out the pipe hole from the left side-
cover with the help or nipper/plier.
hole on right side-cover only if right
side is selected for water drain.
2
Edge part
1
14Air Conditioner
The Indoor Unit Installation
MOUNTING THE ANCHOR NUT AND
BOLT
• Prepare 4 suspension bolts.(Each bolts length
should be same.)
• Measure and mark the position for the
Suspension bolts and the piping hole.
• Drill the hole for anchor nut on the ceiling.
• Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
• Mount the suspension bolts to the anchor-nuts
firmly.
• Secure the hangers onto the Suspension bolts
(adjust level roughly.) using nuts, washers and
spring washers.
• Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
• Adjust a level on the direction of top-bottom by
adjusting supension the unit will be
declined to the bottomside so as to drain well.
Suspension
bolts
Spring
washer
Hangen
Max.
12mm
Nut
DIM.
MODEL
VL
VK
VJ
Anchor nut
Ceiling
Nut
Suspension
bolts
Washer
A
1655
1255
855
B
320
320
320
ENGLISH
A
Suspension bolt
B
Washer
:Tighten the nut and bolt to prevent unit
falling.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Flat washer for M10
(accessory)
DRILL A HOLE IN THE WALL.
• Drill the piping hole with a ø70mm hole core
the piping hole at either the right or
the left with the hole slightly slanted to the
outdoor side.
Indoor
WALL
Outdoor
Installation Manual 15
(
3
/
1
6
"
~
5
/
1
6
"
)
5
-
7
m
m
The Indoor Unit Installation
Hang the Indoor unit on suspension bolt as per following guidelines:
the indoor unit to sufficient height.
the suspended part of four suspension bolt in the four hangers provided on the side of
main body one by one.
the indoor unit till the hangers rest on their respective flat washer.
the level in the top down direction by adjusting the suspension bolts.
Inclined the indoor unit as per direction provided in the fig
:Installation Information For Declination
l declinationof the indoor unit is very important for the drainof the
convertible type air conditioner.
m thickness of the insulation for the connecting pipe shall be 10mm.
the Installation Plates are fixed to horizontal line, the indoor unit after installing will
be declined to the bottomside.
Front of view
• The unit must be horizontal or inclined at angle.
• The inclination should be less than or equal to 1°or in between 10 to 20mm inclined in drain
direction as shown in fig.
Ceiling
10~20mm
Side of view
• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
5~10mm
16Air Conditioner
The Indoor Unit Installation
1) Indoor unit installation
IBefore Installing,prepare Installation Plates
• 'Installation Plates' are attached at the bottom
of indoor unit.
Detach them by removing each 3 screws at
both sides.
• Detach 'Side Plate (R,L)' by removing each 2
screws on both sides.
• Pull the upper right and left side of 'Inlet Grille'
to the front, and it will stop at slightly tilted
position.
• Unhook the 'Inlet hanger' from the 'Hanger
screw' on the both left and right side.
• Detach the 'Inlet Grille' from the Indoor Unit.
ENGLISH
Side Plate
Install Plate
Inlet hanger
1) Installation on the ceiling
• Measure and mark the position for the
Suspension bolts and the piping hole.
• Drill the hole for anchor nut on the ceiling.
Inlet Grille
Hanger
screw
1)
1076
265
Before secure the Installation Plates,
select the bent direction of the
Installion Plate to the inside or the
outside according to the installation
circumstances.
Suspension
bolt
Center-line for the
piping hole
2)
1236
265
• Drill the piping hole on the wall slightly tilted
to the outdoor side using a ø70 hole-core
drill.
Indoor
WALL
Outdoor
5~7mm
Installation Manual 17
The Indoor Unit Installation
• Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
• Mount the suspension bolts to the anchor-
nuts firmly.
• Secure the Installation plates onto the
Suspension bolts (adjust level roughly.)
using nuts, washers and spring washers.
1)
Nut
Anchor nut
Ceiling
Washer
Suspension
bolts
Suspension
bolts
Spring
washer
Nut
Max.
12mm
Washer
2)
• Engage 2 hooks on the both left and right
side of the unit to the lower slot of
Installation Plates.
• Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
• Move the hooks on the unit to the upper slot
of Installation the unit will be
declined to the bottomside so as to drain
well.
Lower slot
Level gauge
Suspension
bolt
Adjust a level
Installation plate
Upper slot
18Air Conditioner
The Indoor Unit Installation
CAUTION
ENGLISH
l declinationof the indoor unit is very important for the drainof
the convertible type air conditioner.
m thickness of the insulation for the connecting pipe shall be 7mm.
the Installation Plates are fixed to horizontal line, the indoor unit after
installing will be declined to the bottomside.
Front of view
• The unit must be horizontal or declined to the drain hose connected when finished
installation.
Ceiling
Drain hose
Ceiling
Side of view
• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
Installation Manual 19
The Indoor Unit Installation
• Secure the unit to the Installation Plates
with four M8 bolts and washers.
• Before working, refer to "Connecting pipe
to Indoor Unit" on page 16.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
Inlet hanger
Hook
Cabinet Bottom
• Fit the projection hooks of the side plates to
the 'Side Panel' and the 'Front Panel' by
lifting it.
• Fasten the screws.
2
1
20Air Conditioner
The Indoor Unit Installation
2) Installation on the Wall
• Select and mark the position for fixing bolts
and piping hole.
Decide the position for fixing bolts slightly
tilted to the drain direction after considering
the direction of drain hose.
• Drill the hole for anchor nut on the wall.
m
o
1
0
7
6
ENGLISH
r
e
t
2
6
0
h
a
n
2
6
5
• Drill the piping hole on the wall slightly tilted
to the outdoor side using a ø70 hole-core
drill.
Wall
IndoorOutdoor
• Secure the 'Install Plate' onto the wall with
four anchor bolts, washers and spring
washers.
Spring
washer
Wall
Nut
Washer
Anchor nut
Less than
12mm
Before secure the Install Plates, select the
bent direction of the 'Install Plate' to the
inside or outside according to the
installation circumstances.
1
2
3
6
Installation Manual 21
5
~
7
m
m
The Indoor Unit Installation
Install the Indoor unit onto Installation Plate.
• Insert 2 hooks on the both left and right
side of the unit to the inner slot (wall side)
of the Installation Plate.
• Secure the unit to the Installation Plate with
four M8 bolts and washers.
Inner slot
• Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 16.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
2
1
• Fit the projection hooks of the side plates to
the 'Side Panel' and the 'Front Panel' by
lifting it.
• Fasten the screws.
22Air Conditioner
The Indoor Unit Installation
3) Installation on the floor
Installation of Mount Bracket.
• Select and mark the position for Mount
Brackets and the piping hole.
• Drill the hole for the anchor nut on the wall.
• Drill the piping hole using a ø70 hole-core
drill.
• Secure the Mount Brackets on the wall with
four M4 screws.
Install the indoor unit onto the Mount
Brackets.
• Engage the slot at the back of the unit with
Mount Bracket.
Slot
From the left wall
more than 760mm
ENGLISH
From the
right wall
more than 840mm
448mm
Floor mount
bracket
• Drill the piping hole with 70mm dia, hole
core drill.
• Piping hole should be slightly slant to the
outdoor side.
Wall
IndoorOutdoor
After Installing,reassemble detached parts.
• Hang the 'Inlet Grille' and hook the 'Inlet
Hanger' to the Hanger Screw.
• Assemble the 'Side Plates(R,L)' with 2
screws on both left and right side.
Slot
Wall
Floor mount
bracket
Install plate
Piping hole
Installation Manual 23
5
~
7
m
m
Remote Controller Installation
Wired Remote Controller Installation
DISASSEMBLING
Front case
T
h
• Separate the under plate from Remote control box.
e
l
o
w
e
r
p
a
r
t
Lever carefully
the box open
using a screw
driver, etc.
Remote control
box body
• Fix the under plate on the wall
Face of wall
Under plate
• Fix the cord clamps on the wall by
ø 3 tapping screws (accessory).
• Fix the remote control cord.
Cord clamp
(accessory)
Screw (accessory)
ELECTRICAL WIRING
(Main board)
CN REMO
Wire and make sure that terminal
numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
2
use a wire size greater than 0.5mm.
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
the battery cover from the remote
controller.
• Slide the cover according to the arrow direction.
the two batteries.
• Be sure that the (+) and (-) directions are
correct.
• Be sure that both batteries are new.
-attach the cover.
• Slide it back into position.
24Air Conditioner
• Do not use rechargeable
batteries, such batteries differ
from standard dry cells in
shape, dimensions, and
performance.
• Romove the batteries from the
remote controller if the air
conditioner is not going to be
used for some long time.
Wiring Connection
Wiring Connection
ENGLISH
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Indoor
power cord
Remote
controller
cord
Control box cover
[Air inlet side view]
Control box cover screw
36k Btu
(3Ø)
R
Terminals on the Outdoor Unit
STN1(L)2(N)3
POWER INPUT
Terminals on the Indoor Unit
1(L)2(N)345
30k Btu
(1Ø)
Terminals on the Outdoor Unit
1(L)2(N)1(L)2(N)34
Terminals on the Indoor Unit
1(L)2(N)345
POWER INPUT
24k Btu
(1Ø)
Terminals on the outdoor unit
1(L)2(N)1(L)2(N)34
Terminals on the Indoor Unit
1(L)2(N)345
Power Input
CAUTION
The power cord connected to the outdoor unit
should be complied with the following specifications
(This equipment shall be provided with a cord set complying
with the national regulation.)
Capacity
24k/30k
2
0
m
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications
(This equipment shall be provided with a
cord set complying with the national regulation.)
NORMAL
CROSS-SECTIONAL
AREA0.75mm
2
(12/18/24/30/36K)
2
0
m
m
G
N
/
Y
L
m
1 Phase
2.5mm
7
.
5
m
m
G
N
/
Y
L
G
N
/
Y
L
2
0
m
m
Capacity
36k
3 Phase
1.5mm
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
Installation Manual 25
Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical
components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL
REGULATION.
CAUTION:
• The circuit diagram is not subject to
change without notice.
• Be sure to connect wires according
to the wiring diagram.
• Connect the wires firmly, so that not
to be pulled out easily.
• Connect the wires according to
color codes by referring the wiring
diagram.
Capacity
24k Btu/h
30k Btu/h
36k Btu/h
1 Phase
20 A
30 A
3 Phase
Main power source
Air
Conditioner
Circuit Breaker
Use a 30A circuit breaker
or time delay fuse.
25 A
CAUTION:
The Power cord connected to the unit should be selected according to the following
specifications .
1. Remove the Cover control from the unit by
loosening a screw.
Connect the wires to the terminals on the
control board individually as following.
2. Secure the cable onto the control board with
the holder (clamper).
3. Refix the cover control to the original position
with the screw.
4. Use a recongnized circuit breaker between
the power source and the unit. A
disconnection device to adequately
disconnect all supply lines must be fitted.
Outdoor unit
Terminal block
Over 5mm
Holder for
power supply
cord
Power supply
cord
Connecting
cable
Cover control
Holder for
connecting
cable
26Air Conditioner
Connecting Pipes to the Indoor Unit
Connecting Pipes to the Indoor Unit
ENGLISH
Preparation of Piping
Main cause of gas leakage is defect in flaring
out correct flaring work in the
following procedure.
Copper
tube
90°
Slanted Uneven Rough
the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor
and the outdoor unit.
• Cut the pipes a little longer than measured
distance.
•
Cut the cable 1.5m longer than the pipe
length.
Pipe
Reamer
Point down
removal
• Completely remove all burrs from the cut
cross section of pipe/tube.
• Put the end of the copper tube/pipe to
downward direction as you remove burrs in
order to avoid to let burrs drop in the tubing.
Flare nut
Copper tube
g nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring work)
g work
• Carry out flaring work using dedicated
flaring tool for R-410A as shown below.
Outside diameter
1/4"
3/8"
1/2"
5/8"
3/4"
"A"
1.1~1.3 mm
1.5~1.7 mm
1.6~1.8 mm
1.6~1.8 mm
1.9~2.1 mm
Bar
"A"
Bar
Handle
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Smooth all round
Inside is shining without scratches
= Improper flaring =
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the
flared section and do flaring work again.
Even length
all round
Inclined
SurfaceCrackedUneven
damagedthickness
Installation Manual 27
Connecting Pipes to the Indoor Unit
the piping according to its routing.
Avoid bending and bending back the same
piping point more than three times.(This will
result in hardening the pipe.)
deforming the piping, align centers of
the union fitting of the indoor unit and the
piping, and tighten them firmly with
wrenches.
t pipe to the service valve or ball
valve which is located below the outdoor unit.
completing the piping connection, be
sure to check if there is gas leakage in indoor
and outdoor connection.
Liquid side
Indoor
unit
Outdoor
unit
Flare connection
Gas side
Flare connection
After completing the piping connection,
execute vacuum drying for the connecting
piping and the indoor unit.
The vacuum drying must be carried out
using the service ports of both the liquid and
gas side valves.
CAUTION:Use two wrenches and
tighten with regular torque.'
Outside diameter
mminch
Ø6,351/4
Ø9,523/8
Ø12,71/2
Ø15,885/8
Ø19,053/4
torque
kgf
.
m
1.8~2.5
3.4~4.2
5.5~6.6
6.3~8.2
9.9~12.1
Union
28Air Conditioner
Installation to Decorative Panel
Installation to Decorative Panel
ENGLISH
The decoration panel has its
installation direction.
Before installing the decoration panel,
always remove the paper template.
arily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body.
(Tighten by amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
the air inlet grille from the decoration panel.(Remove the hook for the air inlet grille cord.)
the decoration panel key hole ( ) on the screws fixed in step above, and slide
the panel so that the screws reach the key hole edge.
ten completely two temporarily fixed screws and other two screws.(Total 4 screws)
t the louver motor connector and display connector.
tightening these screws, install the air inlet grille (including the air filter).
Piping side
Air conditioner unit
Control box cover
Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Louver motor
Decoration panel
Display
Lead wire for
louver motor and
display
Decoration panel fixing screws
(Hexagon M5 screw)
Inlet Grille
CAUTION :Install
certainly the
decoration panel.
Cool air leakage
causes sweating.
Water drops fall.
Good exampleBad example
Air conditioner
unit
Ceiling
board
Air
Air conditioner unit
Cool air leakage
(no good)
Ceiling
board
Decoration
panel
Decoration panel
Fit the insulator (this part) and
be careful for cool air leakage
Installation Manual 29
Indoor Unit Drain Piping
CAUTION:Install certainly the decorative panel.
Water drops fall.
Cool air leakage causes sweating.
Good example
Air conditioner
unit
Ceiling
board
Decorative panel
Fit the insulator (this part) and
be careful for cool air leakage
Bad example
Air
Air conditioner unit
Cool air leakage
(no good)
Ceiling
board
Decorative
panel
Indoor Unit Drain Piping
• Drain piping must have down-slope (1/50 to
1/100):be sure not to provide up-and-down
slope to prevent reversal flow.
• During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
• The outside diameter of the drain
connection on the indoor unit is 32mm.
Piping material:Polyvinyl chloride pipe VP-25
and pipe fittings
• Be sure to execute heat insulation on the
drain piping.
• Install the drain raising pipes at a right
angle to the indoor unit and no more than
300mm from the unit.
Pipe clamp
Indoor unit
Upward
routing
not allowed
Maintenance
drain port
300mm or less
1 -1.5m
7
0
0
o
r
l
e
s
s
Drain raising pipe
Clamp metal(attached)Drain hose(attached)
Heat insulation material:Polyethylene foam with thickness more than 8 mm.
Flexible drain hose
Flexible drain hose
30Air Conditioner
Indoor Unit Drain Piping
Drain test
ENGLISH
te type
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior and leave
it provisionally until the test comes to an end.
Flexible drain hose
Feed water
(accessory)
• Feed water to the flexible drain hose and check the
Main
piping for leakage.
drain pipe
• Be sure to check the drain pump for normal
Drain
operating and noise when electrical wiring is
port
Glue the joint
Drain Pump
complete.
Drain hose connection
• When the test is complete, connect the flexible drain
Use the clip (accessory)
hose to the drain port on the indoor unit.
Drain pan
Flexible drain hose
type
1) Remove the Air Filter.
2) Check the drainage.
• Spray one or two glasses of water upon the
evaporator.
• Ensure that water flows drain hose of indoor unit
without any leakage.
Installation Manual 31
Indoor Unit Drain Piping
tible type
the air direction louvers up-and-down to
the position(horizontally) by hand.
To check the drainage.
a glass of water on the evaporator using
a kettle.
the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
Drain piping
drain hose should point downward for
easy drain flow.
Downward slope
not make drain piping like the following.
Do not raise
Accumulated
drain water
Air
Tip of drain hose
dipped in water
Water
leakage
Less than
50mm gap
Water
leakage
Water
leakage
Waving
Ditch
32Air Conditioner
Indoor Unit Drain Piping
Heat insulation
the heat insulation material for the refrigerant piping which has an excellent heat-resistance
(over 120°C).
tions in high humidity
circumstance:
This air conditioner has been tested
according to the "KSStandard Conditions
with Mist" and confirmed that there is not
any r, if it is operated for a
long time in high humid atmosphere (dew
point temperature:more than 23°C), water
drops are liable to this case, add
heat insulation material according to the
following procedure:
• Heat insulation material to
Adiabatic glass wool with thickness 10 to
20mm.
• Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Fastening band
(accessory)
ENGLISH
Refrigerant piping
Indoor unit
Thermal insulator
(accessory)
Forming the piping
Form the piping by wrapping the
connecting portion of the indoor
unit with insulation material and
secure it with two kinds of vinyl
tape.
• If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the the drain
hose appropriately.
Seal a small opening
around the pipings
with gum type sealer.
Drain hose
Taping
In cases where the outdoor unit is
installed below the indoor unit
perform the following.
the piping, drain hose and connecting
cable from down to up.
the tapped piping along the exterior
wall using saddle or equivalent.
Pipings
Plastic Band
Connecting
cable
Power supply
cord
Trap is required to prevent water from entering
into electrical parts.
Installation Manual 33
Indoor Unit Drain Piping
In cases where the Outdoor unit is
installed above the Indoor unit
perform the following.
the piping and connecting cable from
down to up.
the taped piping along the exterior
a trap to prevent water entering
the room.
the piping onto the wall by saddle or
equivalent.
Seal a small opening
around the pipings
with gum type sealer.
Trap
Settlement of outdoor unit
the outdoor unit with a bolt and
nut[ø10mm(0.39in)] tightly and horizontally on
a concrete or rigid mount.
installing on the wall, roof or rooftop,
anchor the mounting base securely with a
nail or wire assuming the influence of wind
and earthquake.
the vibration of the unit is transmitted to the
hose, secure the unit with an anti-vibration
rubber.
34Air Conditioner
Test running
Test running
ENGLISH
TIONS IN TEST RUNNING
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run,carry out the cooling operation firstly even during heating
heating operation is carried out firstly,it leads to the trouble
of attention must be paid.
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer
button for 3 seconds at the same time.
• To cancel the test run, press any button.
CAUTION
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
• Measuring items are room temperature, outside temperature, suction temperature, blow out
temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and
noise, operating pressure, piping temperature, compressive pressure.
• As to the structure and appearance, check following items.
Is the circulation of air adequate?
Is the draining smooth?
Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated?
Is there any faulty wiring?
Are not terminal screws loosened?
M4......118N
.
cm{12kgf
.
cm}
M6......245N
.
cm{25kgf
.
cm}
M5......196N
.
cm{20kgf
.
cm}
M8......588N
.
cm{60kgf
.
cm}
tion of power supply
t the power supply cord to the independent power supply.
• Circuit breaker is required.
e the unit for fifteen minutes or more.
tion of the performance
e the temperature of the
intake and discharge air.
the difference between the
intake temperature and the discharge
one is more than 8°C (Cooling) or
reversely (Heating).
Thermometer
Installation Manual 35
Test running
CAUTIO
N:After the confirmation of the above conditions,prepare the wiring
as follows:
1) Never fail to have an individual power specialized for the air conditioner.
As for the method of wiring,be guided by the circuit diagram pasted on
the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are
liable to come loose from vibrations to which the unit is subjected
during the course of them and make sure that
they are all tightly fastened.(If they are loose,it could give rise to burn-
out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent
of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources
specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse
breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) Use only 1 remote-controller contained in the Cassette type indoor unit,
when you combine to use both cassette type indoor unit and different
kind of indoor unit.
After setting the ESP value in the Duct Type Indoor Unit,the main
power turns off and then remove the remote controller.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual
(air filter cleaning, temperature control, etc.).
36Air Conditioner
Optional Operation
Optional Operation
ENGLISH
Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
• Position 1:The room temperature is controlled by the thermistor of the main body.
• Position 2:The room themperature is controlled by the thermistor of the wired remote-
controller, control the temperature according to the position of wired remote-
controller.
• Position 3:The room temperature is controlled by lower temperature between the
temperature of main body and of remote-controller sensor.
(3) Move the slide switch to set position.
Room Temp. sensor
Slide switch for 2 Thermistor
Position 2
Position 1
Position 3
REMO
MAIN
2TH
Slide switch for ceiling height
(4) Close the rear cover and check if it works normally.
CAUTIO
N:
• Select the position after counselling with a customer.
• In case of cooling mode,room temperature is controlled by the main body sensor.
• To control the room temperature by a wired remote controller,install controller(room
) to sense the temperature more accurately.
• Manufactured in the position 3.
Installation Manual 37
Optional Operation
ing air volume to the height of ceiling (Cassette type)
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to
supply the comfortable atmosphere to consumers.
Procedure
the selectable position in the table after measuring the height of ceiling.
Ceiling height
more than 3.3m
2.7~3.3m
less than 2.7m
Mode of slide switch
High Ceiling
Standard
Low Ceiling
Change of air volume
Increasing
-
Decreasing
Remark
Manufactured in
standard mode
the case of changing the height as "high" or "low", open the rear cover of the wired remote-
controller.
the slide switch to the set position.
Slide switch for 2 Thermistor
Low ceiling
Standard
(Default)
High Ceiling
Lo
STAND
Hi
Slide switch for ceiling height
the rear cover and check if it works normally.
38Air Conditioner
Optional Operation
3.E.S.P.(External Static Pressure) Setting (Duct type)
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
IWithout Zone System
on V-H, F-H:
• This position sets the maximum E.S.P as a default set.
on V-L:
• This position sets the minimum E.S.P as a default set.
IWith Zone System
on V-H:
• Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
on F-H:
• Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of
dampers.
on V-L:
• Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
* Maximum
Minimum
:24k-6mmAq
:0mmAq
ENGLISH
(3) Move the slide switch to set position.
V-L
F-H
V-H
Slide switch for ceiling height
(4) Close the rear cover and check if it works normally.
• Select the position after checking duct work and E.S.P of the unit.
• Maunfactured in the position F-H.
CAUTIO
N:
Installation Manual 39
Optional Operation
to Set E.S.P?
Procedure of RPM change:
Ex) External Static pressure is 6mmAq for 36k.
• To protect the unit, compressor is designed to be off during g.
1
Push the "On/Off" button.
The unit will start.
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrostHumidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
2
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Timer
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrost
Humidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
3
Push the "Up" of "Down" button for E.S.P adjustment.
And, adjust the number which you want.(In this example, the number is "220".Refer to the
table 1 on the next page.)
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrost
Humidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
Note:The range of selection is from 1~, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
4
Shift the fan speed mode by pressing the fan speed button.
And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "235" and "243" respectly)
5
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Timer
OnOff
Set
01
Time
Timer
Operation unit
030507
AUTOHeaterPreheat
JETDefrostHumidify
FilterOut door
ZONE
1234
17192123
Program set
09111315
40Air Conditioner
Optional Operation
[Table.1]
Static Pressure(mmAq)
Model Name
24 k
Step
High
Med
Low
High
30 k
Med
Low
High
36 k
Med
Low
CMM(CFM)
18(636)
16.5(583)
14(494)
26.5(936)
23(812)
20(706)
32(1130)
29(1024)
26.5(936)
220
235
250
153
173
190
230
240
245
205
230
240
150
173
190
230
238
245
190
220
235
150
175
190
225
237
243
50
200
230
148
175
190
220
235
243
02468
Setting Value
1
100
210
130
170
190
150
230
240
1
155
190
1
220
240
10121415
ENGLISH
Note
: sure to set the value refering table cted set value will cause mal-
function.
1 is based at ing to the fluctuation of voltage,air flow rate
varies.
Installation Manual 41
Optional Operation
conditioners should not be installed in areas where corrosive gases, such as acid or alkaline
gas, are produced.
not install the product where it could be exposed to sea wind (salty wind) can
result corrosion on the ion, particularly on the condenser and evaporator fins,
could cause product malfunc-tion or inefficient performance.
outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind
should be l the outdoor unit on the opposite side of the sea wind direction.
Sea windSea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the
sea wind.
Windbreak
• It should be strong enough like concrete
to prevent the sea wind from the sea.
• The height and width should be more
than 150% of the outdoor unit.
Sea wind
• It should be keep more than 70 cm of
space between outdoor unit and the
windbreak for easy air flow.
3) Select a well-drained place.
❈ you can’t meet above guide line in the seaside installation, please contact LG
Electronics for the additional anticorrosion treatment.
ic ( more than once/year ) cleaning of the dust or salt particles stuck on the
heat exchanger by using water
42Air Conditioner
2024年10月5日发(作者:字虹星)
ENGLISH
ESPAÑOL
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
P/NO : MFL40910608
Installation
Requirements
3
Installation of Indoor,
.6
The indoor unit
9
Remote controller
24
25
Connecting Pipes to
the 27
Installation to
29
Indoor unit drain
30
• Pipes:Gas side
Liquid side
• Insulated drain hose
• Additional Drain hose
Inner Dia
32mm
25mm
• Additional drain pipe
(Convertible type)
(15.5mm)
• Flaring Tools set
• Torque Wrenches
• Hexagonal Wrench (4mm, 5mm)
• Gas-leak detector
Required PartsRequired Tools
• Connecting cable
• Four Type "A" Screw
• Hanging Bolt
(W 3/8 or M10 length 650mm)
• Level
• Screw driver
• Electric drill
• Hole core drill (ø70mm)
35
•
Owner’s Manual
• Thermometer
37
Installation guide at
.42
2Air Conditioner
Safety Precautions
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions
must be followed.
IBe sure to read before installing the air conditioner.
IBe sure to observe the cautions specified here as they include important items related to safety.
IIncorrect operation due to ignoring instruction will cause harm or seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
IThe meanings of the symbols used in this manual are as shown below.
ENGLISH
Be sure not to do.
Be sure to follow the instruction.
IInstallation
Always perform ’t use a power cord,a
plug or a loose socket which
is damaged.
• Otherwise, it may cause a fire
or electrical shock.
Always install an air leakage
breaker and a dedicated
switching board.
For installation of the product,
always contact the service
center or a professional
installation agency.
• Otherwise, it may cause a fire,
electrical shock, explosion or
injury.
Do not keep or use flammable
gases or combustibles near
the air conditioner.
• Otherwise, it may cause a fire
or the failure of product.
• Otherwise, it may cause
electrical shock.
Securely attach the electrical
part cover to the indoor unit
and the service panel to the
outdoor unit.
• If the electrical part cover of the• No installation may cause a fire
and electrical unit and the service
panel of the outdoor unit are not
attached securely, it could result
in a fire or electric shock due to
dust, water, etc.
Ensure that an installation frame of the
outdoor unit is not damaged due to use for a
long time.
• It may cause injury or an accident.
Do not disassemble or repair the product
randomly.
• It will cause a fire or electrical shock.
Installation Manual 3
Safety Precautions
Do not install the product at a place that there
is concern of falling down.
• Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
• Sharp edges may cause injury.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge.
Do not compress air or Oxygen and Do not use Flammable gases.
Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
■Operation
Do not share the outlet with
other appliances.
• It will cause an electric shock
or a fire due to heat
generation.
Take care so that the power
cord may not be pulled
during operation.
• Otherwise, it may cause a fire
or electrical shock.
Take the power plug out if
necessary, holding the head
of the plug and do not touch
it with wet hands.
• Otherwise, it may cause a fire
or electrical shock.
Do not allow water to run
into electrical parts.
Do not use the damaged
power cord.
• Otherwise, it may cause a fire
or electrical shock.
Unplug the unit if strange
sounds, smell, or smoke
comes from it.
• Otherwise, it may cause
electrical shock or a fire.
Do not use the power cord
near the heating tools.
Do not modify or extend the
power cord randomly.
• Otherwise, it may cause a fire
or electrical shock.
Keep the flames away.
• Otherwise, it may cause a fire.
Do not open the suction
inlet of the indoor/outdoor
unit during operation.
• Otherwise, it may electrical
shock and failure.
Never touch the metal parts
of the unit when removing
the filter.
• They are sharp and may
cause injury.
• Otherwise, it may cause a fire
and electrical shock.
Hold the plug by the head
when taking it out.
• Otherwise, it may cause the• It may cause electric shock
failure of machine or electricaland damage.
shock.
Do not step on the indoor/outdoor unit and
do not put anything on it.
• It may cause an injury through dropping of the
unit or falling down.
When the product is submerged into water,
always contact the service center.
• Otherwise, it may cause a fire or electrical
shock.
4Air Conditioner
Do not place a heavy object on the power
cord.
• Otherwise, it may cause a fire or electrical
shock.
Take care so that children may not step on
the outdoor unit.
• Otherwise, children may be seriously injured
due to falling down.
Safety Precautions
IInstallation
Install the drain hose to ensure that drain
can be securely done.
• Otherwise, it may cause water leakage.
Install the product so that the noise or hot
wind from the outdoor unit may not cause
any damage to the neighbors.
• Otherwise, it may cause dispute with the
neighbors.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water
leakage.
ENGLISH
Always inspect gas leakage after the
installation and repair of product.
• Otherwise, it may cause the failure of product.
IOperation
Avoid excessive cooling and perform
ventilation sometimes.
• Otherwise, it may do harm to your health.
Use a soft cloth to not use wax,
thinner,or a strong detergent.
• The appearance of the air conditioner may
deteriorate, change color, or develop surface
flaws.
Do not place obstacles around the flow inlet
or outlet.
• Otherwise, it may cause the failure of appliance
or an accident.
Do not use an appliance for special purposes
such as preserving animals vegetables,
precision machine,or art articles.
• Otherwise, it may damage your properties.
Installation Manual 5
Installation of Indoor, Outdoor Unit
Installation of Indoor,Outdoor Unit
Selection of the best location
unit
Cassette type
• There should not be any heat source or steam
near the unit.
• There should not be any obstacles to prevent
the air circulation.
• A place where air circulation in the room will
be good.
• A place where drainage can be easily
obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
• The indoor unit must keep the maintenance
space.
Ceiling
Ceiling Board
3
0
o
r
m
o
r
e
Ceiling Board
3
0
o
r
l
e
s
s
Unit:cm
Duct type
• The place shall easily bear a load exceeding
four times the indoor unit’s weight.
• The place shall be able to inspect the unit as
the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water
drainage.(Suitable dimension “H”is necessary
to get a slope to drain as figure.)
• The place shall easily connect with the
outdoor unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will
be good .
• There should not be any heat source or steam
near the unit
Top view
(unit: mm)
Inspection hole
(600X600)
Control box
Front view
1
0
0
0
600
A
b
o
v
e
2
5
0
3
3
0
o
r
l
e
s
s
50 or
more
1
0
0
o
r
m
o
r
e
50 or
more
Floor
600
Front
H
6Air Conditioner
Installation of Indoor, Outdoor Unit
Convertible type
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in
front of the unit.
• Make sure that condensation drainage can be
conveniently routed away.
• Do not install near a doorway.
• Ensure that the interval between a wall and
the left (or right) of the unit is more than
70cm.
• Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
• There should not be any heat source or steam
near the unit.
• There should not be any obstacles to prevent
the air circulation.
• A place where air circulation in the room will
be good.
• A place where drainage can be easily
obtained.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from
the wall, ceiling, or other obstacles.
(Floor/Wall installation)
More than
20cm
More than eye-level
More than
70cm
ENGLISH
More than
30cm
More than
70cm
More than
20cm
(Ceiling installation)
More than
20cm
More than
20cm
r unit
an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
that the spaces indicated by arrows
around front, back and side of the unit.
not place animals and plants in the path
of the warm air.
the air conditioner weight into account
and select a place where noise and vibration
are minimum.
a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
More than 60cm
More than
30cm
More than 30cm
More than
70cm
More
than 60cm
Installation Manual 7
Installation of Indoor, Outdoor Unit
length and the elevation
Capacity
24k Btu/h
30k Btu/h
36k Btu/h
Pipe Size
(Diameter:Ø)
GasLiquid
5/8"(15.88mm)3/8"(9.52mm)
5/8"(15.88mm)3/8"(9.52mm)
5/8"(15.88mm)3/8"(9.52mm)
Length A(m)
Standard
7.5
7.5
7.5
Max.
40
50
50
Elevation B(m)
Standard
5
5
5
Max.
30
30
30
*Additional
refrigerant(g/m)
45
45
45
Indoor unit
Outdoor unit
Outdoor unit
A
B
Outdoor unit
Indoor unit
A
B
Oil trap
A
B
Indoor unit
If piping length is more than 5m
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
8Air Conditioner
The indoor unit installation
The indoor unit installation
te type
ENGLISH
Ceiling
Ceiling board
Level gauge
TE Series
600 (Ceiling opening)
39.5
521(Hanging bolt)
39.5
45
TH/TD Series
875 (Ceiling opening)
785(Hanging bolt)
45
TM/TN/TP Series
875
(Ceiling opening)
787
(Hanging bolt)
1
0
1
.
5
6
7
2
(
H
a
n
g
i
n
g
b
o
l
t
)
1
0
1
.
5
6
7
2
(
H
a
n
g
i
n
g
b
o
l
t
)
7
5
6
0
0
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
8
7
5
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
5
7
0
U
n
i
t
s
i
z
e
8
4
0
U
n
i
t
s
i
z
e
6
7
1
570 Unit size840 Unit size
840 Unit size
8
4
0
U
n
i
t
s
i
z
e
7
5
Unit:mmUnit:mmUnit:mm
CAUTION :
• This air-conditioner uses a drain
pump.
• Install the unit horizontally using
a level gauge.
• During the installation,care should be
taken not to damage electric wires.
NOTICE
•Select and mark the position for fixing bolts and piping
hole.
•Decide the position for fixing bolts slightly tilted to the
drain direction after considering the direction of drain
hose.
•Drill the hole for anchor bolt on the wall.
• Avoid the following installation location.
places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it
may not suck oily steam.
installng air conditioner
Air conditioner
in such places where
cooking oil or iron powder is
generated.
Take enough
places where
distance
inflammable gas is generated.
Use the ventilation fan
for smoke-collecting
place where noxious gas is
hood with sufficient
capacity.
generated.
Cooking table
places near high frequency
generators.
Installation Manual 9
8
7
5
(
C
e
i
l
i
n
g
o
p
e
n
i
n
g
)
6
8
4
(
H
a
n
g
i
n
g
b
o
l
t
)
The Indoor Unit Installation
Ceiling
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Keep the length of the bolt
from the bracket to 40mm
Flat washer for M10
(accessory)
Ceiling board
Air Conditioner body
Ceiling board
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Paper model
for installation
Adjust the same height
Set screw of
paper model (4 pieces)
Open the ceiling board
along the outer edge of the
paper model
• The following parts is option.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
• Drill the piping hole on the wall slightly tilted to the
outdoor side using a Ø 70 hole-core drill.
Wall
IndoorOutdoor
CAUTION:Tighten the nut and bolt
to prevent unit falling.
5
~
7
m
m
10Air Conditioner
1
5
0
m
m
The Indoor Unit Installation
type
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and
duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
(Unit:mm)
Dimension
Capacity
ENGLISH
A
B
ABCDEF
30
30
(G)HI
30/36k Btu/hr45.5450
24k Btu/h93288035545.5450
87830186
87750163
I
H
Drainage hole
CASE 2
• Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
M10 NutX 4
(Local
M10 SP. washer X 4
supply)
M10 washer
X 4
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and
that can support the weight of the unit.
• A place where the unit can withstand its
vibration.
• A place where service can be easily
performed.
M10 washer X 4
(Local
M10 SP. washer
X 4
supply)
M10 NutX 4
Installation Manual 11
F
(G)
D
C
E
The Indoor Unit Installation
• Select and mark the position for fixing
bolts.
• Drill the hole for set anchor on the face
of ceiling.
• Insert the set anchor and washer onto
the suspension bolts for locking the
suspension bolts on the ceiling.
• Mount the suspension bolts to the set
anchor firmly.
• Secure the installation plates onto the
suspension bolts (adjust level roughly)
using nuts, washers and spring
washers.
Old buildingNew building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
CAUTION:Tighten the nut and bolt top
revent unit falling.
• Local supply
Set anchor
Plate washer
Spring washer
Nut
Suspension bolt
- M10
- M10
- W3/8 or M10
- W3/8 or M10
12Air Conditioner
The Indoor Unit Installation
CAUTION
ENGLISH
ldeclinationoftheindoorunitisveryimportantforthedrainoftheducttypeair
conditioner.
mthicknessoftheinsulationfortheconnectingpipeshallbe5mm.
Frontofview
•Theunitmustbehorizontalordeclinedtothedrainhoseconnectedwhenfinished
installation.
Ceiling
1
~
3
m
m
CORRECT
Drainage hole
INCORRECT
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
•Alwayslaythedrainwithdownward
inclination(1/50to1/100).
Preventanyupwardfloworreverseflow
inanypart.
•5mmorthickerformedthermalinsulator
shallalwaysbeprovidedforthedrain
pipe.
Lay the drain hose with a downward
inclination so water will drain out.
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)
Unit
Make sure to be ge hole
•Upwardroutingnot
allowed
CORRECT
INCORRECT
AppliedU-TrapDimension
•InstalltheP-Trap(orU-Trap)toprevent
awaterleakagecausedbytheblocking
ofintakeairfilter.
A 70mm
B 2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A 70mm
B 40mm
C 20mm
B
C
A
U-Trap
Installation Manual 13
The Indoor Unit Installation
tible type
Open side cover
two screws from side-cover as
shown in fig.
side-cover from side panel by slightly
pulling the edge of side cover.
the side-cover with your palm on the
backside.(Inlet grill side.)
the side-cover with other hand while
tapping to prevent it to fall down.
Drain hole is on the left side of the unit
and side cover opening is common for drain
pipe,connecting pipe and wiring diagram.
the rubber stopple in the desired
drain direction.
out the pipe hole from the left side-
cover with the help or nipper/plier.
hole on right side-cover only if right
side is selected for water drain.
2
Edge part
1
14Air Conditioner
The Indoor Unit Installation
MOUNTING THE ANCHOR NUT AND
BOLT
• Prepare 4 suspension bolts.(Each bolts length
should be same.)
• Measure and mark the position for the
Suspension bolts and the piping hole.
• Drill the hole for anchor nut on the ceiling.
• Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
• Mount the suspension bolts to the anchor-nuts
firmly.
• Secure the hangers onto the Suspension bolts
(adjust level roughly.) using nuts, washers and
spring washers.
• Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
• Adjust a level on the direction of top-bottom by
adjusting supension the unit will be
declined to the bottomside so as to drain well.
Suspension
bolts
Spring
washer
Hangen
Max.
12mm
Nut
DIM.
MODEL
VL
VK
VJ
Anchor nut
Ceiling
Nut
Suspension
bolts
Washer
A
1655
1255
855
B
320
320
320
ENGLISH
A
Suspension bolt
B
Washer
:Tighten the nut and bolt to prevent unit
falling.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Flat washer for M10
(accessory)
DRILL A HOLE IN THE WALL.
• Drill the piping hole with a ø70mm hole core
the piping hole at either the right or
the left with the hole slightly slanted to the
outdoor side.
Indoor
WALL
Outdoor
Installation Manual 15
(
3
/
1
6
"
~
5
/
1
6
"
)
5
-
7
m
m
The Indoor Unit Installation
Hang the Indoor unit on suspension bolt as per following guidelines:
the indoor unit to sufficient height.
the suspended part of four suspension bolt in the four hangers provided on the side of
main body one by one.
the indoor unit till the hangers rest on their respective flat washer.
the level in the top down direction by adjusting the suspension bolts.
Inclined the indoor unit as per direction provided in the fig
:Installation Information For Declination
l declinationof the indoor unit is very important for the drainof the
convertible type air conditioner.
m thickness of the insulation for the connecting pipe shall be 10mm.
the Installation Plates are fixed to horizontal line, the indoor unit after installing will
be declined to the bottomside.
Front of view
• The unit must be horizontal or inclined at angle.
• The inclination should be less than or equal to 1°or in between 10 to 20mm inclined in drain
direction as shown in fig.
Ceiling
10~20mm
Side of view
• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
5~10mm
16Air Conditioner
The Indoor Unit Installation
1) Indoor unit installation
IBefore Installing,prepare Installation Plates
• 'Installation Plates' are attached at the bottom
of indoor unit.
Detach them by removing each 3 screws at
both sides.
• Detach 'Side Plate (R,L)' by removing each 2
screws on both sides.
• Pull the upper right and left side of 'Inlet Grille'
to the front, and it will stop at slightly tilted
position.
• Unhook the 'Inlet hanger' from the 'Hanger
screw' on the both left and right side.
• Detach the 'Inlet Grille' from the Indoor Unit.
ENGLISH
Side Plate
Install Plate
Inlet hanger
1) Installation on the ceiling
• Measure and mark the position for the
Suspension bolts and the piping hole.
• Drill the hole for anchor nut on the ceiling.
Inlet Grille
Hanger
screw
1)
1076
265
Before secure the Installation Plates,
select the bent direction of the
Installion Plate to the inside or the
outside according to the installation
circumstances.
Suspension
bolt
Center-line for the
piping hole
2)
1236
265
• Drill the piping hole on the wall slightly tilted
to the outdoor side using a ø70 hole-core
drill.
Indoor
WALL
Outdoor
5~7mm
Installation Manual 17
The Indoor Unit Installation
• Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
• Mount the suspension bolts to the anchor-
nuts firmly.
• Secure the Installation plates onto the
Suspension bolts (adjust level roughly.)
using nuts, washers and spring washers.
1)
Nut
Anchor nut
Ceiling
Washer
Suspension
bolts
Suspension
bolts
Spring
washer
Nut
Max.
12mm
Washer
2)
• Engage 2 hooks on the both left and right
side of the unit to the lower slot of
Installation Plates.
• Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
• Move the hooks on the unit to the upper slot
of Installation the unit will be
declined to the bottomside so as to drain
well.
Lower slot
Level gauge
Suspension
bolt
Adjust a level
Installation plate
Upper slot
18Air Conditioner
The Indoor Unit Installation
CAUTION
ENGLISH
l declinationof the indoor unit is very important for the drainof
the convertible type air conditioner.
m thickness of the insulation for the connecting pipe shall be 7mm.
the Installation Plates are fixed to horizontal line, the indoor unit after
installing will be declined to the bottomside.
Front of view
• The unit must be horizontal or declined to the drain hose connected when finished
installation.
Ceiling
Drain hose
Ceiling
Side of view
• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
Installation Manual 19
The Indoor Unit Installation
• Secure the unit to the Installation Plates
with four M8 bolts and washers.
• Before working, refer to "Connecting pipe
to Indoor Unit" on page 16.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
Inlet hanger
Hook
Cabinet Bottom
• Fit the projection hooks of the side plates to
the 'Side Panel' and the 'Front Panel' by
lifting it.
• Fasten the screws.
2
1
20Air Conditioner
The Indoor Unit Installation
2) Installation on the Wall
• Select and mark the position for fixing bolts
and piping hole.
Decide the position for fixing bolts slightly
tilted to the drain direction after considering
the direction of drain hose.
• Drill the hole for anchor nut on the wall.
m
o
1
0
7
6
ENGLISH
r
e
t
2
6
0
h
a
n
2
6
5
• Drill the piping hole on the wall slightly tilted
to the outdoor side using a ø70 hole-core
drill.
Wall
IndoorOutdoor
• Secure the 'Install Plate' onto the wall with
four anchor bolts, washers and spring
washers.
Spring
washer
Wall
Nut
Washer
Anchor nut
Less than
12mm
Before secure the Install Plates, select the
bent direction of the 'Install Plate' to the
inside or outside according to the
installation circumstances.
1
2
3
6
Installation Manual 21
5
~
7
m
m
The Indoor Unit Installation
Install the Indoor unit onto Installation Plate.
• Insert 2 hooks on the both left and right
side of the unit to the inner slot (wall side)
of the Installation Plate.
• Secure the unit to the Installation Plate with
four M8 bolts and washers.
Inner slot
• Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 16.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
2
1
• Fit the projection hooks of the side plates to
the 'Side Panel' and the 'Front Panel' by
lifting it.
• Fasten the screws.
22Air Conditioner
The Indoor Unit Installation
3) Installation on the floor
Installation of Mount Bracket.
• Select and mark the position for Mount
Brackets and the piping hole.
• Drill the hole for the anchor nut on the wall.
• Drill the piping hole using a ø70 hole-core
drill.
• Secure the Mount Brackets on the wall with
four M4 screws.
Install the indoor unit onto the Mount
Brackets.
• Engage the slot at the back of the unit with
Mount Bracket.
Slot
From the left wall
more than 760mm
ENGLISH
From the
right wall
more than 840mm
448mm
Floor mount
bracket
• Drill the piping hole with 70mm dia, hole
core drill.
• Piping hole should be slightly slant to the
outdoor side.
Wall
IndoorOutdoor
After Installing,reassemble detached parts.
• Hang the 'Inlet Grille' and hook the 'Inlet
Hanger' to the Hanger Screw.
• Assemble the 'Side Plates(R,L)' with 2
screws on both left and right side.
Slot
Wall
Floor mount
bracket
Install plate
Piping hole
Installation Manual 23
5
~
7
m
m
Remote Controller Installation
Wired Remote Controller Installation
DISASSEMBLING
Front case
T
h
• Separate the under plate from Remote control box.
e
l
o
w
e
r
p
a
r
t
Lever carefully
the box open
using a screw
driver, etc.
Remote control
box body
• Fix the under plate on the wall
Face of wall
Under plate
• Fix the cord clamps on the wall by
ø 3 tapping screws (accessory).
• Fix the remote control cord.
Cord clamp
(accessory)
Screw (accessory)
ELECTRICAL WIRING
(Main board)
CN REMO
Wire and make sure that terminal
numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
2
use a wire size greater than 0.5mm.
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
the battery cover from the remote
controller.
• Slide the cover according to the arrow direction.
the two batteries.
• Be sure that the (+) and (-) directions are
correct.
• Be sure that both batteries are new.
-attach the cover.
• Slide it back into position.
24Air Conditioner
• Do not use rechargeable
batteries, such batteries differ
from standard dry cells in
shape, dimensions, and
performance.
• Romove the batteries from the
remote controller if the air
conditioner is not going to be
used for some long time.
Wiring Connection
Wiring Connection
ENGLISH
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Indoor
power cord
Remote
controller
cord
Control box cover
[Air inlet side view]
Control box cover screw
36k Btu
(3Ø)
R
Terminals on the Outdoor Unit
STN1(L)2(N)3
POWER INPUT
Terminals on the Indoor Unit
1(L)2(N)345
30k Btu
(1Ø)
Terminals on the Outdoor Unit
1(L)2(N)1(L)2(N)34
Terminals on the Indoor Unit
1(L)2(N)345
POWER INPUT
24k Btu
(1Ø)
Terminals on the outdoor unit
1(L)2(N)1(L)2(N)34
Terminals on the Indoor Unit
1(L)2(N)345
Power Input
CAUTION
The power cord connected to the outdoor unit
should be complied with the following specifications
(This equipment shall be provided with a cord set complying
with the national regulation.)
Capacity
24k/30k
2
0
m
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications
(This equipment shall be provided with a
cord set complying with the national regulation.)
NORMAL
CROSS-SECTIONAL
AREA0.75mm
2
(12/18/24/30/36K)
2
0
m
m
G
N
/
Y
L
m
1 Phase
2.5mm
7
.
5
m
m
G
N
/
Y
L
G
N
/
Y
L
2
0
m
m
Capacity
36k
3 Phase
1.5mm
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
Installation Manual 25
Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical
components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL
REGULATION.
CAUTION:
• The circuit diagram is not subject to
change without notice.
• Be sure to connect wires according
to the wiring diagram.
• Connect the wires firmly, so that not
to be pulled out easily.
• Connect the wires according to
color codes by referring the wiring
diagram.
Capacity
24k Btu/h
30k Btu/h
36k Btu/h
1 Phase
20 A
30 A
3 Phase
Main power source
Air
Conditioner
Circuit Breaker
Use a 30A circuit breaker
or time delay fuse.
25 A
CAUTION:
The Power cord connected to the unit should be selected according to the following
specifications .
1. Remove the Cover control from the unit by
loosening a screw.
Connect the wires to the terminals on the
control board individually as following.
2. Secure the cable onto the control board with
the holder (clamper).
3. Refix the cover control to the original position
with the screw.
4. Use a recongnized circuit breaker between
the power source and the unit. A
disconnection device to adequately
disconnect all supply lines must be fitted.
Outdoor unit
Terminal block
Over 5mm
Holder for
power supply
cord
Power supply
cord
Connecting
cable
Cover control
Holder for
connecting
cable
26Air Conditioner
Connecting Pipes to the Indoor Unit
Connecting Pipes to the Indoor Unit
ENGLISH
Preparation of Piping
Main cause of gas leakage is defect in flaring
out correct flaring work in the
following procedure.
Copper
tube
90°
Slanted Uneven Rough
the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor
and the outdoor unit.
• Cut the pipes a little longer than measured
distance.
•
Cut the cable 1.5m longer than the pipe
length.
Pipe
Reamer
Point down
removal
• Completely remove all burrs from the cut
cross section of pipe/tube.
• Put the end of the copper tube/pipe to
downward direction as you remove burrs in
order to avoid to let burrs drop in the tubing.
Flare nut
Copper tube
g nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring work)
g work
• Carry out flaring work using dedicated
flaring tool for R-410A as shown below.
Outside diameter
1/4"
3/8"
1/2"
5/8"
3/4"
"A"
1.1~1.3 mm
1.5~1.7 mm
1.6~1.8 mm
1.6~1.8 mm
1.9~2.1 mm
Bar
"A"
Bar
Handle
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Smooth all round
Inside is shining without scratches
= Improper flaring =
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the
flared section and do flaring work again.
Even length
all round
Inclined
SurfaceCrackedUneven
damagedthickness
Installation Manual 27
Connecting Pipes to the Indoor Unit
the piping according to its routing.
Avoid bending and bending back the same
piping point more than three times.(This will
result in hardening the pipe.)
deforming the piping, align centers of
the union fitting of the indoor unit and the
piping, and tighten them firmly with
wrenches.
t pipe to the service valve or ball
valve which is located below the outdoor unit.
completing the piping connection, be
sure to check if there is gas leakage in indoor
and outdoor connection.
Liquid side
Indoor
unit
Outdoor
unit
Flare connection
Gas side
Flare connection
After completing the piping connection,
execute vacuum drying for the connecting
piping and the indoor unit.
The vacuum drying must be carried out
using the service ports of both the liquid and
gas side valves.
CAUTION:Use two wrenches and
tighten with regular torque.'
Outside diameter
mminch
Ø6,351/4
Ø9,523/8
Ø12,71/2
Ø15,885/8
Ø19,053/4
torque
kgf
.
m
1.8~2.5
3.4~4.2
5.5~6.6
6.3~8.2
9.9~12.1
Union
28Air Conditioner
Installation to Decorative Panel
Installation to Decorative Panel
ENGLISH
The decoration panel has its
installation direction.
Before installing the decoration panel,
always remove the paper template.
arily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body.
(Tighten by amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
the air inlet grille from the decoration panel.(Remove the hook for the air inlet grille cord.)
the decoration panel key hole ( ) on the screws fixed in step above, and slide
the panel so that the screws reach the key hole edge.
ten completely two temporarily fixed screws and other two screws.(Total 4 screws)
t the louver motor connector and display connector.
tightening these screws, install the air inlet grille (including the air filter).
Piping side
Air conditioner unit
Control box cover
Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Louver motor
Decoration panel
Display
Lead wire for
louver motor and
display
Decoration panel fixing screws
(Hexagon M5 screw)
Inlet Grille
CAUTION :Install
certainly the
decoration panel.
Cool air leakage
causes sweating.
Water drops fall.
Good exampleBad example
Air conditioner
unit
Ceiling
board
Air
Air conditioner unit
Cool air leakage
(no good)
Ceiling
board
Decoration
panel
Decoration panel
Fit the insulator (this part) and
be careful for cool air leakage
Installation Manual 29
Indoor Unit Drain Piping
CAUTION:Install certainly the decorative panel.
Water drops fall.
Cool air leakage causes sweating.
Good example
Air conditioner
unit
Ceiling
board
Decorative panel
Fit the insulator (this part) and
be careful for cool air leakage
Bad example
Air
Air conditioner unit
Cool air leakage
(no good)
Ceiling
board
Decorative
panel
Indoor Unit Drain Piping
• Drain piping must have down-slope (1/50 to
1/100):be sure not to provide up-and-down
slope to prevent reversal flow.
• During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
• The outside diameter of the drain
connection on the indoor unit is 32mm.
Piping material:Polyvinyl chloride pipe VP-25
and pipe fittings
• Be sure to execute heat insulation on the
drain piping.
• Install the drain raising pipes at a right
angle to the indoor unit and no more than
300mm from the unit.
Pipe clamp
Indoor unit
Upward
routing
not allowed
Maintenance
drain port
300mm or less
1 -1.5m
7
0
0
o
r
l
e
s
s
Drain raising pipe
Clamp metal(attached)Drain hose(attached)
Heat insulation material:Polyethylene foam with thickness more than 8 mm.
Flexible drain hose
Flexible drain hose
30Air Conditioner
Indoor Unit Drain Piping
Drain test
ENGLISH
te type
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior and leave
it provisionally until the test comes to an end.
Flexible drain hose
Feed water
(accessory)
• Feed water to the flexible drain hose and check the
Main
piping for leakage.
drain pipe
• Be sure to check the drain pump for normal
Drain
operating and noise when electrical wiring is
port
Glue the joint
Drain Pump
complete.
Drain hose connection
• When the test is complete, connect the flexible drain
Use the clip (accessory)
hose to the drain port on the indoor unit.
Drain pan
Flexible drain hose
type
1) Remove the Air Filter.
2) Check the drainage.
• Spray one or two glasses of water upon the
evaporator.
• Ensure that water flows drain hose of indoor unit
without any leakage.
Installation Manual 31
Indoor Unit Drain Piping
tible type
the air direction louvers up-and-down to
the position(horizontally) by hand.
To check the drainage.
a glass of water on the evaporator using
a kettle.
the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
Drain piping
drain hose should point downward for
easy drain flow.
Downward slope
not make drain piping like the following.
Do not raise
Accumulated
drain water
Air
Tip of drain hose
dipped in water
Water
leakage
Less than
50mm gap
Water
leakage
Water
leakage
Waving
Ditch
32Air Conditioner
Indoor Unit Drain Piping
Heat insulation
the heat insulation material for the refrigerant piping which has an excellent heat-resistance
(over 120°C).
tions in high humidity
circumstance:
This air conditioner has been tested
according to the "KSStandard Conditions
with Mist" and confirmed that there is not
any r, if it is operated for a
long time in high humid atmosphere (dew
point temperature:more than 23°C), water
drops are liable to this case, add
heat insulation material according to the
following procedure:
• Heat insulation material to
Adiabatic glass wool with thickness 10 to
20mm.
• Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
Fastening band
(accessory)
ENGLISH
Refrigerant piping
Indoor unit
Thermal insulator
(accessory)
Forming the piping
Form the piping by wrapping the
connecting portion of the indoor
unit with insulation material and
secure it with two kinds of vinyl
tape.
• If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the the drain
hose appropriately.
Seal a small opening
around the pipings
with gum type sealer.
Drain hose
Taping
In cases where the outdoor unit is
installed below the indoor unit
perform the following.
the piping, drain hose and connecting
cable from down to up.
the tapped piping along the exterior
wall using saddle or equivalent.
Pipings
Plastic Band
Connecting
cable
Power supply
cord
Trap is required to prevent water from entering
into electrical parts.
Installation Manual 33
Indoor Unit Drain Piping
In cases where the Outdoor unit is
installed above the Indoor unit
perform the following.
the piping and connecting cable from
down to up.
the taped piping along the exterior
a trap to prevent water entering
the room.
the piping onto the wall by saddle or
equivalent.
Seal a small opening
around the pipings
with gum type sealer.
Trap
Settlement of outdoor unit
the outdoor unit with a bolt and
nut[ø10mm(0.39in)] tightly and horizontally on
a concrete or rigid mount.
installing on the wall, roof or rooftop,
anchor the mounting base securely with a
nail or wire assuming the influence of wind
and earthquake.
the vibration of the unit is transmitted to the
hose, secure the unit with an anti-vibration
rubber.
34Air Conditioner
Test running
Test running
ENGLISH
TIONS IN TEST RUNNING
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run,carry out the cooling operation firstly even during heating
heating operation is carried out firstly,it leads to the trouble
of attention must be paid.
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer
button for 3 seconds at the same time.
• To cancel the test run, press any button.
CAUTION
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
• Measuring items are room temperature, outside temperature, suction temperature, blow out
temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and
noise, operating pressure, piping temperature, compressive pressure.
• As to the structure and appearance, check following items.
Is the circulation of air adequate?
Is the draining smooth?
Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated?
Is there any faulty wiring?
Are not terminal screws loosened?
M4......118N
.
cm{12kgf
.
cm}
M6......245N
.
cm{25kgf
.
cm}
M5......196N
.
cm{20kgf
.
cm}
M8......588N
.
cm{60kgf
.
cm}
tion of power supply
t the power supply cord to the independent power supply.
• Circuit breaker is required.
e the unit for fifteen minutes or more.
tion of the performance
e the temperature of the
intake and discharge air.
the difference between the
intake temperature and the discharge
one is more than 8°C (Cooling) or
reversely (Heating).
Thermometer
Installation Manual 35
Test running
CAUTIO
N:After the confirmation of the above conditions,prepare the wiring
as follows:
1) Never fail to have an individual power specialized for the air conditioner.
As for the method of wiring,be guided by the circuit diagram pasted on
the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are
liable to come loose from vibrations to which the unit is subjected
during the course of them and make sure that
they are all tightly fastened.(If they are loose,it could give rise to burn-
out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent
of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources
specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse
breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) Use only 1 remote-controller contained in the Cassette type indoor unit,
when you combine to use both cassette type indoor unit and different
kind of indoor unit.
After setting the ESP value in the Duct Type Indoor Unit,the main
power turns off and then remove the remote controller.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual
(air filter cleaning, temperature control, etc.).
36Air Conditioner
Optional Operation
Optional Operation
ENGLISH
Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
• Position 1:The room temperature is controlled by the thermistor of the main body.
• Position 2:The room themperature is controlled by the thermistor of the wired remote-
controller, control the temperature according to the position of wired remote-
controller.
• Position 3:The room temperature is controlled by lower temperature between the
temperature of main body and of remote-controller sensor.
(3) Move the slide switch to set position.
Room Temp. sensor
Slide switch for 2 Thermistor
Position 2
Position 1
Position 3
REMO
MAIN
2TH
Slide switch for ceiling height
(4) Close the rear cover and check if it works normally.
CAUTIO
N:
• Select the position after counselling with a customer.
• In case of cooling mode,room temperature is controlled by the main body sensor.
• To control the room temperature by a wired remote controller,install controller(room
) to sense the temperature more accurately.
• Manufactured in the position 3.
Installation Manual 37
Optional Operation
ing air volume to the height of ceiling (Cassette type)
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to
supply the comfortable atmosphere to consumers.
Procedure
the selectable position in the table after measuring the height of ceiling.
Ceiling height
more than 3.3m
2.7~3.3m
less than 2.7m
Mode of slide switch
High Ceiling
Standard
Low Ceiling
Change of air volume
Increasing
-
Decreasing
Remark
Manufactured in
standard mode
the case of changing the height as "high" or "low", open the rear cover of the wired remote-
controller.
the slide switch to the set position.
Slide switch for 2 Thermistor
Low ceiling
Standard
(Default)
High Ceiling
Lo
STAND
Hi
Slide switch for ceiling height
the rear cover and check if it works normally.
38Air Conditioner
Optional Operation
3.E.S.P.(External Static Pressure) Setting (Duct type)
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
IWithout Zone System
on V-H, F-H:
• This position sets the maximum E.S.P as a default set.
on V-L:
• This position sets the minimum E.S.P as a default set.
IWith Zone System
on V-H:
• Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
on F-H:
• Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of
dampers.
on V-L:
• Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
* Maximum
Minimum
:24k-6mmAq
:0mmAq
ENGLISH
(3) Move the slide switch to set position.
V-L
F-H
V-H
Slide switch for ceiling height
(4) Close the rear cover and check if it works normally.
• Select the position after checking duct work and E.S.P of the unit.
• Maunfactured in the position F-H.
CAUTIO
N:
Installation Manual 39
Optional Operation
to Set E.S.P?
Procedure of RPM change:
Ex) External Static pressure is 6mmAq for 36k.
• To protect the unit, compressor is designed to be off during g.
1
Push the "On/Off" button.
The unit will start.
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrostHumidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
2
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Timer
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrost
Humidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
3
Push the "Up" of "Down" button for E.S.P adjustment.
And, adjust the number which you want.(In this example, the number is "220".Refer to the
table 1 on the next page.)
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Time
OnOff
Set
01
AUTOHeaterPreheat
JETDefrost
Humidify
FilterOut door
ZONE
1234
17192123
Timer
Operation unit
030507
Program set
09111315
Note:The range of selection is from 1~, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
4
Shift the fan speed mode by pressing the fan speed button.
And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "235" and "243" respectly)
5
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWINGOPERATIONSET TEMP
Room Temp
FAN SPEED
HI
MED
LO
SUB FUNCTION
Timer
OnOff
Set
01
Time
Timer
Operation unit
030507
AUTOHeaterPreheat
JETDefrostHumidify
FilterOut door
ZONE
1234
17192123
Program set
09111315
40Air Conditioner
Optional Operation
[Table.1]
Static Pressure(mmAq)
Model Name
24 k
Step
High
Med
Low
High
30 k
Med
Low
High
36 k
Med
Low
CMM(CFM)
18(636)
16.5(583)
14(494)
26.5(936)
23(812)
20(706)
32(1130)
29(1024)
26.5(936)
220
235
250
153
173
190
230
240
245
205
230
240
150
173
190
230
238
245
190
220
235
150
175
190
225
237
243
50
200
230
148
175
190
220
235
243
02468
Setting Value
1
100
210
130
170
190
150
230
240
1
155
190
1
220
240
10121415
ENGLISH
Note
: sure to set the value refering table cted set value will cause mal-
function.
1 is based at ing to the fluctuation of voltage,air flow rate
varies.
Installation Manual 41
Optional Operation
conditioners should not be installed in areas where corrosive gases, such as acid or alkaline
gas, are produced.
not install the product where it could be exposed to sea wind (salty wind) can
result corrosion on the ion, particularly on the condenser and evaporator fins,
could cause product malfunc-tion or inefficient performance.
outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind
should be l the outdoor unit on the opposite side of the sea wind direction.
Sea windSea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the
sea wind.
Windbreak
• It should be strong enough like concrete
to prevent the sea wind from the sea.
• The height and width should be more
than 150% of the outdoor unit.
Sea wind
• It should be keep more than 70 cm of
space between outdoor unit and the
windbreak for easy air flow.
3) Select a well-drained place.
❈ you can’t meet above guide line in the seaside installation, please contact LG
Electronics for the additional anticorrosion treatment.
ic ( more than once/year ) cleaning of the dust or salt particles stuck on the
heat exchanger by using water
42Air Conditioner