Power Distribution Unit
Front and rear access
Available Options
• Panelboards with 400A panel main breaker
• Additional subfeed breakers
- 225A (50-150kVA)
- 225A/400A (200-300 kVA)
• B
branch CT
ranch circuit monitoring up to 100A per
• Plexiglas see-through doors
• I
provisions
nput and ground compression lug
• Air skirts
• D
check interlock
ual input with manual kirk key or sync
• Lockout breaker tabs
• A
subfeeds
uxiliary and shunt trip main cabinet
• No local Emergency Power Off option
• Field upgradable capabilities
The Eaton line of three-phase power distribution units (PDUs)
provide robust power distribution that can be easily tailored to
meet the design specifications of any facility or data center.
The PDU offers ratings from 50 to 300 kVA and K13 and K20
transformers, including TP-1 efficiency. Energy Management
System (EMS) offers cost effective intelligence to manage
load efficiency.
Easy Service and Setup
Reduce installation time and save on startup costs
• B
technicans for fast reliable service
acked by Eaton's extensive network of over 240 field
• A
subfeed breakers
mple cabling space between panelboards and for
• S
installation options
tandard top and bottom cable access for more flexible
• Front access for operation and general service requirements
• Easily removable side and rear covers with captive hardware
• F
expansion and maintenance
ront access control panel for all standard communication
Monitoring and Connectivity
To understand your power profile
• E
state-of-the-art monitoring and alarming provisions
aton’s Energy Management System (EMS) provides
• P
multiple PDUs together, reducing individual network drops
XGX PDP communication card allows for daisy chaining
to your power equipment
• M
through the integrated web interface, or easily integrate
onitor the PDU from any computer without software
into existing building management systems or Eaton's
Power Xpert Software
• Stores consumption trends for up to 24 months
• Up to 100A branch breaker CTs available
• A
monitoring for subfeed breaker positions
uxiliary contacts to interface with third-party
Safety
Protecting employees, contractors and service personnel
• P
from accidental contact
rotective trim panels cover panelboard bus/breakers/wiring
• S
safer servicing
eparation of Low/High/Control voltage sections for
• UL/CSA approved 60950
• Shunt trip in subfeed breakers
Aesthetics and Flexibility
Providing the right form-factor for demanding applications
• D
facilities and data centers
urable finish gives a clean professional appearance to
• Side car options to expand distribution capacity
TechnicalSpecificaTionS
1
CategoryUp to 150 kVA200-300 kVA
ElECtriCAl ChArACtEristiCs
kVA
50 / 75 / 100 / 125 / 150200 / 225 / 300
input ratings
208 / 380 / 400 / 415 / 480 / 600V - 3 Phase,
3 Wire + Ground (Single & Dual Input)
Dual Input: Basic or Premium
5
Output ratings
208V - 3 Phase, 4 Wire + Ground
Frequency
60 Hz
transformer type
Copper / Double Shielding / Class R (220°C) Insulation
transformer
150°C Temp. Rise / K13 (Std.) & K20 (Opt.) /
Characteristics
Std. & TP-1 Efficiency
transformer
(4) 2 - 1/2% FCBN / (2) 2 - 1/2% FCAN
Compensation taps
Neutral rating
200%
POwEr DistribUtiON
Panelboards
Up to (6) 42-pole Panels - (2) Panels in Main Cabinet &
(4) Panels in Sidecars
2
Panelboard Options
Cutler-Hammer (Bolt-on or Plug-on) or
SquareD Panels (225A & 400A Main Breakers)
Main Cabinet
Up to (8) 225A Frame
4
Up to (12) 225A Frame
2, 4
subfeed breakers
Up to (5) 400A Frame
2
80% or 100%
Up to (3) 600A Frame
2
(CH only) rated
branch breaker
Factory installed branch circuit breaker
3
Additional subfeed
Up to (2) 225A FrameUp to (2) 225A Frame or
breakers
(1) 400A Frame
sidecars
Up to (2) Front or Side Facing Sidecars
sidecar Options
(2) 42-pole Panels or
(4) 225A Frame Subfeeds (each Sidecar)
DiMENsiONs
Main Cabinet
39”W x 35”D x 80”H44”W x 35”D x 80”H
Front Facing sidecar
24”W x 35”D x 80”H
side Facing sidecar
9.5”W x 35”D x 80”H
stANDArDs
NEMA, UL 60950, CSA 60950
1. Due to continuing improvements, specifications are subject to change without notice.
2. Please see sales configurator for additional information.
3. Branch breaker schedule required at time of order.
4. When using optional PRL3 chassis, a maximum of (8) 225A Frame breakers can be installed.
5. Dual Input requires a Right Hand Sidecar.
Aux and Shunt
Eaton Corporation
8609 Six Forks Road
Raleigh, NC 27615
United States
800.356.5794
/powerquality
©2012 Eaton Corporation
All Rights Reserved
Printed in USA
PDU20FXA
January 2012
Options
• Dual Input
5
• Branch Circuit Monitoring
• 100% Rated Sub-Feed breakers
• 100% Rated Panel Main breakers
• Subfeed Breaker Monitoring
• High kAIC main input and
subfeed breakers
• Surge Protection Device
(100 or 200kA) UL1449
• Lightning Arrestor
• Transient Suppression Plate
• Isolated Ground
(Standard)
• Clear Plexiglas Doors
• Load Bank Test Lugs (standard)
• Lockout Breaker Tabs
• Air Skirts
• Floor Stands - seismic
(12", 18", 24", 36" & 48")
• High Voltage Input Junction Box
• Low Voltage Control Junction Box
• Input & Ground Compression Lugs
• Dual Input Basic with Kirk
Key Interlock
• Dual Input Premium with Sync Check
General
• Natural Convection Cooling
• All Swivel Casters
• System Level Metering Included
• 8 x 40 Character LDC Display
• Top & Bottom Entry
• Protective Trim Panels
• Cable management for Input &
Panel Wiring
• (2) X-Slots for Communication
Control
• Local EPO (optional)
• REPO provisions
• Up to 4 Building Alarm Inputs
(N/O or N/C)
Optional custom shutdowns
on alarms:
• Phase rotation/loss
• Ground/Neutral Overcurrent
• transformer Overtemperature
• Output Overload
• input Voltage Out of tolerance
• Frequency Out of tolerance
Single Input Crimp Lug
Energy Management system
Monitored Parameters
• Input voltage (L-L & L-N)
• Output voltage (L-L & L-N)
• Output current (A,B & C Phases)
• Output neutral current
• S ystem ground current
• kVA, kW, Hz
• Monthly, yearly, total output kWH
• Input voltage THD (all phases)
• Output voltage THD (all phases)
• Power factor (lead/lag indicator)
• Output current % (A, B & C phases)
load Profiling
Captures highest and lowest
reading on monthly basis with trend
information over the last 24 months
• Input/Output Voltage
• Output Current
• Input/Output Frequency
• Output Power Factor
• Output kVA
• Input/Output Voltage THD
• Ground and Neutral Current
warnings/Alarms
• Over-temp & shutdown
• Input/Output over- & under-voltage
• Input/Output over- & under-fre-
quency
• Input/Output phase rotation
• Input/Output voltage and current
THD
• Output Overload (3 Levels)
• Remote EPO
• Building Alarms (4 programmable)
• Summary Alarm
• Communication Fault
Connectivity
• Modbus RTU (RS232/485)
• Power Xpert Gateway Card -
PXGX PDP (Modbus TCP/IP,
SNMP, Ethernet)
EPO or No EPO Option
Eaton, Cutler-Hammer, Power Xpert
and X-Slot are registered trademarks
of Eaton Corporation.
All other trademarks are property of
their respective owners.
2024年10月6日发(作者:陈其雨)
Power Distribution Unit
Front and rear access
Available Options
• Panelboards with 400A panel main breaker
• Additional subfeed breakers
- 225A (50-150kVA)
- 225A/400A (200-300 kVA)
• B
branch CT
ranch circuit monitoring up to 100A per
• Plexiglas see-through doors
• I
provisions
nput and ground compression lug
• Air skirts
• D
check interlock
ual input with manual kirk key or sync
• Lockout breaker tabs
• A
subfeeds
uxiliary and shunt trip main cabinet
• No local Emergency Power Off option
• Field upgradable capabilities
The Eaton line of three-phase power distribution units (PDUs)
provide robust power distribution that can be easily tailored to
meet the design specifications of any facility or data center.
The PDU offers ratings from 50 to 300 kVA and K13 and K20
transformers, including TP-1 efficiency. Energy Management
System (EMS) offers cost effective intelligence to manage
load efficiency.
Easy Service and Setup
Reduce installation time and save on startup costs
• B
technicans for fast reliable service
acked by Eaton's extensive network of over 240 field
• A
subfeed breakers
mple cabling space between panelboards and for
• S
installation options
tandard top and bottom cable access for more flexible
• Front access for operation and general service requirements
• Easily removable side and rear covers with captive hardware
• F
expansion and maintenance
ront access control panel for all standard communication
Monitoring and Connectivity
To understand your power profile
• E
state-of-the-art monitoring and alarming provisions
aton’s Energy Management System (EMS) provides
• P
multiple PDUs together, reducing individual network drops
XGX PDP communication card allows for daisy chaining
to your power equipment
• M
through the integrated web interface, or easily integrate
onitor the PDU from any computer without software
into existing building management systems or Eaton's
Power Xpert Software
• Stores consumption trends for up to 24 months
• Up to 100A branch breaker CTs available
• A
monitoring for subfeed breaker positions
uxiliary contacts to interface with third-party
Safety
Protecting employees, contractors and service personnel
• P
from accidental contact
rotective trim panels cover panelboard bus/breakers/wiring
• S
safer servicing
eparation of Low/High/Control voltage sections for
• UL/CSA approved 60950
• Shunt trip in subfeed breakers
Aesthetics and Flexibility
Providing the right form-factor for demanding applications
• D
facilities and data centers
urable finish gives a clean professional appearance to
• Side car options to expand distribution capacity
TechnicalSpecificaTionS
1
CategoryUp to 150 kVA200-300 kVA
ElECtriCAl ChArACtEristiCs
kVA
50 / 75 / 100 / 125 / 150200 / 225 / 300
input ratings
208 / 380 / 400 / 415 / 480 / 600V - 3 Phase,
3 Wire + Ground (Single & Dual Input)
Dual Input: Basic or Premium
5
Output ratings
208V - 3 Phase, 4 Wire + Ground
Frequency
60 Hz
transformer type
Copper / Double Shielding / Class R (220°C) Insulation
transformer
150°C Temp. Rise / K13 (Std.) & K20 (Opt.) /
Characteristics
Std. & TP-1 Efficiency
transformer
(4) 2 - 1/2% FCBN / (2) 2 - 1/2% FCAN
Compensation taps
Neutral rating
200%
POwEr DistribUtiON
Panelboards
Up to (6) 42-pole Panels - (2) Panels in Main Cabinet &
(4) Panels in Sidecars
2
Panelboard Options
Cutler-Hammer (Bolt-on or Plug-on) or
SquareD Panels (225A & 400A Main Breakers)
Main Cabinet
Up to (8) 225A Frame
4
Up to (12) 225A Frame
2, 4
subfeed breakers
Up to (5) 400A Frame
2
80% or 100%
Up to (3) 600A Frame
2
(CH only) rated
branch breaker
Factory installed branch circuit breaker
3
Additional subfeed
Up to (2) 225A FrameUp to (2) 225A Frame or
breakers
(1) 400A Frame
sidecars
Up to (2) Front or Side Facing Sidecars
sidecar Options
(2) 42-pole Panels or
(4) 225A Frame Subfeeds (each Sidecar)
DiMENsiONs
Main Cabinet
39”W x 35”D x 80”H44”W x 35”D x 80”H
Front Facing sidecar
24”W x 35”D x 80”H
side Facing sidecar
9.5”W x 35”D x 80”H
stANDArDs
NEMA, UL 60950, CSA 60950
1. Due to continuing improvements, specifications are subject to change without notice.
2. Please see sales configurator for additional information.
3. Branch breaker schedule required at time of order.
4. When using optional PRL3 chassis, a maximum of (8) 225A Frame breakers can be installed.
5. Dual Input requires a Right Hand Sidecar.
Aux and Shunt
Eaton Corporation
8609 Six Forks Road
Raleigh, NC 27615
United States
800.356.5794
/powerquality
©2012 Eaton Corporation
All Rights Reserved
Printed in USA
PDU20FXA
January 2012
Options
• Dual Input
5
• Branch Circuit Monitoring
• 100% Rated Sub-Feed breakers
• 100% Rated Panel Main breakers
• Subfeed Breaker Monitoring
• High kAIC main input and
subfeed breakers
• Surge Protection Device
(100 or 200kA) UL1449
• Lightning Arrestor
• Transient Suppression Plate
• Isolated Ground
(Standard)
• Clear Plexiglas Doors
• Load Bank Test Lugs (standard)
• Lockout Breaker Tabs
• Air Skirts
• Floor Stands - seismic
(12", 18", 24", 36" & 48")
• High Voltage Input Junction Box
• Low Voltage Control Junction Box
• Input & Ground Compression Lugs
• Dual Input Basic with Kirk
Key Interlock
• Dual Input Premium with Sync Check
General
• Natural Convection Cooling
• All Swivel Casters
• System Level Metering Included
• 8 x 40 Character LDC Display
• Top & Bottom Entry
• Protective Trim Panels
• Cable management for Input &
Panel Wiring
• (2) X-Slots for Communication
Control
• Local EPO (optional)
• REPO provisions
• Up to 4 Building Alarm Inputs
(N/O or N/C)
Optional custom shutdowns
on alarms:
• Phase rotation/loss
• Ground/Neutral Overcurrent
• transformer Overtemperature
• Output Overload
• input Voltage Out of tolerance
• Frequency Out of tolerance
Single Input Crimp Lug
Energy Management system
Monitored Parameters
• Input voltage (L-L & L-N)
• Output voltage (L-L & L-N)
• Output current (A,B & C Phases)
• Output neutral current
• S ystem ground current
• kVA, kW, Hz
• Monthly, yearly, total output kWH
• Input voltage THD (all phases)
• Output voltage THD (all phases)
• Power factor (lead/lag indicator)
• Output current % (A, B & C phases)
load Profiling
Captures highest and lowest
reading on monthly basis with trend
information over the last 24 months
• Input/Output Voltage
• Output Current
• Input/Output Frequency
• Output Power Factor
• Output kVA
• Input/Output Voltage THD
• Ground and Neutral Current
warnings/Alarms
• Over-temp & shutdown
• Input/Output over- & under-voltage
• Input/Output over- & under-fre-
quency
• Input/Output phase rotation
• Input/Output voltage and current
THD
• Output Overload (3 Levels)
• Remote EPO
• Building Alarms (4 programmable)
• Summary Alarm
• Communication Fault
Connectivity
• Modbus RTU (RS232/485)
• Power Xpert Gateway Card -
PXGX PDP (Modbus TCP/IP,
SNMP, Ethernet)
EPO or No EPO Option
Eaton, Cutler-Hammer, Power Xpert
and X-Slot are registered trademarks
of Eaton Corporation.
All other trademarks are property of
their respective owners.