OPERATING MANUAL
Blemo –Frequency converter ER50 with
PID-Application
KAUFMANN UMWELTTECHNIK 79664 Wehr Tel. 07762/3013 + 3210 + 7088-0 Fax 07762/3632
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
Index
1. General information for performance control by frequency converter
2. Control Keypad and drive status indications
2.1
Controls/Display overview
2.2 Output mode
2.3 Status information
2.3.1 Top
2.3.2 Middle
2.3.3 Bottom
3. Control panel operating
3.1 Mode arts
4. Manual adjustment of ozone production
4.1 Adjustment of automatic controlled ozone production
4.2 Controller settings
4.2.1 Parameter setting of PID controller
5. Fault listing
6. Ratings
2
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
1.
General information for performance control by frequency converter
The frequency converter is applied for control of performance of the high-tension
transformer and resulting from this of the ozone production.
The desired set-point (Hz) must be adjusted at the control panel.
Operating data, for instance temperature, current etc. are indicated on the display.
The frequency converter is adapted to the high-tension transformer by configuration of
several parameters. These parameters may be changed only after contacting Kaufmann
Umwelttechnik, because parameter changes may cause damages with high-tension
transformer or frequency converter.
Following is the general description of frequency converter operation.
Warning ! Dangerous voltage is present when input power is connected.
After
disconnecting the supply, wait at least 5 minutes (to let the intermediate
circuit
capacitors discharge) before removing the cover
2
. Control Keypad and drive status indications
The ER50 Assistant Control Panel features a alphanumeric control panel with a LCD
display.
Use a control panel to control the ER50, to read status data and adjust parameters.
The Assistant Control panel includes pre-programmed assistants to autmate the most
commonparameter setups.
Assistant Control Panel
3
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
2.1
Controls/Display Overview
2.2
Output Mode
Use the Output mode to read information on the drive’s status and to operate
the drive. To reach the Output mode, press EXIT until the LCD display shows
status information as described below
4
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
2.3
Status information
2.3.1
Top
The top line of the LCD display shows the basic status information of the drive.
Ø LOC – indicates that the drive control is local, that is, from the control
panel.
Ø REM - indicates that the drive control is remote, such as the basic I/O (X1)
or fieldbus.
Ø - indicates the drive and motor rotation status as follows:
• Rotating arrow clockwise - Drive is running and at setpoint.
• Rotating dotted blinking arrow Drive is running but not at setpoint.
• Stationary dotted arrow - Start command is present, but motor is not
running.
Ø Upper right – shows the active reference.
2.3.2
Middle
Using parameter Group 34, the middle of the LCD display can be configured to
display:
Up to three parameter values.
• Frequency
• Current
• Actual value
Use parameters 3401, 3408, and 3415 to select the parameters (from Group 01)
to display.
A bar graph rather than any of the parameter values. Enable bar
graph displays using parameters 3404, 3411 and 3418.
2.3.3
Bottom
Ø Lower corners – show the functions currently assigned to the two soft keys.
Ø Lower middle – displays the current time (if configured to show the time).
5
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
3. Control panel operating
From output mode to menue mode press function button 2 „Menü To select
required su –menue press scroll buttons up or down and confirm by pressing
function button 2 „Select“.
3.1 Mode arts
Ø Parameter
Use the Parameters mode to view and edit parameter values
Ø Start-up Assistant
The Start-up Assistant is divided into tasks. You may activate the tasks one after
the other, as the Start-up Assistant suggests, or independently. (You are not
required to use the assistant, you may use instead, the parameter mode to set
the drive parameters.)
Ø Changed Parameters Mode
Use the Changed Parameters mode to view (and edit) a listing of all parameters
that have been changed from macro default values.
Ø Par Backup Mode
The Assistant Control Panel can store a full set of drive parameters.
The Control
Panel memory is non-volatile and does not depend on the panel’s battery.
Ø Clock Set Mode
Use the Clock Set mode to:
• Enable/disable the clock function
• Set date and time.
• Select display format.
Ø
I/O Settings Mode
Use the I/O Setting mode to check (and edit) the setting at any I/O terminal.
6
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
4.
Manual adjustment of ozone production
Switch position:
• Switch Control to „1“
• Switch Ozone generator to „Auto“
• Switch Ozone production to „Manu“
Setting at control panel of frequency converter as following:
Setting of frequency when ozone generator in operation by means of pressing
scroll button “up” or “Down”.
Possible faults:
• Drive is stopped, marking arrow of drive-direction is local.
Ursache: Ozone generator is OFF
In automaticmode (switch ozone generator; position „Auto“ external
starting contact is not closed).
• Operating mode is in position „LOC“ .
Measure: Push button LOC/REM until display shows „REM“.
• Switch Ozone production in position „Auto“
Adjustment of automatic controlled ozone production
Switch position:
• Switch Control to „1“
• Switch Ozone generator to „Auto“
• Switch Ozone production to „Auto“
Ozone production automatically dependent on input signal from external measuring
device for disssolved ozone or ORP (0/4-20mA)
Possible faults:
• Drive is stopped, marking arrow of drive-direction is local.
Ursache: Ozone generator is OFF
In automaticmode (switch ozone generator; position „Auto“ external
starting contact is not closed).
• Operating mode is in position „LOC“ .
Measure: Push button LOC/REM until display shows „REM“.
• Switch Ozone production in position „Manu“
7
4.1
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
4.2 Controller settings:
The control caracteristics of PID controller, which is integrated in frequency converter
must be adapted to the corresponding control circuit. Rarameter setting as following:
4.2.1 Parameter setting of PID controller
To go to menue mode from output mode press menue button 2
„Menue“ Select menue “Parameter” by pressing scroll buttons and confirm by
pressing menue button 2
„Enter“. Further select menue point 40 “Process PID1” by means of scroll
buttons and confirm by pressing menue button 2 “Sel”
Now all control parameters can be edited by means of scroll buttons. Confirm
parameter selection by pressing menue button 2 „Edit“ Parameter setting by
means of scroll buttons and confirmation by pressing menue button 2 “Save”.
To go back to the output mode press several times menue button 1 “Exit”.
Parameter 4001 P-gain Setting range 0,1-100
%
Parameter 4002 I- Integratiotime Setting range
0,1- 3600,0 Sec.
Parameter 4003 D- Differencial time Setting
range 0,1- 10,0 Sec.
Parameter 4011 Internal set point zB.: 50%.
8
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
5.
Fault listing
Fault Name In
Panel
OVERCURRENT
Description and Recommended Corrective Action
Output current is excessive. Check for and correct
• Excessive motor load
• Insufficient acceleration time (parameters 2202
ACCELER TIME 1 and 2205 ACCELER TIME 2)
• Faulty motor, motor cables or connections
Intermediate circuit DC voltage is excessive. Check for and
correct
• Static or transient overvoltages in the input power
supply.
• Insufficient deceleration time (parameters 2203
DECELER TIME 1 and 2206 DECELER TIME 2)
• Undersized brake chopper (if present).•Verify that
overvoltage controller is ON (using parameter
2005).
Drive heatsink is overheated. Temperature is at or above
limit.R1…R4 & R7/R8: 115°C (239 °F)R5/R6: 125°C (257
°F) Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature
• Excessive motor load.
Fault current. Check for and correct:
• A short-circuit in the motor cable(s) or motor.
• Supply disturbances.
Not used.
Intermediate circuit DC voltage is not sufficient. Check for
and correct:
• Missing phase in the input power supply.•Blown
fuse.
• Undervoltage on mains
Analog input 1 loss. Analog input value is less than
AI1FLT LIMIT (3021). Check for and correct.
• Source and connection for analog input.
• Parameter settings for AI1FLT LIMIT (3021) and
3001AI Analog input 2 loss. Analog input value is less than AI2FLT LIMIT (3022). Check for and correct: • Source and connection for analog input. • Parameter settings for AI2FLT LIMIT (3022) and 3001AI Motor is too hot, based on either the drive’s estimate or on temperature feedback. • Check for overloaded motor. • Adjust the parameters used for the estimate (3005…3009). • Check the temperature sensors and Group 35 parameters. Panel communication is lost and either: • Drive is in local control mode (the control panel displays LOC), or • Drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. To correct check: • Communication lines and connections • Parameter 3002 PANEL COMM ERROR. • Parameters in Group 10: Command Inputs and Group 11: Reference Select (if drive operation is REM). Fault Code 1 DC OVERVOLT 2 DEV OVERTEMP 3 4 5 6 SHORT CIRC RESERVED DC UNDERVOLT AI1 LOSS 7 AI2 LOSS 8 MOT TEMP 9 PANEL LOSS 10 9 Kaufmann Umwelttechnik Blemo frequency converter PID-Application ID RUN FAIL 11 MOTOR STALL 12 13 14 15 RESERVED EXTERNAL FLT 1 EXTERNAL FLT 2 EARTH FAULT The motor ID Run was not completed successfully. Check for and correct: • Motor connections • Motor parameters 9905…9909 Motor or process stall. Motor is operating in the stall region. Check for and correct: • Excessive load. • Insufficient motor power. • Parameters 3010…3012. Not used Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1. Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT 2. Possible ground fault detected in the motor or motor cables. The drive monitors for ground faults while the drive is running and while the drive is not running. Detection is more sensitive when the drive is not running and can produce false le corrections: • Check for/correct faults in the input wiring. • Verify that motor cable does not exceed maximum specified length. • A delta grounded input power supply and motor cables with high capacitance may result in erroneous error reports during non-running tests. To disable response to fault monitoring when the drive is not running, use parameter 3023 WIRING FAULT. To disable response to all ground fault monitoring, use parameter 3017 EARTH FAULT. Motor load is lower than expected. Check for and correct: • Disconnected load. • Parameters 3013 UNDERLOAD FUNCTION…3015 UNDERLOAD CURVE. Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Contact your local ABB sales representative. Internal fault. A communication-related problem has been detected on the fiber optic link between the OITF and OINT boards. Contact your local ABB sales representative. Internal fault. Low voltage condition detected on OINT power supply. Contact your local ABB sales representative. nternal fault. Current measurement is out of range. Contact your local ABB sales representative. Ripple voltage in the DC link is too high. Check for and correct: • Missing mains phase. • Blown fuse. Nicht verwendet Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED. Check for and correct: • Parameter settings for 2001 and 2002. • Adequacy of motor braking torque. • Applicability of torque control. • Brake chopper and resistor.. • Brems-Chopper und Wiederstand Nicht verwendet Internal fault. Configuration Block Drive ID is not valid. Contact your local ABB sales representative. Internal configuration file has an error. Contact your local ABB sales representative. 16 UNDERLOAD 17 18 19 20 21 22 23 RESERVED OVERSPEED OPEX PWR CURR MEAS SUPPLY PHASE THERM FAIL OPEX LINK 24 25 26 27 RESERVED DRIVE ID CONFIG FILE 10 Kaufmann Umwelttechnik Blemo frequency converter PID-Application SERIAL 1 ERR 28 29 30 31 32 33 34 EFB CONFIG FILE FORCE TRIP EFB 1 EFB 2 EFB 3 MOTOR PHASE Fieldbus communication has timed out. Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line.. Error in reading the configuration file for the embedded fieldbus. Fault trip forced by the fieldbus. See the fieldbus User’s Manual. Fault code reserved for the embedded fieldbus (EFB) protocol application. The meaning is protocol dependent. OUTPUT WIRING 35 101 102 103 104 105 201 202 203 204 205 206 SERF CORRUPT SERF IITFILE SERF MACRO SERF EFBPROT SERF BPFILE DSP T1 OVERLOAD DSP T1 OVERLOAD DSP T1 OVERLOAD DSP STACK ERROR DSP REV ERROR OMIO ID ERROR PAR HZRPM Fault in the motor circuit. One of the motor phases is lost. Check for and correct:^ • Motor fault. • Motor cable fault. • Thermal relay fault (if used). • Internal fault Possible power wiring error detected. When the drive is not running it monitors for an improper connection between the drive input power and the drive output. Check for and correct: • Proper input wiring – line voltage is NOT connected to drive output. • The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT. Error internal to the drive. Contact your local ABB sales representative and report the error number. Error internal to the drive. Contact your local ABB sales representative and report the error number. 1000 PAR PFCREFNG 1001 Parameter values are inconsistent. Check for any of the following: • 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED. • 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ. • 2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (>50) • 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (>50) • 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (>50) • 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (>50) Parameter values are inconsistent. Check for the following. • 2007 MINIMUM FREQ is negative, when 8123 PFC ENABLE is active. 11 Kaufmann Umwelttechnik Blemo frequency converter PID-Application PAR AI SCALE 1003 PAR AO SCALE 1004 PAR PCU 2 1005 1006 PAR EXTROMISSING 1007 1008 PAR FBUSMISSING PAR PFCWOSCALAR PAR PCU1 1009 Parameter values are inconsistent. Check for any of the following: • 1301 AI 1 MIN > 1302 AI 1 MAX. • 1304 AI 2 MIN > 1305 AI 2 MAX. Parameter values are inconsistent. Check for any of the following: • 504 AO 1 MIN > 1505 AO 1 MAX • 1510 AO 2 MIN > 1511 AO 2 MAX. Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check for the following: • 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 3.0 • Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW)or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g. in US) Parameter values are inconsistent. Check for the following: • Extension relay module not connected and • 1410…1412 RELAY OUTPUTS 4…6 have non- zero values. Parameter values are inconsistent. Check for and correct: • A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0. Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3 (SCALAR: SPEED), when 8123 PFC ENABLE is activated. Parameter values for power control are inconsistent: Improper motor nominal frequency or speed. Check for both of the following: • 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16 • 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor Poles) < 0.992 6. Ratings By type code, the table below provides ratings for the ACS550 Type code Normal Use Heavy-Duty Use ER50- I2 N P N P N I2 hd P hd P hd A kW HP A kW HP Three-phase supply voltage, 380…480 V 0,75/4K/4G 1,1/4K/4G 1,5/4K/4G 2,2/4K/4G 3,0/4K/4G 4,0/4K/4G 5,5/4K/4G 7,5/4K/4G 11,0/4K/4G 15,0/4K/4G 18,5/4K/4G 22,0/4K/4G 30,0/4K/4G 37,0/4K/4G 45,0/4K/4G 55,0/4K/4G 75,0/4K/4G 3,3 4,1 5,4 6,9 8,8 11,9 15,4 23 31 38 44 59 72 96 124 157 180 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 90 1,5 2 3 5 7,5 10 15 20 25 30 40 50 75 100 125 150 2,4 3,3 4,1 5,4 6,9 8,8 11,9 15,4 23 31 38 44 59 77 96 124 156 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 1 1,5 2 3 5 7,5 10 15 20 25 30 40 60 75 100 125 Frame Size R1 R1 R1 R1 R1 R1 R2 R2 R3 R3 R4 R4 R4 R5 R6 R6 R6 12
2024年8月30日发(作者:蒋幻丝)
Appendix A
OPERATING MANUAL
Blemo –Frequency converter ER50 with
PID-Application
KAUFMANN UMWELTTECHNIK 79664 Wehr Tel. 07762/3013 + 3210 + 7088-0 Fax 07762/3632
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
Index
1. General information for performance control by frequency converter
2. Control Keypad and drive status indications
2.1
Controls/Display overview
2.2 Output mode
2.3 Status information
2.3.1 Top
2.3.2 Middle
2.3.3 Bottom
3. Control panel operating
3.1 Mode arts
4. Manual adjustment of ozone production
4.1 Adjustment of automatic controlled ozone production
4.2 Controller settings
4.2.1 Parameter setting of PID controller
5. Fault listing
6. Ratings
2
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
1.
General information for performance control by frequency converter
The frequency converter is applied for control of performance of the high-tension
transformer and resulting from this of the ozone production.
The desired set-point (Hz) must be adjusted at the control panel.
Operating data, for instance temperature, current etc. are indicated on the display.
The frequency converter is adapted to the high-tension transformer by configuration of
several parameters. These parameters may be changed only after contacting Kaufmann
Umwelttechnik, because parameter changes may cause damages with high-tension
transformer or frequency converter.
Following is the general description of frequency converter operation.
Warning ! Dangerous voltage is present when input power is connected.
After
disconnecting the supply, wait at least 5 minutes (to let the intermediate
circuit
capacitors discharge) before removing the cover
2
. Control Keypad and drive status indications
The ER50 Assistant Control Panel features a alphanumeric control panel with a LCD
display.
Use a control panel to control the ER50, to read status data and adjust parameters.
The Assistant Control panel includes pre-programmed assistants to autmate the most
commonparameter setups.
Assistant Control Panel
3
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
2.1
Controls/Display Overview
2.2
Output Mode
Use the Output mode to read information on the drive’s status and to operate
the drive. To reach the Output mode, press EXIT until the LCD display shows
status information as described below
4
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
2.3
Status information
2.3.1
Top
The top line of the LCD display shows the basic status information of the drive.
Ø LOC – indicates that the drive control is local, that is, from the control
panel.
Ø REM - indicates that the drive control is remote, such as the basic I/O (X1)
or fieldbus.
Ø - indicates the drive and motor rotation status as follows:
• Rotating arrow clockwise - Drive is running and at setpoint.
• Rotating dotted blinking arrow Drive is running but not at setpoint.
• Stationary dotted arrow - Start command is present, but motor is not
running.
Ø Upper right – shows the active reference.
2.3.2
Middle
Using parameter Group 34, the middle of the LCD display can be configured to
display:
Up to three parameter values.
• Frequency
• Current
• Actual value
Use parameters 3401, 3408, and 3415 to select the parameters (from Group 01)
to display.
A bar graph rather than any of the parameter values. Enable bar
graph displays using parameters 3404, 3411 and 3418.
2.3.3
Bottom
Ø Lower corners – show the functions currently assigned to the two soft keys.
Ø Lower middle – displays the current time (if configured to show the time).
5
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
3. Control panel operating
From output mode to menue mode press function button 2 „Menü To select
required su –menue press scroll buttons up or down and confirm by pressing
function button 2 „Select“.
3.1 Mode arts
Ø Parameter
Use the Parameters mode to view and edit parameter values
Ø Start-up Assistant
The Start-up Assistant is divided into tasks. You may activate the tasks one after
the other, as the Start-up Assistant suggests, or independently. (You are not
required to use the assistant, you may use instead, the parameter mode to set
the drive parameters.)
Ø Changed Parameters Mode
Use the Changed Parameters mode to view (and edit) a listing of all parameters
that have been changed from macro default values.
Ø Par Backup Mode
The Assistant Control Panel can store a full set of drive parameters.
The Control
Panel memory is non-volatile and does not depend on the panel’s battery.
Ø Clock Set Mode
Use the Clock Set mode to:
• Enable/disable the clock function
• Set date and time.
• Select display format.
Ø
I/O Settings Mode
Use the I/O Setting mode to check (and edit) the setting at any I/O terminal.
6
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
4.
Manual adjustment of ozone production
Switch position:
• Switch Control to „1“
• Switch Ozone generator to „Auto“
• Switch Ozone production to „Manu“
Setting at control panel of frequency converter as following:
Setting of frequency when ozone generator in operation by means of pressing
scroll button “up” or “Down”.
Possible faults:
• Drive is stopped, marking arrow of drive-direction is local.
Ursache: Ozone generator is OFF
In automaticmode (switch ozone generator; position „Auto“ external
starting contact is not closed).
• Operating mode is in position „LOC“ .
Measure: Push button LOC/REM until display shows „REM“.
• Switch Ozone production in position „Auto“
Adjustment of automatic controlled ozone production
Switch position:
• Switch Control to „1“
• Switch Ozone generator to „Auto“
• Switch Ozone production to „Auto“
Ozone production automatically dependent on input signal from external measuring
device for disssolved ozone or ORP (0/4-20mA)
Possible faults:
• Drive is stopped, marking arrow of drive-direction is local.
Ursache: Ozone generator is OFF
In automaticmode (switch ozone generator; position „Auto“ external
starting contact is not closed).
• Operating mode is in position „LOC“ .
Measure: Push button LOC/REM until display shows „REM“.
• Switch Ozone production in position „Manu“
7
4.1
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
4.2 Controller settings:
The control caracteristics of PID controller, which is integrated in frequency converter
must be adapted to the corresponding control circuit. Rarameter setting as following:
4.2.1 Parameter setting of PID controller
To go to menue mode from output mode press menue button 2
„Menue“ Select menue “Parameter” by pressing scroll buttons and confirm by
pressing menue button 2
„Enter“. Further select menue point 40 “Process PID1” by means of scroll
buttons and confirm by pressing menue button 2 “Sel”
Now all control parameters can be edited by means of scroll buttons. Confirm
parameter selection by pressing menue button 2 „Edit“ Parameter setting by
means of scroll buttons and confirmation by pressing menue button 2 “Save”.
To go back to the output mode press several times menue button 1 “Exit”.
Parameter 4001 P-gain Setting range 0,1-100
%
Parameter 4002 I- Integratiotime Setting range
0,1- 3600,0 Sec.
Parameter 4003 D- Differencial time Setting
range 0,1- 10,0 Sec.
Parameter 4011 Internal set point zB.: 50%.
8
Kaufmann Umwelttechnik Blemo frequency converter PID-Application
5.
Fault listing
Fault Name In
Panel
OVERCURRENT
Description and Recommended Corrective Action
Output current is excessive. Check for and correct
• Excessive motor load
• Insufficient acceleration time (parameters 2202
ACCELER TIME 1 and 2205 ACCELER TIME 2)
• Faulty motor, motor cables or connections
Intermediate circuit DC voltage is excessive. Check for and
correct
• Static or transient overvoltages in the input power
supply.
• Insufficient deceleration time (parameters 2203
DECELER TIME 1 and 2206 DECELER TIME 2)
• Undersized brake chopper (if present).•Verify that
overvoltage controller is ON (using parameter
2005).
Drive heatsink is overheated. Temperature is at or above
limit.R1…R4 & R7/R8: 115°C (239 °F)R5/R6: 125°C (257
°F) Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature
• Excessive motor load.
Fault current. Check for and correct:
• A short-circuit in the motor cable(s) or motor.
• Supply disturbances.
Not used.
Intermediate circuit DC voltage is not sufficient. Check for
and correct:
• Missing phase in the input power supply.•Blown
fuse.
• Undervoltage on mains
Analog input 1 loss. Analog input value is less than
AI1FLT LIMIT (3021). Check for and correct.
• Source and connection for analog input.
• Parameter settings for AI1FLT LIMIT (3021) and
3001AI Analog input 2 loss. Analog input value is less than AI2FLT LIMIT (3022). Check for and correct: • Source and connection for analog input. • Parameter settings for AI2FLT LIMIT (3022) and 3001AI Motor is too hot, based on either the drive’s estimate or on temperature feedback. • Check for overloaded motor. • Adjust the parameters used for the estimate (3005…3009). • Check the temperature sensors and Group 35 parameters. Panel communication is lost and either: • Drive is in local control mode (the control panel displays LOC), or • Drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. To correct check: • Communication lines and connections • Parameter 3002 PANEL COMM ERROR. • Parameters in Group 10: Command Inputs and Group 11: Reference Select (if drive operation is REM). Fault Code 1 DC OVERVOLT 2 DEV OVERTEMP 3 4 5 6 SHORT CIRC RESERVED DC UNDERVOLT AI1 LOSS 7 AI2 LOSS 8 MOT TEMP 9 PANEL LOSS 10 9 Kaufmann Umwelttechnik Blemo frequency converter PID-Application ID RUN FAIL 11 MOTOR STALL 12 13 14 15 RESERVED EXTERNAL FLT 1 EXTERNAL FLT 2 EARTH FAULT The motor ID Run was not completed successfully. Check for and correct: • Motor connections • Motor parameters 9905…9909 Motor or process stall. Motor is operating in the stall region. Check for and correct: • Excessive load. • Insufficient motor power. • Parameters 3010…3012. Not used Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1. Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT 2. Possible ground fault detected in the motor or motor cables. The drive monitors for ground faults while the drive is running and while the drive is not running. Detection is more sensitive when the drive is not running and can produce false le corrections: • Check for/correct faults in the input wiring. • Verify that motor cable does not exceed maximum specified length. • A delta grounded input power supply and motor cables with high capacitance may result in erroneous error reports during non-running tests. To disable response to fault monitoring when the drive is not running, use parameter 3023 WIRING FAULT. To disable response to all ground fault monitoring, use parameter 3017 EARTH FAULT. Motor load is lower than expected. Check for and correct: • Disconnected load. • Parameters 3013 UNDERLOAD FUNCTION…3015 UNDERLOAD CURVE. Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Contact your local ABB sales representative. Internal fault. A communication-related problem has been detected on the fiber optic link between the OITF and OINT boards. Contact your local ABB sales representative. Internal fault. Low voltage condition detected on OINT power supply. Contact your local ABB sales representative. nternal fault. Current measurement is out of range. Contact your local ABB sales representative. Ripple voltage in the DC link is too high. Check for and correct: • Missing mains phase. • Blown fuse. Nicht verwendet Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED. Check for and correct: • Parameter settings for 2001 and 2002. • Adequacy of motor braking torque. • Applicability of torque control. • Brake chopper and resistor.. • Brems-Chopper und Wiederstand Nicht verwendet Internal fault. Configuration Block Drive ID is not valid. Contact your local ABB sales representative. Internal configuration file has an error. Contact your local ABB sales representative. 16 UNDERLOAD 17 18 19 20 21 22 23 RESERVED OVERSPEED OPEX PWR CURR MEAS SUPPLY PHASE THERM FAIL OPEX LINK 24 25 26 27 RESERVED DRIVE ID CONFIG FILE 10 Kaufmann Umwelttechnik Blemo frequency converter PID-Application SERIAL 1 ERR 28 29 30 31 32 33 34 EFB CONFIG FILE FORCE TRIP EFB 1 EFB 2 EFB 3 MOTOR PHASE Fieldbus communication has timed out. Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line.. Error in reading the configuration file for the embedded fieldbus. Fault trip forced by the fieldbus. See the fieldbus User’s Manual. Fault code reserved for the embedded fieldbus (EFB) protocol application. The meaning is protocol dependent. OUTPUT WIRING 35 101 102 103 104 105 201 202 203 204 205 206 SERF CORRUPT SERF IITFILE SERF MACRO SERF EFBPROT SERF BPFILE DSP T1 OVERLOAD DSP T1 OVERLOAD DSP T1 OVERLOAD DSP STACK ERROR DSP REV ERROR OMIO ID ERROR PAR HZRPM Fault in the motor circuit. One of the motor phases is lost. Check for and correct:^ • Motor fault. • Motor cable fault. • Thermal relay fault (if used). • Internal fault Possible power wiring error detected. When the drive is not running it monitors for an improper connection between the drive input power and the drive output. Check for and correct: • Proper input wiring – line voltage is NOT connected to drive output. • The fault can be erroneously declared if the input power is a delta grounded system and motor cable capacitance is large. This fault can be disabled using parameter 3023 WIRING FAULT. Error internal to the drive. Contact your local ABB sales representative and report the error number. Error internal to the drive. Contact your local ABB sales representative and report the error number. 1000 PAR PFCREFNG 1001 Parameter values are inconsistent. Check for any of the following: • 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED. • 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ. • 2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (>50) • 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (>50) • 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (>50) • 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (>50) Parameter values are inconsistent. Check for the following. • 2007 MINIMUM FREQ is negative, when 8123 PFC ENABLE is active. 11 Kaufmann Umwelttechnik Blemo frequency converter PID-Application PAR AI SCALE 1003 PAR AO SCALE 1004 PAR PCU 2 1005 1006 PAR EXTROMISSING 1007 1008 PAR FBUSMISSING PAR PFCWOSCALAR PAR PCU1 1009 Parameter values are inconsistent. Check for any of the following: • 1301 AI 1 MIN > 1302 AI 1 MAX. • 1304 AI 2 MIN > 1305 AI 2 MAX. Parameter values are inconsistent. Check for any of the following: • 504 AO 1 MIN > 1505 AO 1 MAX • 1510 AO 2 MIN > 1511 AO 2 MAX. Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check for the following: • 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 3.0 • Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW)or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g. in US) Parameter values are inconsistent. Check for the following: • Extension relay module not connected and • 1410…1412 RELAY OUTPUTS 4…6 have non- zero values. Parameter values are inconsistent. Check for and correct: • A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0. Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3 (SCALAR: SPEED), when 8123 PFC ENABLE is activated. Parameter values for power control are inconsistent: Improper motor nominal frequency or speed. Check for both of the following: • 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16 • 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor Poles) < 0.992 6. Ratings By type code, the table below provides ratings for the ACS550 Type code Normal Use Heavy-Duty Use ER50- I2 N P N P N I2 hd P hd P hd A kW HP A kW HP Three-phase supply voltage, 380…480 V 0,75/4K/4G 1,1/4K/4G 1,5/4K/4G 2,2/4K/4G 3,0/4K/4G 4,0/4K/4G 5,5/4K/4G 7,5/4K/4G 11,0/4K/4G 15,0/4K/4G 18,5/4K/4G 22,0/4K/4G 30,0/4K/4G 37,0/4K/4G 45,0/4K/4G 55,0/4K/4G 75,0/4K/4G 3,3 4,1 5,4 6,9 8,8 11,9 15,4 23 31 38 44 59 72 96 124 157 180 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 90 1,5 2 3 5 7,5 10 15 20 25 30 40 50 75 100 125 150 2,4 3,3 4,1 5,4 6,9 8,8 11,9 15,4 23 31 38 44 59 77 96 124 156 0,75 1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 1 1,5 2 3 5 7,5 10 15 20 25 30 40 60 75 100 125 Frame Size R1 R1 R1 R1 R1 R1 R2 R2 R3 R3 R4 R4 R4 R5 R6 R6 R6 12