Battery & Energy Meter
Quick Guide
Issue: 01
Date: 2017-12-14
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
1
Preparing Cables
NOTICE
The battery output voltage
should always be lower
than or equal to 500 V DC.
NOTE
NOTE
The CAN_H and CAN_L ports of the battery are not used in this document.
This chapter describes the
CHINT-DDSU666 energy
meter. For information about
more energy meters, see
Chapter 3 Energy Meter
Cables Connection.
1.1
Preparing the Battery Cables
e the battery switch between theLG RESU7H/LG RESU10H and the SUN2000L.
Component
Battery switch
Description
Recommended: a DC circuit breaker with a rated voltage greater than
or equal to 600 V DC and a rated current of 20 A
Source
Prepared by the customer
e the power cable between theLG RESU7H/LG RESU10H and the SUN2000L.
CableLG
RESU7H/LG
RESU10H
SUN2000L
TypeConductor Cross-
sectional Area
Range
4–6 mm
2
4–6 mm
2
Outer
Diameter
N/A
4.5–7.8
mm
Source
Ground wire
Negative line of
the power cable
Positive line of the
power cable
-
+
N/A
BAT-
BAT+
Single-core outdoor
copper cable
Standard PV cable in
the industry
(recommended model:
PV1-F)
Prepared by the
customer
Prepared by the
customer
e the battery communications cable between theLG RESU7H/LG RESU10H and the SUN2000L.
Cable
Communications
cable
LG RESU7H/LG
RESU10H
2) EN GND
3)ENABLE_H
4) RS485_H
5) RS485_L
(COM)
SUN2000L
5) EN-
6) EN+
4) 485A2
3) 485B2
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
1
1.2
Preparing the Energy Meter Cables
e the AC switch between the energy meter and the SUN2000L.
Component
AC switch
Description
Recommended: a single-phase AC circuit breaker with a rated voltage
greater than or equal to 250 V AC and a rated current of
•16 A (SUN2000L-2KTL)
•25 A (SUN2000L-3KTL and SUN2000L-3.68KTL)
•32 A (SUN2000L-4KTL, SUN2000L-4.6KTL, and SUN2000L-5KTL)
Source
Prepared by the customer
e cables between the energy meter and the SUN2000L.
CHINT-DDSU666
CableCHINT-
DDSU666
1) L
3) N
(AC)
SUN2000L
L
N
Type
Two-core (L and N)
outdoor copper
cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and
the SUN2000L
Cable
Communications
cable
CHINT-
DDSU666
RS485A(+)
RS485B(-)
(COM)
SUN2000L
2) 485A1
1) 485B1
Type
Four-core outdoor
shielded twisted
pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
EM111DINAV81XS1X
CableEM111DINA
V81XS1X
2) L
N
(AC)
SUN2000L
L
N
Type
Two-core (L and N)
outdoor copper cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and
the SUN2000L
Cable
Communications
cable
EM111DINAV81X
S1X
6) B+
(COM)
SUN2000L
2) 485A1
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
8) A-1) 485B1
EM340DINAV23XS1X
CableEM340DINA
V23XS1X
4) L
N
EM340DINAV23X
S1X
8) B+
9) A-
(AC)
SUN2000L
L
N
(COM)
SUN2000L
2) 485A1
1) 485B1
Type
Two-core (L and N)
outdoor copper
cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and the
SUN2000L
Cable
Communications
cable
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
NOTICE
If a connector needs to connect to two signal cables, ensure that the cables have the same outer diameter.
2
2
Battery Cables Connection
2.1
Connecting the Battery Cables to the Battery Pack
NOTICE
Make sure that the Auxiliary Power ON/OFF switch and the Circuit Breaker switch of the battery pack are turned off before connecting
the power cable to the battery pack.
Make sure that the inverter AC and DC disconnections are turned off before connecting the power cable to the battery pack.
t the Communications Cable.
t the power cable.
a)Connect the ground wire to terminal 1.
b)Connect the negative line of the power cable to terminal 2.
c)Connect the positive line of the power cable to terminal 3.
At first, connect the wire to terminal 2. Then, make
connections to the 3, 4, and 5 terminals one after another.
2.2
Connecting the Battery Cables to the SUN2000L
DANGER
Do not connect or disconnect battery cables when the SUN2000L is running. Failing to do so may cause electric shocks.
Before connecting battery cables, ensure that the DC switch on the SUN2000L and all the switches connecting to the SUN2000L are OFF,
and the SUN2000L has no residual electricity. Otherwise, the high voltage of the SUN2000L and battery may result in electric shocks.
If no battery connects to the SUN2000L, do not remove the watertight cap from the battery terminal. Otherwise, the SUN2000L willnot
comply with its Ingress Protection Rating. If a battery connects to the SUN2000L, set aside the watertight cap. Reinstall thewatertight cap
immediately after removing the connector. The high voltage of the battery terminal may result in electric shocks.
le the blue positive and negative connectors, and then connect the power cable.
Positive metal terminal
Positive connector
Ensure that
the locking nut
is secured.
Negative metal terminal
Ensure that the cable will not
be extracted after crimped.
Negative connector
Pull the power cable back to ensure that it
is connected securely.
Click
Savethe watertight
caps for later use.
Pull the battery cable back to ensure
that it is connected securely.
WARNING
Do not connect any load between the SUN2000L and the battery.
Ensure that the following conditions are met. Otherwise, the SUN2000L will be damaged, or even become a fire hazard.
The battery cable is connected correctly. That is, the positive and negative terminals of the battery connect to the positive battery terminal
and negative battery terminal on the SUN2000L respectively.
The cable between the battery and the SUN2000L should be less than or equal to 10 meters, and within 5 meters is recommended.
The battery voltage can result in fatal injury. Use dedicated insulation tools to terminate cables.
Ensure that the battery cable is correctly connected. Avoid reverse polarity.
3
t the communications cable.
No.
3
4
LabelDefinition
RS485B, RS485
485B2
differential signal–
485A2
RS485A, RS485
differential signal+
NOTICE
5
6
8
EN–
EN+
PE
Enable signal–
Enable signal+
Grounding the shield layer
When laying out signal cables, separate
them from power cables to avoid strong
signal interference sources.
The protection layer of the signal cable is
in the connector. Surplus core wires are
cut off from the protection layer. The
exposed core wire is totally inserted into
the cable hole and connected securely.
3
a)
3.1
Connecting the Energy Meter Cables to the SUN2000L
t the AC output power cable to the SUN2000L.
Connect the AC output power cable to the AC connector.
Energy Meter Cables Connection
Connection
Click
b)Connect the AC connector to the AC output port.
c)Check the route of the AC
output power cable.
t the communications cable to the SUN2000L.
4
3.2
Connecting the Energy Meter Cables to the Energy Meter
CHINT-DDSU666
Open the front cover, and then connect the cable to the CHINT-DDSU666.
Top view
4) N
8) RS485B
7) RS485A
3) N
SUN2000L
7) 485A
8) 485B
3) N4) N
COM
1) 485B1
2) 485A1
AC
LN
Power grid
Side view
Front cover
AC
switch
CHINT-DDSU666
1) L
2) L
Front cover
L
Bottom view
1) L
5) P+
6) PQ-
2) L
NL
Load
NOTE
The P+ and PQ+ ports are not used in this document.
It is recommended that the energy meter be installed in the original residential power
distribution unit. The energy meter can also be independently installed outside the original
residential power distribution unit.
EM111DINAV81XS1X
Open the front cover, and then connect the cable to the EM111DINAV81XS1X.
LL
SUN2000L
COM
2) 485A11) 485B1
AC
LN
B+
Power grid
A-
AC
switch
Residential power
distribution unit
NOTE
It is recommended that the energy meter be installed in
the original residential power distribution unit. The
energy meter can also be independently installed
outside the original residential power distribution unit.
NL
Load
5
EM340DINAV23XS1X
Open the front cover, and then connect the cable to the EM340DINAV23XS1X.
L1L2L3
COM
2) 485A11) 485B1
AC
L
N
EM340DINAV23XS1X
AC
switch
B+
A-
Power grid
L1L2L3
NOTE
It is recommended that the energy meter be
installed in the original residential power
distribution unit. The energy meter can also be
independently installed outside the original
residential power distribution unit.
NL1L2L3
Residential power
distribution unit
Load
3
Commissioning
3.1
Powering On the System
the battery pack in operation by taking the following steps:
a)Turn on the Auxiliary Power ON/OFF switch after installing the battery pack. Make sure that the Circuit Breaker switch is in theOFF
position (including the Trip position).
b)Set the Circuit Breaker switch to the ON position.
Auxiliary Power ON/OFF switch Circuit Breaker switch
c)Several seconds after the Circuit Breaker switch is set to ON, 4 LEDs will be lit.
d)Make sure that ON indicator is on and see if the battery pack is successfully initialized. The power-on indicator on the front should turn on
in green.
e)Close the wiring box cover.
6
on the SUN2000L:
NOTICE
.
Before turning on the AC switch between the SUN2000L and the power grid, check that the AC voltage on the power grid side of the AC
switch is within the specified range.
If the DC is on and the AC is off, the SUN2000L reports a Grid Failurealarm. The SUN2000L starts normally only after the fault is rectified.
If the AC is on and the battery is off, the SUN2000L reports a Battery Abnormal alarm.
(A) PV string
(D) AC switch
(G) Residential power meter
(J) Battery switch
(B) DC switch
(E)Residential power distribution unit
(H) Power grid
(K) Alarm beacon
(C) SUN2000L
(F) Energy meter
(I) Battery
(L) Residential load
a)Turn on the battery switch between the battery pack and the SUN2000L.
b)Turn on the AC switchbetween the SUN2000L and the power grid.
NOTICE
If the SUN2000L is connected to the battery, after turning on the AC switch:
If the DC switch is turned on within 1 minute, the SUN2000L will run properly in grid-tied mode.
If the DC switch is not turned on within 1 minute, the SUN2000L will enter the nighttime grid-tied mode. Then, after the DC switch is
turned on, the SUN2000L will shut down and then restart to run in grid-tied mode.
c)Turn on the DC switch between the PV string and the SUN2000L if there is any.
d)Turn on the DC switch at the bottom of the SUN2000L.
e)Perform quick setting over the FusionHomeapp. There are two methods to add the device. Method 1: tap Go to set after quick setting is
complete, and then configure parameters on the Add/Delete device 2: on the Operation consolescreen, choose Device
maintenance > Add/Delete device, and add the deviceaccording to actual conditions.
7
Model
CHINT-DDSU666
Gavazzi-EM111DINAV81XS1X
Gavazzi-EM340DINAV23XS1X
LG-RESU
Commaddress
11
1
1
15
Energy Meter Parameter
Commaddress
DescriptionValue Range
Specifies the RS485 address for the connected energy meter. The address
[1, 247]
should be the same as the actual address for the energy meter.
Specifies the model of the connected energymeter. No energymeters of
other models can be connected.
Metermodel
CHINT-DDSU666
Gavazzi-EM111DINAV81XS1X
Gavazzi-EM340DINAV23XS1X
Value RangeBattery Parameter
Commaddress
Battery type
Maximum Discharging
Power
Description
Specifies the RS485 address for the connected battery. The address should be [1, 247]
the same as the actual address for the battery.
Specifies the type of the connected battery. No batteries of other types can be
connected.
Specifies the maximum battery charging power.
The maximum charging power is limited by the maximum output power of the
SUN2000L and whether the charge/discharge powerfunction is enabled.
LG-RESU
[0, 3500]
Maximum Charging
Power
Specifies the maximum battery discharging power.
The maximum discharging power is limited by the maximum output power of
the SUN2000L and whether the charge/discharge powerfunction is
enabled.
[0, 3500]
Full Charging Capacity
Full Discharging Capacity
Specifies the battery charging cutoff capacity.
Specifies the battery discharging cutoff capacity.
[90, 100]
[12, 20]
f)(Optional) Measure the temperatures at the joints between the DC terminals and the connectors using a point-test thermometer.
NOTE
Under normal operation conditions of the SUN2000L, the temperature rise at DC connectors should remain below 30°C at all time.
g)Observe the LEDs to check the SUN2000L operating status.
8
3.2
Checking the Match between the SUN2000L and the Battery Protocol
NOTICE
The following text describes the operations on iOS screens. The operations on Android screens are the same as those on iOS screens,
except that the screens are somewhat different. The actual screens prevail.
In the iOS system, the upgrade file can be imported to the mobile phone over your mailbox. The upgrade file name extension must
be .zip. Manually select is unavailable.
In the Android system, the upgrade file can be copied to the mobile phone. The upgrade file name extension must be .zip and the file
can be stored in your required directory. Manually select is available.
the FusionHomeapp, and choose Device maintenance > Upgrade device to view the SUN2000L version. Upgrade the SUN2000L if its
version is earlier than V100R001C00SPC305.
a)Import the SUN2000L upgrade packageto the mobile phone over your mailbox, and then log in to the FusionHomeapp as installer.
b)Upgrade the SUN2000L. The SUN2000L upgrade takes about 5 minutes. When the SUN2000L is upgraded successfully, the SUN2000L
will restart. Log in again after the restart.
9
that the battery cable connection and parameter settings (Commaddr: 15, Battery type: LG-RGSU) are correct. Then in either of the
three following cases, upgrade the battery.
ch CaseRemarks
LG RESU10H:
On the FusionHomeapp, choose Device
maintenance > Upgrade device to view the
battery version.
Upgrade the LG RESU10H if DCDC Current
versionis not 7kW-V4.7.
LG RESU7H:
1
Upgrade the LG RESU7H if DCDC Current
versionis not 5kW-V4.7.
2
The battery is Offlineand not working properly.
View the battery status by choosing Device info
> Device status on the FusionHomeapp.
3
The battery status is displayed on the Device
status screen. The battery auxiliary power
indicator is on but the battery chargingand
discharging indicators are off.
Battery
auxiliary
power
indicator
Battery
charging
indicator
Battery
discharging
indicator
NOTE
In the iOS system, the upgrade file can be imported to the mobile phone over your mailbox. The upgrade file name extension must
be .zip. Manually selectis unavailable.
10
a)Import the battery upgrade packageto the mobile phone over your mailbox, and then log in to the FusionHomeapp as installer.
The upgrade package for the LG RESU10H is RESU10H_DCDC_UPGRADE_.
The upgrade package for the LG RESU7H is RESU7H_DCDC_UPGRADE_.
b)Select the upgrade package to upgrade the battery from V2.0 to V4.7. The upgrade takes about 5 minutes.
The upgrade package for the LG RESU10H is RESU10H_DCDC_UPGRADE_.
The upgrade package for the LG RESU7H is RESU7H_DCDC_UPGRADE_.
The following figure uses LG RESU10H upgrade as an example.
11
completing the upgrade, check that the battery is working properly.
3.3
Powering Off the System
off the SUN2000L:
WARNING
After the SUN2000L powers off, the remaining electricity and heat may still cause electric shocks and body burns. Therefore, puton
protective gloves and begin servicing the SUN2000L 5 minutes after the power-off.
If the SUN2000L is connected to the battery, ensure that a shutdown command is sent from the app. Power off the system after the
SUN2000L has shut down. If no shutdown command is sent from the app, the SUN2000L will shut down after the power grid is
powered off. Then, the SUN2000L will wait for 1 minute and restart (not grid-tied) to charge the battery, which poses the risk of turning
off the DC switch with power.
a)Send a shutdown command from the app. If you log in as installer, on the Operation console screen, choose Device maintenance >
Inverter ON/OFF, and perform operations as required; if you log in as user, on the main screen, choose > Setmaint> Inverter
ON/OFF, and perform operations as required.
b)
c)
d)
e)
Turn off the AC switch between the SUN2000L and the power grid.
Turn off the DC switch at the bottom of the SUN2000L.
Turn off the DC switch between the PV string and the SUN2000L if there is any.
If a battery connects to the battery port, turn off the battery switch.
(A) PV string
(D) AC switch
(G) Residential power meter
(J) Battery switch
(B) DC switch
(E)Residential power distribution unit
(H) Power grid
(K) Alarm beacon
(C) SUN2000L
(F) Energy meter
(I) Battery
(L) Residential load
off the battery pack:
WARNING
•
•
a)
b)
c)
d)
e)
Do not turn off the Auxiliary Power ON/OFF switch in normal operation mode such as charge and discharge mode.
If not using the battery pack for a long time or there is any fault on the battery pack, turn off the Circuit Breaker switch,and then turn off
the Auxiliary Power ON/OFF switch.
Remove the wiring box cover.
Turn off the battery pack by setting the Circuit Breaker switch to the OFF position.
Make sure that every indicator on the battery pack is off. It should take 60 seconds at most for the indicators to turn off.
Turn off the Auxiliary Power ON/OFF switch.
Close the wiring box cover.
Auxiliary Power ON/OFF switch Circuit Breaker switch
12
4
2067
Alarm NameAlarm SeverityPossible CauseSuggestionAlarm ID
Faulty Power
Collector
MajorCause ID = 1
In Grid Connection with Zero
Power mode, the power
collector communication is
interrupted.
In Maximum Use of Self-
Produced Power mode, the
power collector communication
is interrupted.
that the preset power
collector model is the same as the
actual model.
that the preset
communications parameters for the
power collector are the same as the
actual configurations.
that the power collector is
powered on and the RS485
communications cable is correctly
connected.
that the communications
cable and power cable between the
SUN2000L and the battery are
properly connected.
that the battery switch is
turned on properly.
off the AC output switch, DC
input switch, and battery switch, and
then turn them on after 5 minutes. If
the fault persists, contact your
dealer.
2068Abnormal
Battery
MinorCause ID = 1
The battery is faulty.
The battery communication is
interrupted.
The battery switch trips when
the SUN2000L is running.
Customer Service Contact Information
Region
Europe
Asia Pacific
Other countries
Japan and Korea
China
India
North America
Latin America
The Middle East and Africa
Japan and Korea
China
India
The United States and Canada
All countries
All countries
***************************
**********************.com
***********************
******************************
******************************
******************************
*******************************
Country
All countries
Australia
Service Support Mailbox
******************************
******************************
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang
Shenzhen 518129 People's Republic of China
13
2024年10月5日发(作者:黄含莲)
Battery & Energy Meter
Quick Guide
Issue: 01
Date: 2017-12-14
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
1
Preparing Cables
NOTICE
The battery output voltage
should always be lower
than or equal to 500 V DC.
NOTE
NOTE
The CAN_H and CAN_L ports of the battery are not used in this document.
This chapter describes the
CHINT-DDSU666 energy
meter. For information about
more energy meters, see
Chapter 3 Energy Meter
Cables Connection.
1.1
Preparing the Battery Cables
e the battery switch between theLG RESU7H/LG RESU10H and the SUN2000L.
Component
Battery switch
Description
Recommended: a DC circuit breaker with a rated voltage greater than
or equal to 600 V DC and a rated current of 20 A
Source
Prepared by the customer
e the power cable between theLG RESU7H/LG RESU10H and the SUN2000L.
CableLG
RESU7H/LG
RESU10H
SUN2000L
TypeConductor Cross-
sectional Area
Range
4–6 mm
2
4–6 mm
2
Outer
Diameter
N/A
4.5–7.8
mm
Source
Ground wire
Negative line of
the power cable
Positive line of the
power cable
-
+
N/A
BAT-
BAT+
Single-core outdoor
copper cable
Standard PV cable in
the industry
(recommended model:
PV1-F)
Prepared by the
customer
Prepared by the
customer
e the battery communications cable between theLG RESU7H/LG RESU10H and the SUN2000L.
Cable
Communications
cable
LG RESU7H/LG
RESU10H
2) EN GND
3)ENABLE_H
4) RS485_H
5) RS485_L
(COM)
SUN2000L
5) EN-
6) EN+
4) 485A2
3) 485B2
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
1
1.2
Preparing the Energy Meter Cables
e the AC switch between the energy meter and the SUN2000L.
Component
AC switch
Description
Recommended: a single-phase AC circuit breaker with a rated voltage
greater than or equal to 250 V AC and a rated current of
•16 A (SUN2000L-2KTL)
•25 A (SUN2000L-3KTL and SUN2000L-3.68KTL)
•32 A (SUN2000L-4KTL, SUN2000L-4.6KTL, and SUN2000L-5KTL)
Source
Prepared by the customer
e cables between the energy meter and the SUN2000L.
CHINT-DDSU666
CableCHINT-
DDSU666
1) L
3) N
(AC)
SUN2000L
L
N
Type
Two-core (L and N)
outdoor copper
cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and
the SUN2000L
Cable
Communications
cable
CHINT-
DDSU666
RS485A(+)
RS485B(-)
(COM)
SUN2000L
2) 485A1
1) 485B1
Type
Four-core outdoor
shielded twisted
pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
EM111DINAV81XS1X
CableEM111DINA
V81XS1X
2) L
N
(AC)
SUN2000L
L
N
Type
Two-core (L and N)
outdoor copper cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and
the SUN2000L
Cable
Communications
cable
EM111DINAV81X
S1X
6) B+
(COM)
SUN2000L
2) 485A1
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
8) A-1) 485B1
EM340DINAV23XS1X
CableEM340DINA
V23XS1X
4) L
N
EM340DINAV23X
S1X
8) B+
9) A-
(AC)
SUN2000L
L
N
(COM)
SUN2000L
2) 485A1
1) 485B1
Type
Two-core (L and N)
outdoor copper
cable
Conductor Cross-
sectional Area Range
4–6 mm
2
Outer
Diameter
10–21 mm
Source
Prepared by the
customer
AC output power
cable between the
energy meter and the
SUN2000L
Cable
Communications
cable
Type
Four-core
outdoor
shielded
twisted pair
Conductor Cross-
sectional Area Range
0.25–1 mm
2
Outer
Diameter
4–11 mm
Source
Prepared by the
customer
NOTICE
If a connector needs to connect to two signal cables, ensure that the cables have the same outer diameter.
2
2
Battery Cables Connection
2.1
Connecting the Battery Cables to the Battery Pack
NOTICE
Make sure that the Auxiliary Power ON/OFF switch and the Circuit Breaker switch of the battery pack are turned off before connecting
the power cable to the battery pack.
Make sure that the inverter AC and DC disconnections are turned off before connecting the power cable to the battery pack.
t the Communications Cable.
t the power cable.
a)Connect the ground wire to terminal 1.
b)Connect the negative line of the power cable to terminal 2.
c)Connect the positive line of the power cable to terminal 3.
At first, connect the wire to terminal 2. Then, make
connections to the 3, 4, and 5 terminals one after another.
2.2
Connecting the Battery Cables to the SUN2000L
DANGER
Do not connect or disconnect battery cables when the SUN2000L is running. Failing to do so may cause electric shocks.
Before connecting battery cables, ensure that the DC switch on the SUN2000L and all the switches connecting to the SUN2000L are OFF,
and the SUN2000L has no residual electricity. Otherwise, the high voltage of the SUN2000L and battery may result in electric shocks.
If no battery connects to the SUN2000L, do not remove the watertight cap from the battery terminal. Otherwise, the SUN2000L willnot
comply with its Ingress Protection Rating. If a battery connects to the SUN2000L, set aside the watertight cap. Reinstall thewatertight cap
immediately after removing the connector. The high voltage of the battery terminal may result in electric shocks.
le the blue positive and negative connectors, and then connect the power cable.
Positive metal terminal
Positive connector
Ensure that
the locking nut
is secured.
Negative metal terminal
Ensure that the cable will not
be extracted after crimped.
Negative connector
Pull the power cable back to ensure that it
is connected securely.
Click
Savethe watertight
caps for later use.
Pull the battery cable back to ensure
that it is connected securely.
WARNING
Do not connect any load between the SUN2000L and the battery.
Ensure that the following conditions are met. Otherwise, the SUN2000L will be damaged, or even become a fire hazard.
The battery cable is connected correctly. That is, the positive and negative terminals of the battery connect to the positive battery terminal
and negative battery terminal on the SUN2000L respectively.
The cable between the battery and the SUN2000L should be less than or equal to 10 meters, and within 5 meters is recommended.
The battery voltage can result in fatal injury. Use dedicated insulation tools to terminate cables.
Ensure that the battery cable is correctly connected. Avoid reverse polarity.
3
t the communications cable.
No.
3
4
LabelDefinition
RS485B, RS485
485B2
differential signal–
485A2
RS485A, RS485
differential signal+
NOTICE
5
6
8
EN–
EN+
PE
Enable signal–
Enable signal+
Grounding the shield layer
When laying out signal cables, separate
them from power cables to avoid strong
signal interference sources.
The protection layer of the signal cable is
in the connector. Surplus core wires are
cut off from the protection layer. The
exposed core wire is totally inserted into
the cable hole and connected securely.
3
a)
3.1
Connecting the Energy Meter Cables to the SUN2000L
t the AC output power cable to the SUN2000L.
Connect the AC output power cable to the AC connector.
Energy Meter Cables Connection
Connection
Click
b)Connect the AC connector to the AC output port.
c)Check the route of the AC
output power cable.
t the communications cable to the SUN2000L.
4
3.2
Connecting the Energy Meter Cables to the Energy Meter
CHINT-DDSU666
Open the front cover, and then connect the cable to the CHINT-DDSU666.
Top view
4) N
8) RS485B
7) RS485A
3) N
SUN2000L
7) 485A
8) 485B
3) N4) N
COM
1) 485B1
2) 485A1
AC
LN
Power grid
Side view
Front cover
AC
switch
CHINT-DDSU666
1) L
2) L
Front cover
L
Bottom view
1) L
5) P+
6) PQ-
2) L
NL
Load
NOTE
The P+ and PQ+ ports are not used in this document.
It is recommended that the energy meter be installed in the original residential power
distribution unit. The energy meter can also be independently installed outside the original
residential power distribution unit.
EM111DINAV81XS1X
Open the front cover, and then connect the cable to the EM111DINAV81XS1X.
LL
SUN2000L
COM
2) 485A11) 485B1
AC
LN
B+
Power grid
A-
AC
switch
Residential power
distribution unit
NOTE
It is recommended that the energy meter be installed in
the original residential power distribution unit. The
energy meter can also be independently installed
outside the original residential power distribution unit.
NL
Load
5
EM340DINAV23XS1X
Open the front cover, and then connect the cable to the EM340DINAV23XS1X.
L1L2L3
COM
2) 485A11) 485B1
AC
L
N
EM340DINAV23XS1X
AC
switch
B+
A-
Power grid
L1L2L3
NOTE
It is recommended that the energy meter be
installed in the original residential power
distribution unit. The energy meter can also be
independently installed outside the original
residential power distribution unit.
NL1L2L3
Residential power
distribution unit
Load
3
Commissioning
3.1
Powering On the System
the battery pack in operation by taking the following steps:
a)Turn on the Auxiliary Power ON/OFF switch after installing the battery pack. Make sure that the Circuit Breaker switch is in theOFF
position (including the Trip position).
b)Set the Circuit Breaker switch to the ON position.
Auxiliary Power ON/OFF switch Circuit Breaker switch
c)Several seconds after the Circuit Breaker switch is set to ON, 4 LEDs will be lit.
d)Make sure that ON indicator is on and see if the battery pack is successfully initialized. The power-on indicator on the front should turn on
in green.
e)Close the wiring box cover.
6
on the SUN2000L:
NOTICE
.
Before turning on the AC switch between the SUN2000L and the power grid, check that the AC voltage on the power grid side of the AC
switch is within the specified range.
If the DC is on and the AC is off, the SUN2000L reports a Grid Failurealarm. The SUN2000L starts normally only after the fault is rectified.
If the AC is on and the battery is off, the SUN2000L reports a Battery Abnormal alarm.
(A) PV string
(D) AC switch
(G) Residential power meter
(J) Battery switch
(B) DC switch
(E)Residential power distribution unit
(H) Power grid
(K) Alarm beacon
(C) SUN2000L
(F) Energy meter
(I) Battery
(L) Residential load
a)Turn on the battery switch between the battery pack and the SUN2000L.
b)Turn on the AC switchbetween the SUN2000L and the power grid.
NOTICE
If the SUN2000L is connected to the battery, after turning on the AC switch:
If the DC switch is turned on within 1 minute, the SUN2000L will run properly in grid-tied mode.
If the DC switch is not turned on within 1 minute, the SUN2000L will enter the nighttime grid-tied mode. Then, after the DC switch is
turned on, the SUN2000L will shut down and then restart to run in grid-tied mode.
c)Turn on the DC switch between the PV string and the SUN2000L if there is any.
d)Turn on the DC switch at the bottom of the SUN2000L.
e)Perform quick setting over the FusionHomeapp. There are two methods to add the device. Method 1: tap Go to set after quick setting is
complete, and then configure parameters on the Add/Delete device 2: on the Operation consolescreen, choose Device
maintenance > Add/Delete device, and add the deviceaccording to actual conditions.
7
Model
CHINT-DDSU666
Gavazzi-EM111DINAV81XS1X
Gavazzi-EM340DINAV23XS1X
LG-RESU
Commaddress
11
1
1
15
Energy Meter Parameter
Commaddress
DescriptionValue Range
Specifies the RS485 address for the connected energy meter. The address
[1, 247]
should be the same as the actual address for the energy meter.
Specifies the model of the connected energymeter. No energymeters of
other models can be connected.
Metermodel
CHINT-DDSU666
Gavazzi-EM111DINAV81XS1X
Gavazzi-EM340DINAV23XS1X
Value RangeBattery Parameter
Commaddress
Battery type
Maximum Discharging
Power
Description
Specifies the RS485 address for the connected battery. The address should be [1, 247]
the same as the actual address for the battery.
Specifies the type of the connected battery. No batteries of other types can be
connected.
Specifies the maximum battery charging power.
The maximum charging power is limited by the maximum output power of the
SUN2000L and whether the charge/discharge powerfunction is enabled.
LG-RESU
[0, 3500]
Maximum Charging
Power
Specifies the maximum battery discharging power.
The maximum discharging power is limited by the maximum output power of
the SUN2000L and whether the charge/discharge powerfunction is
enabled.
[0, 3500]
Full Charging Capacity
Full Discharging Capacity
Specifies the battery charging cutoff capacity.
Specifies the battery discharging cutoff capacity.
[90, 100]
[12, 20]
f)(Optional) Measure the temperatures at the joints between the DC terminals and the connectors using a point-test thermometer.
NOTE
Under normal operation conditions of the SUN2000L, the temperature rise at DC connectors should remain below 30°C at all time.
g)Observe the LEDs to check the SUN2000L operating status.
8
3.2
Checking the Match between the SUN2000L and the Battery Protocol
NOTICE
The following text describes the operations on iOS screens. The operations on Android screens are the same as those on iOS screens,
except that the screens are somewhat different. The actual screens prevail.
In the iOS system, the upgrade file can be imported to the mobile phone over your mailbox. The upgrade file name extension must
be .zip. Manually select is unavailable.
In the Android system, the upgrade file can be copied to the mobile phone. The upgrade file name extension must be .zip and the file
can be stored in your required directory. Manually select is available.
the FusionHomeapp, and choose Device maintenance > Upgrade device to view the SUN2000L version. Upgrade the SUN2000L if its
version is earlier than V100R001C00SPC305.
a)Import the SUN2000L upgrade packageto the mobile phone over your mailbox, and then log in to the FusionHomeapp as installer.
b)Upgrade the SUN2000L. The SUN2000L upgrade takes about 5 minutes. When the SUN2000L is upgraded successfully, the SUN2000L
will restart. Log in again after the restart.
9
that the battery cable connection and parameter settings (Commaddr: 15, Battery type: LG-RGSU) are correct. Then in either of the
three following cases, upgrade the battery.
ch CaseRemarks
LG RESU10H:
On the FusionHomeapp, choose Device
maintenance > Upgrade device to view the
battery version.
Upgrade the LG RESU10H if DCDC Current
versionis not 7kW-V4.7.
LG RESU7H:
1
Upgrade the LG RESU7H if DCDC Current
versionis not 5kW-V4.7.
2
The battery is Offlineand not working properly.
View the battery status by choosing Device info
> Device status on the FusionHomeapp.
3
The battery status is displayed on the Device
status screen. The battery auxiliary power
indicator is on but the battery chargingand
discharging indicators are off.
Battery
auxiliary
power
indicator
Battery
charging
indicator
Battery
discharging
indicator
NOTE
In the iOS system, the upgrade file can be imported to the mobile phone over your mailbox. The upgrade file name extension must
be .zip. Manually selectis unavailable.
10
a)Import the battery upgrade packageto the mobile phone over your mailbox, and then log in to the FusionHomeapp as installer.
The upgrade package for the LG RESU10H is RESU10H_DCDC_UPGRADE_.
The upgrade package for the LG RESU7H is RESU7H_DCDC_UPGRADE_.
b)Select the upgrade package to upgrade the battery from V2.0 to V4.7. The upgrade takes about 5 minutes.
The upgrade package for the LG RESU10H is RESU10H_DCDC_UPGRADE_.
The upgrade package for the LG RESU7H is RESU7H_DCDC_UPGRADE_.
The following figure uses LG RESU10H upgrade as an example.
11
completing the upgrade, check that the battery is working properly.
3.3
Powering Off the System
off the SUN2000L:
WARNING
After the SUN2000L powers off, the remaining electricity and heat may still cause electric shocks and body burns. Therefore, puton
protective gloves and begin servicing the SUN2000L 5 minutes after the power-off.
If the SUN2000L is connected to the battery, ensure that a shutdown command is sent from the app. Power off the system after the
SUN2000L has shut down. If no shutdown command is sent from the app, the SUN2000L will shut down after the power grid is
powered off. Then, the SUN2000L will wait for 1 minute and restart (not grid-tied) to charge the battery, which poses the risk of turning
off the DC switch with power.
a)Send a shutdown command from the app. If you log in as installer, on the Operation console screen, choose Device maintenance >
Inverter ON/OFF, and perform operations as required; if you log in as user, on the main screen, choose > Setmaint> Inverter
ON/OFF, and perform operations as required.
b)
c)
d)
e)
Turn off the AC switch between the SUN2000L and the power grid.
Turn off the DC switch at the bottom of the SUN2000L.
Turn off the DC switch between the PV string and the SUN2000L if there is any.
If a battery connects to the battery port, turn off the battery switch.
(A) PV string
(D) AC switch
(G) Residential power meter
(J) Battery switch
(B) DC switch
(E)Residential power distribution unit
(H) Power grid
(K) Alarm beacon
(C) SUN2000L
(F) Energy meter
(I) Battery
(L) Residential load
off the battery pack:
WARNING
•
•
a)
b)
c)
d)
e)
Do not turn off the Auxiliary Power ON/OFF switch in normal operation mode such as charge and discharge mode.
If not using the battery pack for a long time or there is any fault on the battery pack, turn off the Circuit Breaker switch,and then turn off
the Auxiliary Power ON/OFF switch.
Remove the wiring box cover.
Turn off the battery pack by setting the Circuit Breaker switch to the OFF position.
Make sure that every indicator on the battery pack is off. It should take 60 seconds at most for the indicators to turn off.
Turn off the Auxiliary Power ON/OFF switch.
Close the wiring box cover.
Auxiliary Power ON/OFF switch Circuit Breaker switch
12
4
2067
Alarm NameAlarm SeverityPossible CauseSuggestionAlarm ID
Faulty Power
Collector
MajorCause ID = 1
In Grid Connection with Zero
Power mode, the power
collector communication is
interrupted.
In Maximum Use of Self-
Produced Power mode, the
power collector communication
is interrupted.
that the preset power
collector model is the same as the
actual model.
that the preset
communications parameters for the
power collector are the same as the
actual configurations.
that the power collector is
powered on and the RS485
communications cable is correctly
connected.
that the communications
cable and power cable between the
SUN2000L and the battery are
properly connected.
that the battery switch is
turned on properly.
off the AC output switch, DC
input switch, and battery switch, and
then turn them on after 5 minutes. If
the fault persists, contact your
dealer.
2068Abnormal
Battery
MinorCause ID = 1
The battery is faulty.
The battery communication is
interrupted.
The battery switch trips when
the SUN2000L is running.
Customer Service Contact Information
Region
Europe
Asia Pacific
Other countries
Japan and Korea
China
India
North America
Latin America
The Middle East and Africa
Japan and Korea
China
India
The United States and Canada
All countries
All countries
***************************
**********************.com
***********************
******************************
******************************
******************************
*******************************
Country
All countries
Australia
Service Support Mailbox
******************************
******************************
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang
Shenzhen 518129 People's Republic of China
13