Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
Model catalogue reference
Number of UPM's
(Uninterruptible Power Modules)
UPS Options:
Internal batteries, standard or
long life
Internal Battery Breaker (BB)
Internal maintenance bypass
(MBS)
Integrated maintenance bypass
(SIAC-MBS)
Separate battery per UPM (SB)
Top Cable Access (C)
Plywood package
Upgradeability
External paralleling
30-50 kW
93PM-XX(50)
1 UPM
30-100 kW
93PM-XXX(100)
1...2 UPM's
30-150 kW
93PM-XXX(150)
1...3 UPM's
30-200 kW
93PM-XXX(200)
1...4 UPM's
X
Default
X
X
X
X
X
X
X
X
X
up to 50 kW
X
X
up to 100 kW
X
X
X
up to 150 kW
X
Default
X
up to 200 kW
Up to 8 units with HotSync technology
Double conversion, 3-level IGBT converters
VFI-SS-111
5.1.1
5.3.4
UPS topology
UPS performance classification
MECHANICAL
UPS dimensions (width x depth x
height)
UPS dimensions with top air
exhaust (width x depth x height)
N/A
UPS+0bat: 330 kg
UPS+3bat: 615 kg
UPS+4bat: 745 kg
UPS+5bat: 845 kg
UPS+6bat: 945 kg
UPS+0bat: 288 kg
UPS+3bat: 579 kg
UPS+4bat: 676 kg
UPS+5bat: 773 kg
UPS+6bat: 870 kg
560 x 914 x 1876 mm
560 x 1114 x 1876 mm
760 x 914 x 1876 mm
760 x 1114 x 1876
mm
1 UPM: 431 kg
2 UPMs: 496 kg
3 UPMs: 561 kg
4 UPMs: 626 kg
1 UPM: 346 kg
2 UPMs: 408 kg
3 UPMs: 471 kg
4 UPMs: 556 kg
Top / bottom / rear
entry
Shipping weight, UPS and
internal batteries
1 UPM: 337 kg
2 UPMs: 408 kg
1 UPM: 378 kg
2 UPMs: 443 kg
3 UPMs: 508 kg
Installed weight, UPS and
internal batteries
1 UPM: 267 kg
2 UPMs: 338 kg
1 UPM: 279 kg
2 UPMs: 341 kg
3 UPMs: 438 kg
UPS Cable entry
UPS Degree of protection
UPS colour
Mean time to repair (MTTR)
ENVIRONMENTAL
6.5.5
Acoustic noise at 1m, in 25 °
C
ambient temperature
Ambient storage temperature
range
4.1.4
UPS
Internal and external VRLA
battery
Bottom / rear entry
Top entry with optional kit
Black, RAL 9005
< 30 minutes
IP20 (EN60529), with front door mounted washable dust filter
< 60 dBA in double
conversion
< 47 dBA in ESS
< 65 dBA in double conversion
< 47 dBA in ESS
-25 °C to +55 °C in the protective package
-25 °C to +25 °C in the protective package*
*Recommended for optimized battery life time
Page 1 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
Ambient operating temperature
+5 to +40 °C
range
The maximum rate of change shall be limited to 1.67 °C over 5 minutes (20 °C/hour),
4.2.1.1 and
UPS
based on the ASHRAE standard 90.1-2013
5.4.2.2 h
Internal and External VRLA
+ 20 °C to + 25 °C recommended for optimized battery life time
battery
5 to 95%, no condensation allowed. Recommended range 20-60%.
Relative humidity range during
There shall be at least a 1.0 °C difference between the dry bulb temperature and the
4.2.1.1
storage and operation
wet bulb temperature at all times, to maintain a non-condensing environment.
Install in controlled indoor area, free of conductive contaminants (IEC 60947-1 pollution
degree 2). Do not expose to overly aggressive environments like salt mist and/or
corrosive gases. UPS should be installed in a G1 environment (based on ANSI/ISA S-
71.04 classifications). Do not place near a source of dust or sand.
1000 m above sea level at 40 °C
Maximum 2000 m with 1% de-rating per each additional 100m above 1000m
Yes
Airborne contaminants
4.2.1.2Operating altitude
RoHS/WEEE compliancy
EFFICIENCY
Efficiency in double-conversion,
rated linear load
5.3.2 r and
6.4.1.6
100% load
75% load
50% load
25% load
Heat dissipation in double
conversion, [W]
30 40 50
96,6 96,5 96,3%
96,6 96,6 96,6%
96,1 96,5 96,6%
94,0 95,1 95,7%
60 80 100
96,7 96,6 96,4%
96,6 96,7 96,6%
96,2 96,6 96,7%
93,4 95,5 96,0%
90 120 150
96,7 96,7 96,5%
96,7 96,7 96,7%
96,4 96,7 96,7%
94,0 95,7 96,1%
120 160 200kW
96,7 96,6 96,4%
96,6 96,7 96,6%
96,3 96,6 96,7%
93,4 95,3 95,9%
30 40 50 60 80 100
2049 2816 3734 W
1584 2048 2640 W
1185 1408 1706 W
1060 942 1042 W
760 W
90 120 150
3071 4095 5440 W
2304 3071 3839 W
1680 2048 2559 W
1436 1348 1623 W
1120 W
120 160 200kW
4095 5631 7469 W
3167 4095 5280 W
2305 2816 3413 W
2120 1973 2138 W
1520 W
100% load
1055 1450 1921 W
75% load
791 1056 1320 W
50% load
609 725 880 W
25% load
479 515 562 W
No load
Efficiency in ESS, rated linear
load
100% load
75% load
50% load
25% load
Heat dissipation in ESS
366 W
30 40 50
99,0 99,1 99,2%
99,0 99,0 99,1%
98,5 98,9 99,0%
97,5 98,1 98,3%
30 40 50
60 80 100
99,1 99,2 99,3%
99,0 99,1 99,2%
98,7 99,0 99,0%
98,4 98,6 98,6%
60 80 100
544 645 705 W
216 W
90 120 150
99,2 99,2 99,3%
99,0 99,2 99,2%
98,8 99,0 99,2%
98,2 98,4 98,7%
90 120 150
723 968 1057 W
340 W
120 160 200kW
99,1 99,2 99,2%
99,0 99,1 99,2%
98,8 99,0 99,0%
98,2 98,4 98,6%
120 160 200kW
1090 1290 1613 W
500 W
100% load
303 363 403 W
No load
Efficiency in stored energy mode,
up to
128 W
95.5 %
Page 2 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
ELECTRICAL CHARACTERISTICS
INPUT
Rated input voltage
5.2.1.a and
Voltage tolerance
5.2.1 b
Rectifier input
Bypass input
5.2.1 c and
Rated input frequency
5.2.1 d
Frequency tolerance
5.2.2 a and
Number of input phases
5.2.2 b
5.2.2 dInput power factor
30 40 50
220/380 V; 230/400 V; 240/415 V
rated voltage -20% / +20%
rated voltage -10% / +10%
50 or 60 Hz
42 to 72 Hz
3 phases + neutral + PE
0,99 at 100% load
60 80 100 90 120 150120 160 200kVA
5.2.2 c
5.2.2 f
Rated rectifier input current,
100% load without charging
Maximum rectifier input current
Rated Bypass input current
45 A 60 A 75 A90 A 120 A 150 A135 A 180 A 226 A 180 A 241 A 301 A
57 A 76 A 95 A 114 A 152 A 190 A 171 A 228 A 285 A228 A 304 A 380 A
44 A 58 A 73 A 87 A 117 A 146 A 131 A 175 A 219 A175 A 233 A 292 A
60 80 100 90 120 150120 160 200kVA
Input current distortion at rated
5.2.2 h and
input current
30 40 50
5.2.2. i
Resistive load
< 5% <3%
5.2.2 e
5.2.2 k
In-rush current
AC power distribution system
compatibility
Rectifier ramp-up, at rectifier
start and load step
Backfeed protection
ELECTRICAL CHARACTERISTICS
OUTPUT
5.3.2 k
Output power rating
Output power factor
≤
145 A
<5% <3%
≤ 150 A
<5% <3%
≤ 180 A
<5% <3%
≤ 380 A
TN, TT, IT (4-wire)
10 A/s (default), configurable.
Minimum 1 A/s.
Yes, for rectifier and bypass lines
30kVA; 40kVA; 50kVA; 60kVA; 80kVA; 100kVA; 90kVA; 120kVA; 150kVA; 160kVA; 200kVA
1.0
From 0,8 lagging to 0,8 leading without de-rating
3 phase + neutral + PE
2,3
220/380 V; 230/400 V; 240/415 V, configurable
< 1%
5.3.2 o and Load power factor, permitted
5.3.2 prange
5.3.2 f and
Number of output phases
5.3.2 g
Crest factor
Rated output voltage
5.3.2 b
Output voltage variation, steady
state
Total voltage harmonic distortion
100%
linear load
100% non-linear load
Voltage unbalance at reference
unbalanced load
Phase displacement at reference
unbalanced load
Voltage transient (r.m.s) and
recovery time
5.3.2 i
< 1,0%
< 3,0%
< 0,1%
< 0,3 deg
< 1,2%
< 3,0%
< 0,6 %
< 1,0 deg
5.3.2 q
0% during transfer from stored energy to normal mode
±4% with 110 ms
recovery from 100%
load step
±4% with 140 ms recovery from 100% load step
5.3.2 j
Page 3 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
Rated output frequency
Output frequency variation
30-50 kW30-100 kW30-150 kW30-200 kW
5.3.2 c
50 or 60 Hz, configurable
± 0,1 Hz
± 4 Hz as default. User settable ± 0,5 to ± 5 Hz.
< 1° with static balanced load
0,4 Hz/s
30, 40, 60, 80, 90, 120, 160 kW
10 min 135% load
60 sec 155% load
10 sec 185% load
300 ms >185% load
50, 100, 150, 200 kW
10 min 110% load
60 sec 125% load
10 sec 150% load
300 ms >150% load
50, 100, 150, 200 kW
10 min 110% load
60 sec 125% load
300 ms >125% load
Continuous < 125% load
10 ms 1000% load
170 A, 400 ms
35 A gL/gG fuse /
B25/C10 circuit
breaker
Maximum frequency range for
synchronization with bypass
5.3.2 d and
Maximum synchronized phase
5.3.2 e
error
Maximum slew-rate when
synchronizing
Overload capability
On inverter
5.3.2 l
Overload capability
On inverter, stored energy mode
30, 40, 60, 80, 90, 120, 160 kW
10 min 135% load
60 sec 155% load
300 ms >155% load
Overload capability
On bypass
5.3.2 m
Output current limitation, short-
circuit capability
345 A, 400 ms
35 A gL/gG fuse /
B50/C25 circuit
breaker
510 A, 400 ms
63 A gL/gG fuse /
B63/C32 circuit
breaker
670 A, 400 ms
63 A gL/gG fuse /
B100/C50 circuit
breaker
6.4.2.10.3
and Fault clearing capability
6.4.2.10.4
ESS MODE CHARACTERISTICS
Transfer time to double-
conversion
Mains available
Mains failure
Output voltage variation setting
Output frequency variation setting
No break
< 2 ms in normal transfer conditions, < 10 ms maximum
±10% of nominal voltage, default
±4 Hz, default
UPS locks into double-conversion mode when three power line disturbances have
forced the unit to double-conversion three times (user adjustable) within a one-hour
period (user adjustable).
UPS will stay on double-conversion for one hour (user adjustable), after which the unit
will automatically return to operate on ESS.
Storm detection
High Alert mode
Page 4 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
VMMS MODE CHARACTERISTICS
VMMS Availability
Available for multi-module 93PM UPS system, both between internal modules and
modules in an external parallel connected system.
When load level per module is less than 55%, VMMS will automatically optimise the
number of online modules for optimised operating efficiency.
The extra UPMs will be set to ready state mode, capable to transfer online in < 2ms
transfer time.
The load will be fed in double conversion mode the entire time, even during and after a
load step.
Number of redundant online UPMs (system wide), configurable.
System will automatically rotate the ready state UPMs.
Enabled by default, configurable.
VMMS operation
Redundancy level setting
UPM module rotation
BYPASS
Type of bypass
Static Bypass rating
Static Bypass voltage range
Transfer time break
Maintenance bypass
Backfeed protection
Rated conditional short-circuit
current, Icc Static bypass
Optional internal or integrated
Maintenance bypass
Internal static bypass ultra-rapid
fuse
Bypass fuse i
2
t value
Pre-arc i
2
t
Total clearing i
2
t
10 kA*
50 kVA100 kVA
Static
150 kVA200 kVA
220/380 V; 230/400 V; 240/415 V
tolerance -10% / +10% of rated voltage
No break
Option, internal or external
Integrated as standard
100 kA (internal ultra rapid fusing)
25 kA*10 kA*50 kA*
Option, integrated
sidecar or external
*using external protective fuse
Bussmann 160LETBussmann 550 A
170M4465
96 100 A
2
s
230 000 A
2
s
60 80 100
Bussmann 900 A 170M4419
1 100 A
2
s
16 000 A
2
s
155 000 A
2
s
850 000 A
2
s
90 120 150120 160 200kVA
External bypass protective fuse,
30 40 50
recommended rating
3x
63 A 80 A 100 A
125 A 160 A 200 A200 A 250 A 315 A250 A 315 A 400 A
Page 5 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
BATTERY CHARACTERISTICS
5.4.2.2 dBattery technology
36 blocks, 216 cells
Battery quantity, internal batteries
per battery string
5.4.2.2 b
Battery quantity, external
batteries
12 V, VRLA
N/A
Note! Units with internal batteries only support 36 block string length
30, 40, 60, 80, 90, 120, 160 kW: 32 ... 40 blocks, 240 cells per battery string
50, 100, 150, 200 kW: 36 ... 40 blocks, 240 cells per battery string
Note! Never connect battery strings with different battery quantity and voltage in
parallel
432 V (36 blocks)
N/A
Battery voltage, internal batteries
5.4.2.2 c
Battery voltage, external batteries
5.4.2.2 o
5.4.2.2 q
5.4.2.2 r
Recharge profile
End of discharge voltage
Charging current at nominal load
Battery start
Temperature compensated
battery charging option
Alternative backup power
technologies
30, 40, 60, 80, 90, 120, 160 kW: 384 V (32 blocks) to 480 V (40 blocks)
50, 100, 150, 200 kW: 432 V (36 blocks) to 480 V (40 blocks)
Advanced Battery Management (ABM
®
) = 90% resting,10% charging (typical)
OR float charge
1.67 VPC to 1.75 VPC
Configurable or automatic (load adaptive)
Configurable 0…29 A per UPM
At > 40 kVA load per UPM, automatically limited to 16,5 A per UPM
Yes
Yes, standard for internal batteries
Yes, with Environmental Monitoring Probe (EMP) for external batteries
Wet cell batteries
NiCd batteries
Lithium-ion batteries
Supercapacitors
COMMUNICATION CIRCUITS
5.6Display
Standard connectivity ports
Optional
Complete list of indications and
interface devices
COMPLIANCE WITH STANDARDS
Safety Access
IEC 62040-1
Degree of protection
Electromagnetic Compatibility
IEC 62040-2
Immunity and EmissionsEMC Category C3
EMC Category C2
as option
EMC Category C3
Operator access area
IP20; protection against medium sized foreign matter (incl. finger)
IP21 available as option
Touchscreen LCD, 4x LEDs for notice and alarm, status LED light stripes
3x Mini-Slot ports for optional cards, Device USB and Host USB, RS-232 service port,
1 x relay output, 5 x building alarm inputs and a dedicated EPO
Mini-Slot cards: Web/SNMP/Modbus, Industrial relay card
See User’s Manual
Page 6 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
2024年10月6日发(作者:汪傲柔)
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
Model catalogue reference
Number of UPM's
(Uninterruptible Power Modules)
UPS Options:
Internal batteries, standard or
long life
Internal Battery Breaker (BB)
Internal maintenance bypass
(MBS)
Integrated maintenance bypass
(SIAC-MBS)
Separate battery per UPM (SB)
Top Cable Access (C)
Plywood package
Upgradeability
External paralleling
30-50 kW
93PM-XX(50)
1 UPM
30-100 kW
93PM-XXX(100)
1...2 UPM's
30-150 kW
93PM-XXX(150)
1...3 UPM's
30-200 kW
93PM-XXX(200)
1...4 UPM's
X
Default
X
X
X
X
X
X
X
X
X
up to 50 kW
X
X
up to 100 kW
X
X
X
up to 150 kW
X
Default
X
up to 200 kW
Up to 8 units with HotSync technology
Double conversion, 3-level IGBT converters
VFI-SS-111
5.1.1
5.3.4
UPS topology
UPS performance classification
MECHANICAL
UPS dimensions (width x depth x
height)
UPS dimensions with top air
exhaust (width x depth x height)
N/A
UPS+0bat: 330 kg
UPS+3bat: 615 kg
UPS+4bat: 745 kg
UPS+5bat: 845 kg
UPS+6bat: 945 kg
UPS+0bat: 288 kg
UPS+3bat: 579 kg
UPS+4bat: 676 kg
UPS+5bat: 773 kg
UPS+6bat: 870 kg
560 x 914 x 1876 mm
560 x 1114 x 1876 mm
760 x 914 x 1876 mm
760 x 1114 x 1876
mm
1 UPM: 431 kg
2 UPMs: 496 kg
3 UPMs: 561 kg
4 UPMs: 626 kg
1 UPM: 346 kg
2 UPMs: 408 kg
3 UPMs: 471 kg
4 UPMs: 556 kg
Top / bottom / rear
entry
Shipping weight, UPS and
internal batteries
1 UPM: 337 kg
2 UPMs: 408 kg
1 UPM: 378 kg
2 UPMs: 443 kg
3 UPMs: 508 kg
Installed weight, UPS and
internal batteries
1 UPM: 267 kg
2 UPMs: 338 kg
1 UPM: 279 kg
2 UPMs: 341 kg
3 UPMs: 438 kg
UPS Cable entry
UPS Degree of protection
UPS colour
Mean time to repair (MTTR)
ENVIRONMENTAL
6.5.5
Acoustic noise at 1m, in 25 °
C
ambient temperature
Ambient storage temperature
range
4.1.4
UPS
Internal and external VRLA
battery
Bottom / rear entry
Top entry with optional kit
Black, RAL 9005
< 30 minutes
IP20 (EN60529), with front door mounted washable dust filter
< 60 dBA in double
conversion
< 47 dBA in ESS
< 65 dBA in double conversion
< 47 dBA in ESS
-25 °C to +55 °C in the protective package
-25 °C to +25 °C in the protective package*
*Recommended for optimized battery life time
Page 1 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
Ambient operating temperature
+5 to +40 °C
range
The maximum rate of change shall be limited to 1.67 °C over 5 minutes (20 °C/hour),
4.2.1.1 and
UPS
based on the ASHRAE standard 90.1-2013
5.4.2.2 h
Internal and External VRLA
+ 20 °C to + 25 °C recommended for optimized battery life time
battery
5 to 95%, no condensation allowed. Recommended range 20-60%.
Relative humidity range during
There shall be at least a 1.0 °C difference between the dry bulb temperature and the
4.2.1.1
storage and operation
wet bulb temperature at all times, to maintain a non-condensing environment.
Install in controlled indoor area, free of conductive contaminants (IEC 60947-1 pollution
degree 2). Do not expose to overly aggressive environments like salt mist and/or
corrosive gases. UPS should be installed in a G1 environment (based on ANSI/ISA S-
71.04 classifications). Do not place near a source of dust or sand.
1000 m above sea level at 40 °C
Maximum 2000 m with 1% de-rating per each additional 100m above 1000m
Yes
Airborne contaminants
4.2.1.2Operating altitude
RoHS/WEEE compliancy
EFFICIENCY
Efficiency in double-conversion,
rated linear load
5.3.2 r and
6.4.1.6
100% load
75% load
50% load
25% load
Heat dissipation in double
conversion, [W]
30 40 50
96,6 96,5 96,3%
96,6 96,6 96,6%
96,1 96,5 96,6%
94,0 95,1 95,7%
60 80 100
96,7 96,6 96,4%
96,6 96,7 96,6%
96,2 96,6 96,7%
93,4 95,5 96,0%
90 120 150
96,7 96,7 96,5%
96,7 96,7 96,7%
96,4 96,7 96,7%
94,0 95,7 96,1%
120 160 200kW
96,7 96,6 96,4%
96,6 96,7 96,6%
96,3 96,6 96,7%
93,4 95,3 95,9%
30 40 50 60 80 100
2049 2816 3734 W
1584 2048 2640 W
1185 1408 1706 W
1060 942 1042 W
760 W
90 120 150
3071 4095 5440 W
2304 3071 3839 W
1680 2048 2559 W
1436 1348 1623 W
1120 W
120 160 200kW
4095 5631 7469 W
3167 4095 5280 W
2305 2816 3413 W
2120 1973 2138 W
1520 W
100% load
1055 1450 1921 W
75% load
791 1056 1320 W
50% load
609 725 880 W
25% load
479 515 562 W
No load
Efficiency in ESS, rated linear
load
100% load
75% load
50% load
25% load
Heat dissipation in ESS
366 W
30 40 50
99,0 99,1 99,2%
99,0 99,0 99,1%
98,5 98,9 99,0%
97,5 98,1 98,3%
30 40 50
60 80 100
99,1 99,2 99,3%
99,0 99,1 99,2%
98,7 99,0 99,0%
98,4 98,6 98,6%
60 80 100
544 645 705 W
216 W
90 120 150
99,2 99,2 99,3%
99,0 99,2 99,2%
98,8 99,0 99,2%
98,2 98,4 98,7%
90 120 150
723 968 1057 W
340 W
120 160 200kW
99,1 99,2 99,2%
99,0 99,1 99,2%
98,8 99,0 99,0%
98,2 98,4 98,6%
120 160 200kW
1090 1290 1613 W
500 W
100% load
303 363 403 W
No load
Efficiency in stored energy mode,
up to
128 W
95.5 %
Page 2 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
ELECTRICAL CHARACTERISTICS
INPUT
Rated input voltage
5.2.1.a and
Voltage tolerance
5.2.1 b
Rectifier input
Bypass input
5.2.1 c and
Rated input frequency
5.2.1 d
Frequency tolerance
5.2.2 a and
Number of input phases
5.2.2 b
5.2.2 dInput power factor
30 40 50
220/380 V; 230/400 V; 240/415 V
rated voltage -20% / +20%
rated voltage -10% / +10%
50 or 60 Hz
42 to 72 Hz
3 phases + neutral + PE
0,99 at 100% load
60 80 100 90 120 150120 160 200kVA
5.2.2 c
5.2.2 f
Rated rectifier input current,
100% load without charging
Maximum rectifier input current
Rated Bypass input current
45 A 60 A 75 A90 A 120 A 150 A135 A 180 A 226 A 180 A 241 A 301 A
57 A 76 A 95 A 114 A 152 A 190 A 171 A 228 A 285 A228 A 304 A 380 A
44 A 58 A 73 A 87 A 117 A 146 A 131 A 175 A 219 A175 A 233 A 292 A
60 80 100 90 120 150120 160 200kVA
Input current distortion at rated
5.2.2 h and
input current
30 40 50
5.2.2. i
Resistive load
< 5% <3%
5.2.2 e
5.2.2 k
In-rush current
AC power distribution system
compatibility
Rectifier ramp-up, at rectifier
start and load step
Backfeed protection
ELECTRICAL CHARACTERISTICS
OUTPUT
5.3.2 k
Output power rating
Output power factor
≤
145 A
<5% <3%
≤ 150 A
<5% <3%
≤ 180 A
<5% <3%
≤ 380 A
TN, TT, IT (4-wire)
10 A/s (default), configurable.
Minimum 1 A/s.
Yes, for rectifier and bypass lines
30kVA; 40kVA; 50kVA; 60kVA; 80kVA; 100kVA; 90kVA; 120kVA; 150kVA; 160kVA; 200kVA
1.0
From 0,8 lagging to 0,8 leading without de-rating
3 phase + neutral + PE
2,3
220/380 V; 230/400 V; 240/415 V, configurable
< 1%
5.3.2 o and Load power factor, permitted
5.3.2 prange
5.3.2 f and
Number of output phases
5.3.2 g
Crest factor
Rated output voltage
5.3.2 b
Output voltage variation, steady
state
Total voltage harmonic distortion
100%
linear load
100% non-linear load
Voltage unbalance at reference
unbalanced load
Phase displacement at reference
unbalanced load
Voltage transient (r.m.s) and
recovery time
5.3.2 i
< 1,0%
< 3,0%
< 0,1%
< 0,3 deg
< 1,2%
< 3,0%
< 0,6 %
< 1,0 deg
5.3.2 q
0% during transfer from stored energy to normal mode
±4% with 110 ms
recovery from 100%
load step
±4% with 140 ms recovery from 100% load step
5.3.2 j
Page 3 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
Rated output frequency
Output frequency variation
30-50 kW30-100 kW30-150 kW30-200 kW
5.3.2 c
50 or 60 Hz, configurable
± 0,1 Hz
± 4 Hz as default. User settable ± 0,5 to ± 5 Hz.
< 1° with static balanced load
0,4 Hz/s
30, 40, 60, 80, 90, 120, 160 kW
10 min 135% load
60 sec 155% load
10 sec 185% load
300 ms >185% load
50, 100, 150, 200 kW
10 min 110% load
60 sec 125% load
10 sec 150% load
300 ms >150% load
50, 100, 150, 200 kW
10 min 110% load
60 sec 125% load
300 ms >125% load
Continuous < 125% load
10 ms 1000% load
170 A, 400 ms
35 A gL/gG fuse /
B25/C10 circuit
breaker
Maximum frequency range for
synchronization with bypass
5.3.2 d and
Maximum synchronized phase
5.3.2 e
error
Maximum slew-rate when
synchronizing
Overload capability
On inverter
5.3.2 l
Overload capability
On inverter, stored energy mode
30, 40, 60, 80, 90, 120, 160 kW
10 min 135% load
60 sec 155% load
300 ms >155% load
Overload capability
On bypass
5.3.2 m
Output current limitation, short-
circuit capability
345 A, 400 ms
35 A gL/gG fuse /
B50/C25 circuit
breaker
510 A, 400 ms
63 A gL/gG fuse /
B63/C32 circuit
breaker
670 A, 400 ms
63 A gL/gG fuse /
B100/C50 circuit
breaker
6.4.2.10.3
and Fault clearing capability
6.4.2.10.4
ESS MODE CHARACTERISTICS
Transfer time to double-
conversion
Mains available
Mains failure
Output voltage variation setting
Output frequency variation setting
No break
< 2 ms in normal transfer conditions, < 10 ms maximum
±10% of nominal voltage, default
±4 Hz, default
UPS locks into double-conversion mode when three power line disturbances have
forced the unit to double-conversion three times (user adjustable) within a one-hour
period (user adjustable).
UPS will stay on double-conversion for one hour (user adjustable), after which the unit
will automatically return to operate on ESS.
Storm detection
High Alert mode
Page 4 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
VMMS MODE CHARACTERISTICS
VMMS Availability
Available for multi-module 93PM UPS system, both between internal modules and
modules in an external parallel connected system.
When load level per module is less than 55%, VMMS will automatically optimise the
number of online modules for optimised operating efficiency.
The extra UPMs will be set to ready state mode, capable to transfer online in < 2ms
transfer time.
The load will be fed in double conversion mode the entire time, even during and after a
load step.
Number of redundant online UPMs (system wide), configurable.
System will automatically rotate the ready state UPMs.
Enabled by default, configurable.
VMMS operation
Redundancy level setting
UPM module rotation
BYPASS
Type of bypass
Static Bypass rating
Static Bypass voltage range
Transfer time break
Maintenance bypass
Backfeed protection
Rated conditional short-circuit
current, Icc Static bypass
Optional internal or integrated
Maintenance bypass
Internal static bypass ultra-rapid
fuse
Bypass fuse i
2
t value
Pre-arc i
2
t
Total clearing i
2
t
10 kA*
50 kVA100 kVA
Static
150 kVA200 kVA
220/380 V; 230/400 V; 240/415 V
tolerance -10% / +10% of rated voltage
No break
Option, internal or external
Integrated as standard
100 kA (internal ultra rapid fusing)
25 kA*10 kA*50 kA*
Option, integrated
sidecar or external
*using external protective fuse
Bussmann 160LETBussmann 550 A
170M4465
96 100 A
2
s
230 000 A
2
s
60 80 100
Bussmann 900 A 170M4419
1 100 A
2
s
16 000 A
2
s
155 000 A
2
s
850 000 A
2
s
90 120 150120 160 200kVA
External bypass protective fuse,
30 40 50
recommended rating
3x
63 A 80 A 100 A
125 A 160 A 200 A200 A 250 A 315 A250 A 315 A 400 A
Page 5 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004
Eaton 93PM 30‐200 kW UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040‐3
IEC 62040-3
Subclause
MODEL RATING (1.0 pf)
30-50 kW30-100 kW30-150 kW30-200 kW
BATTERY CHARACTERISTICS
5.4.2.2 dBattery technology
36 blocks, 216 cells
Battery quantity, internal batteries
per battery string
5.4.2.2 b
Battery quantity, external
batteries
12 V, VRLA
N/A
Note! Units with internal batteries only support 36 block string length
30, 40, 60, 80, 90, 120, 160 kW: 32 ... 40 blocks, 240 cells per battery string
50, 100, 150, 200 kW: 36 ... 40 blocks, 240 cells per battery string
Note! Never connect battery strings with different battery quantity and voltage in
parallel
432 V (36 blocks)
N/A
Battery voltage, internal batteries
5.4.2.2 c
Battery voltage, external batteries
5.4.2.2 o
5.4.2.2 q
5.4.2.2 r
Recharge profile
End of discharge voltage
Charging current at nominal load
Battery start
Temperature compensated
battery charging option
Alternative backup power
technologies
30, 40, 60, 80, 90, 120, 160 kW: 384 V (32 blocks) to 480 V (40 blocks)
50, 100, 150, 200 kW: 432 V (36 blocks) to 480 V (40 blocks)
Advanced Battery Management (ABM
®
) = 90% resting,10% charging (typical)
OR float charge
1.67 VPC to 1.75 VPC
Configurable or automatic (load adaptive)
Configurable 0…29 A per UPM
At > 40 kVA load per UPM, automatically limited to 16,5 A per UPM
Yes
Yes, standard for internal batteries
Yes, with Environmental Monitoring Probe (EMP) for external batteries
Wet cell batteries
NiCd batteries
Lithium-ion batteries
Supercapacitors
COMMUNICATION CIRCUITS
5.6Display
Standard connectivity ports
Optional
Complete list of indications and
interface devices
COMPLIANCE WITH STANDARDS
Safety Access
IEC 62040-1
Degree of protection
Electromagnetic Compatibility
IEC 62040-2
Immunity and EmissionsEMC Category C3
EMC Category C2
as option
EMC Category C3
Operator access area
IP20; protection against medium sized foreign matter (incl. finger)
IP21 available as option
Touchscreen LCD, 4x LEDs for notice and alarm, status LED light stripes
3x Mini-Slot ports for optional cards, Device USB and Host USB, RS-232 service port,
1 x relay output, 5 x building alarm inputs and a dedicated EPO
Mini-Slot cards: Web/SNMP/Modbus, Industrial relay card
See User’s Manual
Page 6 of 6
Updated: 21/02/2022
Document: Eaton 93PM 30-200 kW technical specification
The technical specification is subject to change without notice
Rev004