Eaton 198793

Eaton Moeller® series Rapid Link - Speed controllers, 4.3 A, 1.5

kW, Sensor input 4, 180/207 V DC, AS-Interface®, S-7.4 for 31

modules, HAN Q4/2, with manual override switch, with braking

resistance, STO (Safe Torque Off)

Allgemeine spezifikation

Product NameCatalog Number

Eaton Moeller® series Rapid Link Speed 198793

controller

Product Length/Depth

157 mm

Product HeightProduct Width

270 mm220 mm

Product WeightCertifications

3.6 kgIEC/EN 61800-5-1

UL 61800-5-1

CE

RoHS

UL approval

Catalog NotesEAN

3 fixed speeds

4

and 1

Model Code

potentiometer

RASP5-4401A31-412R110S1

speed

can be switched

over from U/f to

(vector) speed

control

Connection of

supply voltage

via adapter

cable on round

or flexible

Mains voltage - max

480 V

10.11 Short-circuit rating

busbar junction

Anmerkungen zur Anwendung

Diagnostics and

Generation change from RA-SP to RASP 4.0

reset on device

Generationentausch RAMO4 zu RAMO5

and via AS-

Generation change RAMO4 to RAMO5

integrated PTC

Firmware Update RASP 4.0

thermistor

Generation change from RA-MO to RAMO 4.0

monitoring and

Generationentausch RA-SP zu RASP4.0

Thermoclick with

safe isolation

Generation Change RASP4 to RASP5

optional: 4

Interface

Is the panel builder's responsibility. The specifications for the

switchgear must be observed.

Rated operational voltage

400 V AC, 3-phase

480 V AC, 3-phase

10.4 Clearances and creepage distances

Elektromagnetische Verträglichkeit (EMV)

sensor inputs

Meets the product standard's requirements.

Configuration to Rockwell PLC for Rapid Link

with M12-Y

Output at quadratic load at rated output voltage - max

adapter for

Configuration to Rockwell PLC Rapid Link 5

1.5 kW

Output voltage - max

500 V

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Ambient storage temperature - min

-40 °C

Mains voltage - min

380 V

Fitted with:

PC connection

Breaking resistance

Selector switch (Positions: REV - OFF - FWD)

Braking resistance

Internal DC link

IGBT inverter

Key switch position AUTO

stop and interlocked manual operation

Control unit

Manual override switch

PTC thermistor monitoring

Key switch position HAND

Thermo-click with safe isolation

Key switch position OFF/RESET

Output frequency - min

0 Hz

Kataloge

Installationsvideos

DE | Rapid Link 5

switchover to

Generationenwechsel RA-SP zu RASP5

creep speed

Generationswechsel RASP4 zu RASP5

optional: Faster

Generation Change RA-SP to RASP5

stop if external

Anschluss von Frequenzumrichtern an Generatornetze

24 V fails

Two sensor

Generationentausch RA-MO zu RAMO4.0

inputs through

Benutzerhandbücher

M12 sockets

MN040003_DE

(max. 150 mA)

for quick stop

MN034004_DE

and interlocked

Broschüren

manual

Rapid Link 5 - brochure

operation

DA-SW-drivesConnect - Installationshilfe

with AUTO -

DA-SW-Driver DX-CBL-PC-3M0

OFF/RESET -

HAND key

switches

with selector

switch REV -

DA-SW-USB Driver PC Cable DX-CBL-PC-1M5

DA-SW-drivesConnect - installation help

DA-SW-USB Driver DX-COM-STICK3-KIT

OFF - FWD

DA-SW-drivesConnect

Material handling applications - airports, warehouses and intra-logistics

eCAD model

Installationsanleitung

IL034085ZU

Two sensor inputs through M12 sockets (max. 150 mA) for quick

Starting current - max

200 %, IH, max. starting current (High Overload), For 2 seconds

every 20 seconds, Power section

Rated conditional short-circuit current (Iq)

10 kA

Ambient operating temperature - max

40 °C

Communication interface

AS-Interface

Assigned motor power at 115/120 V, 60 Hz, 1-phase

2 HP

Output frequency - max

500 Hz

Switching frequency

8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit

Features

Parameterization: drivesConnect

Parameterization: drivesConnect mobile (App)

Parameterization: Keypad

Diagnostics and reset on device and via AS-Interface

Parameterization: Fieldbus

Ambient operating temperature - min

-10 °C

Braking current

≤ 0.6 A (max. 6 A for 120 ms), Actuator for

external motor brake

Number of HW-interfaces (serial TTY)

0

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be

evaluated.

Nominal output current I2N

4.3 A

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be

evaluated.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be

evaluated.

Sortimentskatalog Antriebstechnik-DE

mCAD model

rasp5_

ramo5_

Zeichnungen

Product category

Speed controller

Radio interference class

C1: for conducted emissions only

C2, C3: depending on the motor cable length, the connected

load, and ambient conditions. External radio interference

suppression filters (optional) may be necessary.

Heat dissipation capacity Pdiss

0 W

Rated control voltage (Uc)

24 V DC (-15 %/+20 %, external via AS-Interface® plug)

180/207 V DC (external brake 50/60 Hz)

Assigned motor power at 460/480 V, 60 Hz, 3-phase

2 HP

Number of HW-interfaces (RS-422)

0

Mains current distortion

120 %

Protocol

ASI

AS-Interface profile cable: S-7.4 for 31 modules

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Overvoltage category

III

Degree of protection

IP65

NEMA 12

Ambient storage temperature - max

70 °C

Rated impulse withstand voltage (Uimp)

2000 V

Connection

Plug type: HAN Q4/2

Overload current

For 60 s every 600 s

At 40 °C

Functions

For actuation of motors with mechanical brake

1 potentiometer speed

STO (Safe Torque Off)

Brake chopper with braking resistance for dynamic braking

4-quadrant operation possible

3 fixed speeds

Output at linear load at rated output voltage - max

1.5 kW

Mains voltage tolerance

380 - 480 V (-10 %/+10 %, at 50/60 Hz)

Leakage current at ground IPE - max

3.5 mA

Converter type

U converter

10.2.2 Corrosion resistance

Meets the product standard's requirements.

Supply frequency

50/60 Hz

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Shock resistance

15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-

sinusoidal shock 11 ms, 1000 shocks per shaft

Application in domestic and commercial area permitted

Yes

Number of inputs (analog)

0

Number of phases (output)

3

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the

switchgear must be observed.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be

evaluated.

Number of HW-interfaces (RS-485)

1

Number of HW-interfaces (industrial ethernet)

0

Efficiency

98 % (η)

System configuration type

Center-point earthed star network (TN-S network)

AC voltage

Phase-earthed AC supply systems are not permitted.

10.8 Connections for external conductors

Is the panel builder's responsibility.

Switch-on threshold for the braking transistor

765 VDC

Protection

Finger and back-of-hand proof, Protection against direct contact

(BGV A3, VBG4)

Braking voltage

280/207 V DC -15 % / +10 %, Actuator for external motor brake

Application in industrial area permitted

Yes

Climatic proofing

< 95 %, no condensation

In accordance with IEC/EN 50178

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Overload current IL at 150% overload

6.5 A

Input current ILN at 150% overload

4.1 A

Number of HW-interfaces (RS-232)

0

Number of inputs (digital)

4

Current limitation

0.4 - 4.3 A, motor, main circuit

Adjustable, motor, main circuit

Cable length

C2 ≤ 5 m, maximum motor cable length

C3 ≤ 25 m, maximum motor cable length

C1

≤ 1 m, maximum motor cable length

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be

evaluated.

Mounting position

Vertical

Mains switch-on frequency

Maximum of one time every 60 seconds

10.13 Mechanical function

The device meets the requirements, provided the information in

the instruction leaflet (IL) is observed.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Heat dissipation per pole, current-dependent Pvid

0 W

Electromagnetic compatibility

1st and 2nd environments (according to EN 61800-3)

Resolution

0.1 Hz (Frequency resolution, setpoint value)

Assigned motor power at 460/480 V, 60 Hz

2 HP

Relative symmetric net voltage tolerance

10 %

Rated operational current (Ie)

4.3 A at 150% overload (at an operating frequency of 8 kHz and

an ambient air temperature of +40 °C)

Number of outputs (analog)

0

Rated operational power at 380/400 V, 50 Hz, 3-phase

1.5 kW

Number of HW-interfaces (USB)

0

Operating mode

U/f control

Synchronous reluctance motors

BLDC motors

PM and LSPM motors

Sensorless vector control (SLV)

Rated frequency - min

45 Hz

Delay time

< 10 ms, On-delay

< 10 ms, Off-delay

Number of outputs (digital)

0

Power consumption

46 W

10.2.3.2 Verification of resistance of insulating materials to

normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal

elect. effects

Meets the product standard's requirements.

Number of HW-interfaces (other)

1

Rated frequency - max

66 Hz

Vibration

Resistance: 6 Hz, Amplitude 0.15 mm

Resistance: 57 Hz, Amplitude transition frequency on

acceleration

Resistance: According to IEC/EN 60068-2-6

Resistance: 10 - 150 Hz, Oscillation frequency

Short-circuit protection (external output circuits)

Type 1 coordination via the power bus' feeder unit, Main circuit

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Braking torque

≤ 30 % (I/Ie)

Adjustable to 100 % (I/Ie), DC - Main circuit

Relative symmetric net frequency tolerance

10 %

10.10 Temperature rise

The panel builder is responsible for the temperature rise

calculation. Eaton will provide heat dissipation data for the

devices.

Number of HW-interfaces (parallel)

0

Assigned motor power at 230/240 V, 60 Hz, 1-phase

2 HP

Interfaces

Specification: S-7.4 (AS-Interface®)

Max. total power consumption from AS-Interface® power supply

unit (30 V): 190 mA

Number of slave addresses: 31 (AS-Interface®)

Number of phases (input)

3

Heat dissipation at current/speed

32.3 W at 25% current and 0% speed

33.2 W at 25% current and 50% speed

35.2 W at 50% current and 90% speed

36.2 W at 50% current and 0% speed

37.6 W at 50% current and 50% speed

46.3 W at 100% current and 90% speed

48.7 W at 100% current and 0% speed

48.7 W at 100% current and 50% speed

Number of interfaces (PROFINET)

0

Altitude

Max. 2000 m

Above 1000 m with 1 % performance reduction per 100 m

Eaton Konzern plc

Eaton-Haus

30 Pembroke-Straße

Dublin 4, Irland

© 2023 Eaton. Alle

Rechte vorbehalten.

Eaton ist eine eingetragene

Marke.

Alle anderen Warenzeichen sind

Eigentum ihrer jeweiligen

Besitzer.

/socialmedia

2024年10月20日发(作者:乐正代玉)

Eaton 198793

Eaton Moeller® series Rapid Link - Speed controllers, 4.3 A, 1.5

kW, Sensor input 4, 180/207 V DC, AS-Interface®, S-7.4 for 31

modules, HAN Q4/2, with manual override switch, with braking

resistance, STO (Safe Torque Off)

Allgemeine spezifikation

Product NameCatalog Number

Eaton Moeller® series Rapid Link Speed 198793

controller

Product Length/Depth

157 mm

Product HeightProduct Width

270 mm220 mm

Product WeightCertifications

3.6 kgIEC/EN 61800-5-1

UL 61800-5-1

CE

RoHS

UL approval

Catalog NotesEAN

3 fixed speeds

4

and 1

Model Code

potentiometer

RASP5-4401A31-412R110S1

speed

can be switched

over from U/f to

(vector) speed

control

Connection of

supply voltage

via adapter

cable on round

or flexible

Mains voltage - max

480 V

10.11 Short-circuit rating

busbar junction

Anmerkungen zur Anwendung

Diagnostics and

Generation change from RA-SP to RASP 4.0

reset on device

Generationentausch RAMO4 zu RAMO5

and via AS-

Generation change RAMO4 to RAMO5

integrated PTC

Firmware Update RASP 4.0

thermistor

Generation change from RA-MO to RAMO 4.0

monitoring and

Generationentausch RA-SP zu RASP4.0

Thermoclick with

safe isolation

Generation Change RASP4 to RASP5

optional: 4

Interface

Is the panel builder's responsibility. The specifications for the

switchgear must be observed.

Rated operational voltage

400 V AC, 3-phase

480 V AC, 3-phase

10.4 Clearances and creepage distances

Elektromagnetische Verträglichkeit (EMV)

sensor inputs

Meets the product standard's requirements.

Configuration to Rockwell PLC for Rapid Link

with M12-Y

Output at quadratic load at rated output voltage - max

adapter for

Configuration to Rockwell PLC Rapid Link 5

1.5 kW

Output voltage - max

500 V

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Ambient storage temperature - min

-40 °C

Mains voltage - min

380 V

Fitted with:

PC connection

Breaking resistance

Selector switch (Positions: REV - OFF - FWD)

Braking resistance

Internal DC link

IGBT inverter

Key switch position AUTO

stop and interlocked manual operation

Control unit

Manual override switch

PTC thermistor monitoring

Key switch position HAND

Thermo-click with safe isolation

Key switch position OFF/RESET

Output frequency - min

0 Hz

Kataloge

Installationsvideos

DE | Rapid Link 5

switchover to

Generationenwechsel RA-SP zu RASP5

creep speed

Generationswechsel RASP4 zu RASP5

optional: Faster

Generation Change RA-SP to RASP5

stop if external

Anschluss von Frequenzumrichtern an Generatornetze

24 V fails

Two sensor

Generationentausch RA-MO zu RAMO4.0

inputs through

Benutzerhandbücher

M12 sockets

MN040003_DE

(max. 150 mA)

for quick stop

MN034004_DE

and interlocked

Broschüren

manual

Rapid Link 5 - brochure

operation

DA-SW-drivesConnect - Installationshilfe

with AUTO -

DA-SW-Driver DX-CBL-PC-3M0

OFF/RESET -

HAND key

switches

with selector

switch REV -

DA-SW-USB Driver PC Cable DX-CBL-PC-1M5

DA-SW-drivesConnect - installation help

DA-SW-USB Driver DX-COM-STICK3-KIT

OFF - FWD

DA-SW-drivesConnect

Material handling applications - airports, warehouses and intra-logistics

eCAD model

Installationsanleitung

IL034085ZU

Two sensor inputs through M12 sockets (max. 150 mA) for quick

Starting current - max

200 %, IH, max. starting current (High Overload), For 2 seconds

every 20 seconds, Power section

Rated conditional short-circuit current (Iq)

10 kA

Ambient operating temperature - max

40 °C

Communication interface

AS-Interface

Assigned motor power at 115/120 V, 60 Hz, 1-phase

2 HP

Output frequency - max

500 Hz

Switching frequency

8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit

Features

Parameterization: drivesConnect

Parameterization: drivesConnect mobile (App)

Parameterization: Keypad

Diagnostics and reset on device and via AS-Interface

Parameterization: Fieldbus

Ambient operating temperature - min

-10 °C

Braking current

≤ 0.6 A (max. 6 A for 120 ms), Actuator for

external motor brake

Number of HW-interfaces (serial TTY)

0

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be

evaluated.

Nominal output current I2N

4.3 A

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be

evaluated.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be

evaluated.

Sortimentskatalog Antriebstechnik-DE

mCAD model

rasp5_

ramo5_

Zeichnungen

Product category

Speed controller

Radio interference class

C1: for conducted emissions only

C2, C3: depending on the motor cable length, the connected

load, and ambient conditions. External radio interference

suppression filters (optional) may be necessary.

Heat dissipation capacity Pdiss

0 W

Rated control voltage (Uc)

24 V DC (-15 %/+20 %, external via AS-Interface® plug)

180/207 V DC (external brake 50/60 Hz)

Assigned motor power at 460/480 V, 60 Hz, 3-phase

2 HP

Number of HW-interfaces (RS-422)

0

Mains current distortion

120 %

Protocol

ASI

AS-Interface profile cable: S-7.4 for 31 modules

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Overvoltage category

III

Degree of protection

IP65

NEMA 12

Ambient storage temperature - max

70 °C

Rated impulse withstand voltage (Uimp)

2000 V

Connection

Plug type: HAN Q4/2

Overload current

For 60 s every 600 s

At 40 °C

Functions

For actuation of motors with mechanical brake

1 potentiometer speed

STO (Safe Torque Off)

Brake chopper with braking resistance for dynamic braking

4-quadrant operation possible

3 fixed speeds

Output at linear load at rated output voltage - max

1.5 kW

Mains voltage tolerance

380 - 480 V (-10 %/+10 %, at 50/60 Hz)

Leakage current at ground IPE - max

3.5 mA

Converter type

U converter

10.2.2 Corrosion resistance

Meets the product standard's requirements.

Supply frequency

50/60 Hz

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Shock resistance

15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-

sinusoidal shock 11 ms, 1000 shocks per shaft

Application in domestic and commercial area permitted

Yes

Number of inputs (analog)

0

Number of phases (output)

3

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the

switchgear must be observed.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be

evaluated.

Number of HW-interfaces (RS-485)

1

Number of HW-interfaces (industrial ethernet)

0

Efficiency

98 % (η)

System configuration type

Center-point earthed star network (TN-S network)

AC voltage

Phase-earthed AC supply systems are not permitted.

10.8 Connections for external conductors

Is the panel builder's responsibility.

Switch-on threshold for the braking transistor

765 VDC

Protection

Finger and back-of-hand proof, Protection against direct contact

(BGV A3, VBG4)

Braking voltage

280/207 V DC -15 % / +10 %, Actuator for external motor brake

Application in industrial area permitted

Yes

Climatic proofing

< 95 %, no condensation

In accordance with IEC/EN 50178

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Overload current IL at 150% overload

6.5 A

Input current ILN at 150% overload

4.1 A

Number of HW-interfaces (RS-232)

0

Number of inputs (digital)

4

Current limitation

0.4 - 4.3 A, motor, main circuit

Adjustable, motor, main circuit

Cable length

C2 ≤ 5 m, maximum motor cable length

C3 ≤ 25 m, maximum motor cable length

C1

≤ 1 m, maximum motor cable length

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be

evaluated.

Mounting position

Vertical

Mains switch-on frequency

Maximum of one time every 60 seconds

10.13 Mechanical function

The device meets the requirements, provided the information in

the instruction leaflet (IL) is observed.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Heat dissipation per pole, current-dependent Pvid

0 W

Electromagnetic compatibility

1st and 2nd environments (according to EN 61800-3)

Resolution

0.1 Hz (Frequency resolution, setpoint value)

Assigned motor power at 460/480 V, 60 Hz

2 HP

Relative symmetric net voltage tolerance

10 %

Rated operational current (Ie)

4.3 A at 150% overload (at an operating frequency of 8 kHz and

an ambient air temperature of +40 °C)

Number of outputs (analog)

0

Rated operational power at 380/400 V, 50 Hz, 3-phase

1.5 kW

Number of HW-interfaces (USB)

0

Operating mode

U/f control

Synchronous reluctance motors

BLDC motors

PM and LSPM motors

Sensorless vector control (SLV)

Rated frequency - min

45 Hz

Delay time

< 10 ms, On-delay

< 10 ms, Off-delay

Number of outputs (digital)

0

Power consumption

46 W

10.2.3.2 Verification of resistance of insulating materials to

normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal

elect. effects

Meets the product standard's requirements.

Number of HW-interfaces (other)

1

Rated frequency - max

66 Hz

Vibration

Resistance: 6 Hz, Amplitude 0.15 mm

Resistance: 57 Hz, Amplitude transition frequency on

acceleration

Resistance: According to IEC/EN 60068-2-6

Resistance: 10 - 150 Hz, Oscillation frequency

Short-circuit protection (external output circuits)

Type 1 coordination via the power bus' feeder unit, Main circuit

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Braking torque

≤ 30 % (I/Ie)

Adjustable to 100 % (I/Ie), DC - Main circuit

Relative symmetric net frequency tolerance

10 %

10.10 Temperature rise

The panel builder is responsible for the temperature rise

calculation. Eaton will provide heat dissipation data for the

devices.

Number of HW-interfaces (parallel)

0

Assigned motor power at 230/240 V, 60 Hz, 1-phase

2 HP

Interfaces

Specification: S-7.4 (AS-Interface®)

Max. total power consumption from AS-Interface® power supply

unit (30 V): 190 mA

Number of slave addresses: 31 (AS-Interface®)

Number of phases (input)

3

Heat dissipation at current/speed

32.3 W at 25% current and 0% speed

33.2 W at 25% current and 50% speed

35.2 W at 50% current and 90% speed

36.2 W at 50% current and 0% speed

37.6 W at 50% current and 50% speed

46.3 W at 100% current and 90% speed

48.7 W at 100% current and 0% speed

48.7 W at 100% current and 50% speed

Number of interfaces (PROFINET)

0

Altitude

Max. 2000 m

Above 1000 m with 1 % performance reduction per 100 m

Eaton Konzern plc

Eaton-Haus

30 Pembroke-Straße

Dublin 4, Irland

© 2023 Eaton. Alle

Rechte vorbehalten.

Eaton ist eine eingetragene

Marke.

Alle anderen Warenzeichen sind

Eigentum ihrer jeweiligen

Besitzer.

/socialmedia

发布评论

评论列表 (0)

  1. 暂无评论