最新消息: USBMI致力于为网友们分享Windows、安卓、IOS等主流手机系统相关的资讯以及评测、同时提供相关教程、应用、软件下载等服务。

阿尔лен-布雷利(Allen-Bradley)PowerFlex 4和40 AC驱动器产品概述说

IT圈 admin 33浏览 0评论

2024年7月31日发(作者:战兰娜)

PowerFlex 4 and 40 AC Drives

Product Overview

Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4 and

40 AC drives are the smallest and most cost-effective members of the PowerFlex® family of drives. Available in power ratings

from 0.2 to 11 kW (0.25 to 15 HP) and in voltage classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed

to meet global OEM and end-user demands for flexibility, space savings, ease of use and are cost-effective alternatives for

speed control of applications such as machine tools, fans, pumps and conveyors and material handling systems

Reference Materials

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:

Title

PowerFlex 4 User Manual

PowerFlex 40 User Manual

Wiring and Grounding Guidelines for PWM AC Drives

Preventive Maintenance of Industrial Control and Drive System Equipment

Safety Guidelines for the Application, Installation and Maintenance of Solid State Control

Publication

22A-UM001

22B-UM001

DRIVES-IN001

DRIVES-TD001

SGI-1.1

Online

/literature

For other information, contact Allen-Bradley Drives Technical Support:

Title

Allen-Bradley Drives Technical Support

Online

/support/abdrives

Shaded areas are applicable to PowerFlex 40 only.

2Rockwell Automation Publication 22-TD001I-EN-P - June 2013

PowerFlex 4 and 40 AC Drives

Use the chart below to assist in determining which product is most appropriate for an application.

Feature

Catalog Reference22A

(1.1) 1.5 HP/115V, 1ø

(2.2) 3 HP/230V, 1ø

(3.7) 5 HP/230V, 3ø

(3.7) 5 HP/460V, 3ø

150% for 60 seconds

200% for 3 seconds

Internal - 1ø, 230V

External - All 1ø, 115V and 3ø Ratings

V/Hz

Not available on no brake models.

4

2…16 kHz

Maximum (kW)HP Rating/Input Voltage

Overload Capacity

IP30, NEMA/UL Type 1 Option

IP66, NEMA/UL Type 4X/12 (Indoor)

EMC Filtering

DIN Rail Mounting Standard

Integral Keypad with Speed Pot

Keypad - Remote LCD

Keypad CopyCat Function

Control Type

Internal DB Transistor

Preset Speeds

Carrier Frequency

Skip Frequency

Process Control Loop

StepLogic Functionality

Timer/Counter Functions

Control Voltage

Discrete Inputs

Analog Input - Unipolar

Analog Input - Bipolar

Analog Response

Relay Output

Digital/Optocoupler Output

Analog Output

Integral RS485

RS232 (Requires use of Serial Converter Module)

BACnet

ControlNet

DeviceNet

EtherNet/IP

LonWorks

PROFIBUS DP

(1)With 22-XCOMM-DC-BASE External mounting kit.

(2)Frame B only.

(3)When using bipolar input, the 0…10V unipolar input cannot be used.

22B

(1.1) 1.5 HP/115V, 1ø

(2.2) 3 HP/230V, 1ø

(7.5) 10 HP/230V, 3ø

(11.0) 15 HP/460V, 3ø

(11.0) 15 HP/600V, 3ø

150% for 60 seconds

200% for 3 seconds

(2)

Internal - 1ø, 230V

External - All 1ø, 115V and 3ø Ratings

(Through 5 HP)

Sensorless Vector & V/Hz

8

2…16 kHz

(PID)

24V sink/source

3 fixed for START/STOP/REV

4 fully programmable

2

(0…10V and 4…20 mA)

1

(+/- 10V)

(3)

100 Hz (10 ms)

1 - N.O./N.C. dry contact

2

(0…10V or 4…20 mA)

24V sink/source

3 fixed for START/STOP/REV

2 fully programmable

1

(0…10V or 4…20 mA)

2 Hz (500 ms)

1 - N.O/N.C. dry contact

(1)

(1)

(1)

(1)

(1)

(1)

Rockwell Automation Publication 22-TD001I-EN-P - June 20137

PowerFlex 4 and 40 AC Drives

Catalog Number Explanation

Position

1-3456-8910111213-14

22A

a

A

b

a

Drive

1P5

c

N

d

c4

Rating

1

e

1

f

4

g

e

HIM

Code

1

AA

h

Code

22A

22B

Type

PowerFlex 4

PowerFlex 40

Code

1P4

2P3

4P0

6P0

Ph.

1

1

3

3

3

010

012

017

024

380-480V Three-Phase Input

Amps

1.4

2.3

4.0

6.0

10.5

12

17

24

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10)

11 (15)

Interface Module

Fixed Keypad

f

Emission Class

Code

0

1

Rating

Not Filtered

Filtered

b

Voltage Rating

Code

V

A

B

D

E

Voltage

120V ac

240V ac

240V ac

480V ac

600V ac

g

Brake IGBT

Code

3

4

Description

Without Brake

With Brake

c5

Rating

460-600V Three-Phase Input

Code

1P7

3P0

4P2

6P6

9P9

012

019

Amps

1.7

3.0

4.2

6.6

9.9

12

19

kW (Hp)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10)

11 (15)

c1

Rating

100-120V Single-Phase Input

Code

2P3

5P0

6P0

Amps

2.3

5.0

6.0

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.1 (1.5)

h

Optional

Code

AA through ZZ

Purpose

Reserved for custom

firmware

c2

Rating

200-240V Single-Phase Input

Code

2P3

5P0

8P0

012

Amps

2.3

5.0

8.0

12

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

d

Enclosure

Code

C

F

Enclosure

IP66, NEMA/UL Type 4X *

Flange Mount - IP20, NEMA/UL

Type Open

Replacement Plate Drive - IP20,

NEMA/UL Type Open

Contact factory for ordering

information.

Panel Mount - IP20, NEMA/UL Type

Open

* Check availability before ordering.

c3

Rating

200-240V Three-Phase Input

Code

2P3

5P0

8P0

012

017

024

033

Amps

2.3

5.0

8.0

12

17.5

24

33

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

5.5 (7.5)

7.5 (10)

H

N

8Rockwell Automation Publication 22-TD001I-EN-P - June 2013

PowerFlex 4 and 40 AC Drives

Input/Output Ratings

Approvals

Control Inputs

Output Frequency:

Efficiency:

PowerFlex 4: 0…240 Hz (Programmable)

PowerFlex 40: 0…400 Hz (Programmable)

97.5% (Typical)

CSA C 22.2 No. 14EN 61800-3

LV Directive 73/23/EEC

LV: EN 50178, EN 60204

EMC Directive 89/336/EEC

EMC: EN 61800-3

U

L

UL508C

C

U

L

Control Output –

Programmable Output

(form C relay)

Fuses and Circuit Breakers

Protective Features

Digital

SRC (Source) Mode:

SNK (Sink) Mode:

Analog

4…20 mA Analog:

0…10V DC Analog:

External Pot:

Resistive Rating

Opto Outputs (PF 40):

Analog Outputs (PF 40):

Inductive Rating

Opto Outputs (PF 40):

Analog Outputs (PF 40):

Recommended Fuse Type:

Recommended Circuit Breakers:

Motor Protection:

Overcurrent:

Control Ride Through:

Faultless Power Ride Through:

Over Voltage:

Input Current = 6 mA

18…24V = On, 0…6V = Off

0…6V = On, 18…24V = Off

Dynamic Braking

Environment

Control

Electrical

250 ohm input impedance

100k ohm input impedance

1…10k ohms, 2 Watt minimum

3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC

30V DC, 50 mA

10-bit, 0…10V, 1k ohm minimum

0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

Non-inductive

10 bit, 4…20 mA, 525 ohm maximum

UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

HMCP circuit breaker or equivalent.

I

2

t Overload Protection, 150% for 60 sec., 200% for 3 sec. (provides Class 10 protection)

200% hardware limit, 300% instantaneous fault

Minimum Ride Through is 0.5 sec. - typical value is 2 seconds

100 milliseconds

100…120V AC Input – Trip occurs at 405V DC bus voltage ( = 150V AC incoming line)

200…240V AC Input – Trip occurs at 405V DC bus voltage ( = 290V AC incoming line)

380…480V AC Input – Trip occurs at 810V DC bus voltage ( = 575V AC incoming line)

460…600V AC Input (PF 40) – Trip occurs at 1005V DC bus voltage ( = 711V AC incoming line)

Under Voltage:

100…120V AC Input – Trip occurs at 210V DC bus voltage ( = 75V AC incoming line)

200…240V AC Input – Trip occurs at 210V DC bus voltage ( = 150V AC incoming line)

380…480V AC Input – Trip occurs at 390V DC bus voltage ( = 275V AC incoming line)

460…600V AC Input (PF 40)

If P042 = 1 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);

If P042 = 0 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)

Internal brake IGBT included with all ratings except No Brake drives (Cat. Nos. 22A-AxPxN103 or 22A-AxPxN113). Refer to page 11 for ordering information.

1000 m (3300 ft.) maximum without derating

Altitude:

IP20, NEMA/UL Type Open: –10 to 50 degrees C (14 to 122 degrees F)

Ambient Operating Temperature:

IP30, NEMA/UL Type 1: –10 to 40 degrees C (14 to 104 degrees F)

IP66, NEMA/UL Type 4X/12 (PF 40): –10 to 40 degrees C (14 to 104 degrees F)

Fan, all drive ratings

Cooling Method:

–40 to 85 degrees C (–40 to 185 degrees F)

Storage Temperature:

Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas,

Atmosphere:

vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not

be exposed to a corrosive atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11ms duration (±1.0ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

2…16 kHz. Drive rating based on 4 kHz.

Carrier Frequency:

Digital Input: Within ±0.05% of set output frequency.

Frequency Accuracy:

Analog Input: Within 0.5% of maximum output frequency.

Analog Output (PF 40): ±2% of full scale, 10-bit resolution.

Open Loop with Slip Compensation: ±2% of base speed across a 40:1 speed range.

Speed Regulation:

(PF 40): 1% of base speed across a 60:1 speed range.

Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.

Stop Modes:

Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1

Accel/Decel:

second increments.

150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds.

Intermittent Overload:

Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection

Electronic Motor Overload Protection:

according to NEC article 430.126 (A) (2). UL 508C File 29572.

120V, 200…240V, 380…480V, 460…600V: ±10%

Voltage Tolerance:

48…63 Hz

Frequency Tolerance:

0.98 across entire speed range

Displacement Power Factor:

100,000 Amps symmetrical

Maximum Short Circuit Rating:

Rockwell Automation Publication 22-TD001I-EN-P - June 201321

PowerFlex 4 and 40 AC Drives

Product Dimensions

Approximate Dimensions

A

D

C

F

EB

G

5.5 (0.22)

Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).

Frame

A

B

C

A

80 (3.15)

100 (3.94)

130 (5.1)

B

(1)

152 (5.98)

180 (7.09)

260 (10.2)

C

136 (5.35)

136 (5.35)

180 (7.1)

D

67 (2.64)

87 (3.43)

116 (4.57)

E

140 (5.51

168 (6.61)

246 (9.7)

F

59.3 (2.33)

87.4 (3.44)

G

(2)

185 (7.28)

213 (8.39)

320 (12.6)

Shipping Weight

1.4 (3.1)

2.2 (4.9)

4.3 (9.5)

(1)Overall height of standard IP 20/Open Type Drive.

(2)Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed.

Ratings are in kW and (HP).

PowerFlex 4 — Frame

A

120V AC – 1-Phase

0.2 (0.25)

0.4(0.5)

240V AC – 1-Phase

0.2 (0.25)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

240V AC – 3-Phase

0.2 (0.25)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

240V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

5.5 (7.5)

7.5 (10.0)

480V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10.0)

11.0 (15.0)

480V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

600V AC – 3-Phase

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10.0)

11.0 (15.0)

B0.75 (1.0)

1.1 (1.5)

120V AC – 1-Phase

0.4 (0.5)

0.75 (1.0)

1.1 (1.5)

PowerFlex 40 — Frame

B

240V AC – 1-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

C2.2 (3.0)

Shaded areas are applicable to PowerFlex 40 only.

Rockwell Automation Publication 22-TD001I-EN-P - June 201325

2024年7月31日发(作者:战兰娜)

PowerFlex 4 and 40 AC Drives

Product Overview

Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4 and

40 AC drives are the smallest and most cost-effective members of the PowerFlex® family of drives. Available in power ratings

from 0.2 to 11 kW (0.25 to 15 HP) and in voltage classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed

to meet global OEM and end-user demands for flexibility, space savings, ease of use and are cost-effective alternatives for

speed control of applications such as machine tools, fans, pumps and conveyors and material handling systems

Reference Materials

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:

Title

PowerFlex 4 User Manual

PowerFlex 40 User Manual

Wiring and Grounding Guidelines for PWM AC Drives

Preventive Maintenance of Industrial Control and Drive System Equipment

Safety Guidelines for the Application, Installation and Maintenance of Solid State Control

Publication

22A-UM001

22B-UM001

DRIVES-IN001

DRIVES-TD001

SGI-1.1

Online

/literature

For other information, contact Allen-Bradley Drives Technical Support:

Title

Allen-Bradley Drives Technical Support

Online

/support/abdrives

Shaded areas are applicable to PowerFlex 40 only.

2Rockwell Automation Publication 22-TD001I-EN-P - June 2013

PowerFlex 4 and 40 AC Drives

Use the chart below to assist in determining which product is most appropriate for an application.

Feature

Catalog Reference22A

(1.1) 1.5 HP/115V, 1ø

(2.2) 3 HP/230V, 1ø

(3.7) 5 HP/230V, 3ø

(3.7) 5 HP/460V, 3ø

150% for 60 seconds

200% for 3 seconds

Internal - 1ø, 230V

External - All 1ø, 115V and 3ø Ratings

V/Hz

Not available on no brake models.

4

2…16 kHz

Maximum (kW)HP Rating/Input Voltage

Overload Capacity

IP30, NEMA/UL Type 1 Option

IP66, NEMA/UL Type 4X/12 (Indoor)

EMC Filtering

DIN Rail Mounting Standard

Integral Keypad with Speed Pot

Keypad - Remote LCD

Keypad CopyCat Function

Control Type

Internal DB Transistor

Preset Speeds

Carrier Frequency

Skip Frequency

Process Control Loop

StepLogic Functionality

Timer/Counter Functions

Control Voltage

Discrete Inputs

Analog Input - Unipolar

Analog Input - Bipolar

Analog Response

Relay Output

Digital/Optocoupler Output

Analog Output

Integral RS485

RS232 (Requires use of Serial Converter Module)

BACnet

ControlNet

DeviceNet

EtherNet/IP

LonWorks

PROFIBUS DP

(1)With 22-XCOMM-DC-BASE External mounting kit.

(2)Frame B only.

(3)When using bipolar input, the 0…10V unipolar input cannot be used.

22B

(1.1) 1.5 HP/115V, 1ø

(2.2) 3 HP/230V, 1ø

(7.5) 10 HP/230V, 3ø

(11.0) 15 HP/460V, 3ø

(11.0) 15 HP/600V, 3ø

150% for 60 seconds

200% for 3 seconds

(2)

Internal - 1ø, 230V

External - All 1ø, 115V and 3ø Ratings

(Through 5 HP)

Sensorless Vector & V/Hz

8

2…16 kHz

(PID)

24V sink/source

3 fixed for START/STOP/REV

4 fully programmable

2

(0…10V and 4…20 mA)

1

(+/- 10V)

(3)

100 Hz (10 ms)

1 - N.O./N.C. dry contact

2

(0…10V or 4…20 mA)

24V sink/source

3 fixed for START/STOP/REV

2 fully programmable

1

(0…10V or 4…20 mA)

2 Hz (500 ms)

1 - N.O/N.C. dry contact

(1)

(1)

(1)

(1)

(1)

(1)

Rockwell Automation Publication 22-TD001I-EN-P - June 20137

PowerFlex 4 and 40 AC Drives

Catalog Number Explanation

Position

1-3456-8910111213-14

22A

a

A

b

a

Drive

1P5

c

N

d

c4

Rating

1

e

1

f

4

g

e

HIM

Code

1

AA

h

Code

22A

22B

Type

PowerFlex 4

PowerFlex 40

Code

1P4

2P3

4P0

6P0

Ph.

1

1

3

3

3

010

012

017

024

380-480V Three-Phase Input

Amps

1.4

2.3

4.0

6.0

10.5

12

17

24

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10)

11 (15)

Interface Module

Fixed Keypad

f

Emission Class

Code

0

1

Rating

Not Filtered

Filtered

b

Voltage Rating

Code

V

A

B

D

E

Voltage

120V ac

240V ac

240V ac

480V ac

600V ac

g

Brake IGBT

Code

3

4

Description

Without Brake

With Brake

c5

Rating

460-600V Three-Phase Input

Code

1P7

3P0

4P2

6P6

9P9

012

019

Amps

1.7

3.0

4.2

6.6

9.9

12

19

kW (Hp)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10)

11 (15)

c1

Rating

100-120V Single-Phase Input

Code

2P3

5P0

6P0

Amps

2.3

5.0

6.0

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.1 (1.5)

h

Optional

Code

AA through ZZ

Purpose

Reserved for custom

firmware

c2

Rating

200-240V Single-Phase Input

Code

2P3

5P0

8P0

012

Amps

2.3

5.0

8.0

12

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

d

Enclosure

Code

C

F

Enclosure

IP66, NEMA/UL Type 4X *

Flange Mount - IP20, NEMA/UL

Type Open

Replacement Plate Drive - IP20,

NEMA/UL Type Open

Contact factory for ordering

information.

Panel Mount - IP20, NEMA/UL Type

Open

* Check availability before ordering.

c3

Rating

200-240V Three-Phase Input

Code

2P3

5P0

8P0

012

017

024

033

Amps

2.3

5.0

8.0

12

17.5

24

33

kW (Hp)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

5.5 (7.5)

7.5 (10)

H

N

8Rockwell Automation Publication 22-TD001I-EN-P - June 2013

PowerFlex 4 and 40 AC Drives

Input/Output Ratings

Approvals

Control Inputs

Output Frequency:

Efficiency:

PowerFlex 4: 0…240 Hz (Programmable)

PowerFlex 40: 0…400 Hz (Programmable)

97.5% (Typical)

CSA C 22.2 No. 14EN 61800-3

LV Directive 73/23/EEC

LV: EN 50178, EN 60204

EMC Directive 89/336/EEC

EMC: EN 61800-3

U

L

UL508C

C

U

L

Control Output –

Programmable Output

(form C relay)

Fuses and Circuit Breakers

Protective Features

Digital

SRC (Source) Mode:

SNK (Sink) Mode:

Analog

4…20 mA Analog:

0…10V DC Analog:

External Pot:

Resistive Rating

Opto Outputs (PF 40):

Analog Outputs (PF 40):

Inductive Rating

Opto Outputs (PF 40):

Analog Outputs (PF 40):

Recommended Fuse Type:

Recommended Circuit Breakers:

Motor Protection:

Overcurrent:

Control Ride Through:

Faultless Power Ride Through:

Over Voltage:

Input Current = 6 mA

18…24V = On, 0…6V = Off

0…6V = On, 18…24V = Off

Dynamic Braking

Environment

Control

Electrical

250 ohm input impedance

100k ohm input impedance

1…10k ohms, 2 Watt minimum

3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC

30V DC, 50 mA

10-bit, 0…10V, 1k ohm minimum

0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

Non-inductive

10 bit, 4…20 mA, 525 ohm maximum

UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

HMCP circuit breaker or equivalent.

I

2

t Overload Protection, 150% for 60 sec., 200% for 3 sec. (provides Class 10 protection)

200% hardware limit, 300% instantaneous fault

Minimum Ride Through is 0.5 sec. - typical value is 2 seconds

100 milliseconds

100…120V AC Input – Trip occurs at 405V DC bus voltage ( = 150V AC incoming line)

200…240V AC Input – Trip occurs at 405V DC bus voltage ( = 290V AC incoming line)

380…480V AC Input – Trip occurs at 810V DC bus voltage ( = 575V AC incoming line)

460…600V AC Input (PF 40) – Trip occurs at 1005V DC bus voltage ( = 711V AC incoming line)

Under Voltage:

100…120V AC Input – Trip occurs at 210V DC bus voltage ( = 75V AC incoming line)

200…240V AC Input – Trip occurs at 210V DC bus voltage ( = 150V AC incoming line)

380…480V AC Input – Trip occurs at 390V DC bus voltage ( = 275V AC incoming line)

460…600V AC Input (PF 40)

If P042 = 1 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);

If P042 = 0 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)

Internal brake IGBT included with all ratings except No Brake drives (Cat. Nos. 22A-AxPxN103 or 22A-AxPxN113). Refer to page 11 for ordering information.

1000 m (3300 ft.) maximum without derating

Altitude:

IP20, NEMA/UL Type Open: –10 to 50 degrees C (14 to 122 degrees F)

Ambient Operating Temperature:

IP30, NEMA/UL Type 1: –10 to 40 degrees C (14 to 104 degrees F)

IP66, NEMA/UL Type 4X/12 (PF 40): –10 to 40 degrees C (14 to 104 degrees F)

Fan, all drive ratings

Cooling Method:

–40 to 85 degrees C (–40 to 185 degrees F)

Storage Temperature:

Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas,

Atmosphere:

vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not

be exposed to a corrosive atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11ms duration (±1.0ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

2…16 kHz. Drive rating based on 4 kHz.

Carrier Frequency:

Digital Input: Within ±0.05% of set output frequency.

Frequency Accuracy:

Analog Input: Within 0.5% of maximum output frequency.

Analog Output (PF 40): ±2% of full scale, 10-bit resolution.

Open Loop with Slip Compensation: ±2% of base speed across a 40:1 speed range.

Speed Regulation:

(PF 40): 1% of base speed across a 60:1 speed range.

Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.

Stop Modes:

Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1

Accel/Decel:

second increments.

150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds.

Intermittent Overload:

Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection

Electronic Motor Overload Protection:

according to NEC article 430.126 (A) (2). UL 508C File 29572.

120V, 200…240V, 380…480V, 460…600V: ±10%

Voltage Tolerance:

48…63 Hz

Frequency Tolerance:

0.98 across entire speed range

Displacement Power Factor:

100,000 Amps symmetrical

Maximum Short Circuit Rating:

Rockwell Automation Publication 22-TD001I-EN-P - June 201321

PowerFlex 4 and 40 AC Drives

Product Dimensions

Approximate Dimensions

A

D

C

F

EB

G

5.5 (0.22)

Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).

Frame

A

B

C

A

80 (3.15)

100 (3.94)

130 (5.1)

B

(1)

152 (5.98)

180 (7.09)

260 (10.2)

C

136 (5.35)

136 (5.35)

180 (7.1)

D

67 (2.64)

87 (3.43)

116 (4.57)

E

140 (5.51

168 (6.61)

246 (9.7)

F

59.3 (2.33)

87.4 (3.44)

G

(2)

185 (7.28)

213 (8.39)

320 (12.6)

Shipping Weight

1.4 (3.1)

2.2 (4.9)

4.3 (9.5)

(1)Overall height of standard IP 20/Open Type Drive.

(2)Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed.

Ratings are in kW and (HP).

PowerFlex 4 — Frame

A

120V AC – 1-Phase

0.2 (0.25)

0.4(0.5)

240V AC – 1-Phase

0.2 (0.25)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

240V AC – 3-Phase

0.2 (0.25)

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

240V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

5.5 (7.5)

7.5 (10.0)

480V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10.0)

11.0 (15.0)

480V AC – 3-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

3.7 (5.0)

600V AC – 3-Phase

0.75 (1.0)

1.5 (2.0)

2.2 (3.0)

4.0 (5.0)

5.5 (7.5)

7.5 (10.0)

11.0 (15.0)

B0.75 (1.0)

1.1 (1.5)

120V AC – 1-Phase

0.4 (0.5)

0.75 (1.0)

1.1 (1.5)

PowerFlex 40 — Frame

B

240V AC – 1-Phase

0.4 (0.5)

0.75 (1.0)

1.5 (2.0)

C2.2 (3.0)

Shaded areas are applicable to PowerFlex 40 only.

Rockwell Automation Publication 22-TD001I-EN-P - June 201325

发布评论

评论列表 (0)

  1. 暂无评论