2024年7月31日发(作者:战兰娜)
PowerFlex 4 and 40 AC Drives
Product Overview
Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4 and
40 AC drives are the smallest and most cost-effective members of the PowerFlex® family of drives. Available in power ratings
from 0.2 to 11 kW (0.25 to 15 HP) and in voltage classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed
to meet global OEM and end-user demands for flexibility, space savings, ease of use and are cost-effective alternatives for
speed control of applications such as machine tools, fans, pumps and conveyors and material handling systems
Reference Materials
For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:
Title
PowerFlex 4 User Manual
PowerFlex 40 User Manual
Wiring and Grounding Guidelines for PWM AC Drives
Preventive Maintenance of Industrial Control and Drive System Equipment
Safety Guidelines for the Application, Installation and Maintenance of Solid State Control
Publication
22A-UM001
22B-UM001
DRIVES-IN001
DRIVES-TD001
SGI-1.1
Online
/literature
For other information, contact Allen-Bradley Drives Technical Support:
Title
Allen-Bradley Drives Technical Support
Online
/support/abdrives
Shaded areas are applicable to PowerFlex 40 only.
2Rockwell Automation Publication 22-TD001I-EN-P - June 2013
PowerFlex 4 and 40 AC Drives
Use the chart below to assist in determining which product is most appropriate for an application.
Feature
Catalog Reference22A
(1.1) 1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(3.7) 5 HP/230V, 3ø
(3.7) 5 HP/460V, 3ø
150% for 60 seconds
200% for 3 seconds
●
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●
●
●
●
V/Hz
●
Not available on no brake models.
4
2…16 kHz
Maximum (kW)HP Rating/Input Voltage
Overload Capacity
IP30, NEMA/UL Type 1 Option
IP66, NEMA/UL Type 4X/12 (Indoor)
EMC Filtering
DIN Rail Mounting Standard
Integral Keypad with Speed Pot
Keypad - Remote LCD
Keypad CopyCat Function
Control Type
Internal DB Transistor
Preset Speeds
Carrier Frequency
Skip Frequency
Process Control Loop
StepLogic Functionality
Timer/Counter Functions
Control Voltage
Discrete Inputs
Analog Input - Unipolar
Analog Input - Bipolar
Analog Response
Relay Output
Digital/Optocoupler Output
Analog Output
Integral RS485
RS232 (Requires use of Serial Converter Module)
BACnet
ControlNet
DeviceNet
EtherNet/IP
LonWorks
PROFIBUS DP
(1)With 22-XCOMM-DC-BASE External mounting kit.
(2)Frame B only.
(3)When using bipolar input, the 0…10V unipolar input cannot be used.
22B
(1.1) 1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(7.5) 10 HP/230V, 3ø
(11.0) 15 HP/460V, 3ø
(11.0) 15 HP/600V, 3ø
150% for 60 seconds
200% for 3 seconds
●
●
(2)
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●
(Through 5 HP)
●
●
●
Sensorless Vector & V/Hz
●
8
2…16 kHz
●
●
(PID)
●
●
24V sink/source
3 fixed for START/STOP/REV
4 fully programmable
2
(0…10V and 4…20 mA)
1
(+/- 10V)
(3)
100 Hz (10 ms)
1 - N.O./N.C. dry contact
2
●
(0…10V or 4…20 mA)
●
●
●
●
●
●
●
●
24V sink/source
3 fixed for START/STOP/REV
2 fully programmable
1
(0…10V or 4…20 mA)
2 Hz (500 ms)
1 - N.O/N.C. dry contact
●
●
●
(1)
●
(1)
●
(1)
●
(1)
●
(1)
●
(1)
Rockwell Automation Publication 22-TD001I-EN-P - June 20137
PowerFlex 4 and 40 AC Drives
Catalog Number Explanation
Position
1-3456-8910111213-14
22A
–
a
A
b
a
Drive
1P5
c
N
d
c4
Rating
1
e
1
f
4
g
e
HIM
Code
1
AA
h
Code
22A
22B
Type
PowerFlex 4
PowerFlex 40
Code
1P4
2P3
4P0
6P0
Ph.
1
1
3
3
3
010
012
017
024
380-480V Three-Phase Input
Amps
1.4
2.3
4.0
6.0
10.5
12
17
24
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
Interface Module
Fixed Keypad
f
Emission Class
Code
0
1
Rating
Not Filtered
Filtered
b
Voltage Rating
Code
V
A
B
D
E
Voltage
120V ac
240V ac
240V ac
480V ac
600V ac
g
Brake IGBT
Code
3
4
Description
Without Brake
With Brake
c5
Rating
460-600V Three-Phase Input
Code
1P7
3P0
4P2
6P6
9P9
012
019
Amps
1.7
3.0
4.2
6.6
9.9
12
19
kW (Hp)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
c1
Rating
100-120V Single-Phase Input
Code
2P3
5P0
6P0
Amps
2.3
5.0
6.0
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
h
Optional
Code
AA through ZZ
Purpose
Reserved for custom
firmware
c2
Rating
200-240V Single-Phase Input
Code
2P3
5P0
8P0
012
Amps
2.3
5.0
8.0
12
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
d
Enclosure
Code
C
F
Enclosure
IP66, NEMA/UL Type 4X *
Flange Mount - IP20, NEMA/UL
Type Open
Replacement Plate Drive - IP20,
NEMA/UL Type Open
Contact factory for ordering
information.
Panel Mount - IP20, NEMA/UL Type
Open
* Check availability before ordering.
c3
Rating
200-240V Three-Phase Input
Code
2P3
5P0
8P0
012
017
024
033
Amps
2.3
5.0
8.0
12
17.5
24
33
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10)
H
N
8Rockwell Automation Publication 22-TD001I-EN-P - June 2013
PowerFlex 4 and 40 AC Drives
Input/Output Ratings
Approvals
Control Inputs
Output Frequency:
Efficiency:
PowerFlex 4: 0…240 Hz (Programmable)
PowerFlex 40: 0…400 Hz (Programmable)
97.5% (Typical)
CSA C 22.2 No. 14EN 61800-3
LV Directive 73/23/EEC
LV: EN 50178, EN 60204
EMC Directive 89/336/EEC
EMC: EN 61800-3
U
L
UL508C
C
U
L
Control Output –
Programmable Output
(form C relay)
Fuses and Circuit Breakers
Protective Features
Digital
SRC (Source) Mode:
SNK (Sink) Mode:
Analog
4…20 mA Analog:
0…10V DC Analog:
External Pot:
Resistive Rating
Opto Outputs (PF 40):
Analog Outputs (PF 40):
Inductive Rating
Opto Outputs (PF 40):
Analog Outputs (PF 40):
Recommended Fuse Type:
Recommended Circuit Breakers:
Motor Protection:
Overcurrent:
Control Ride Through:
Faultless Power Ride Through:
Over Voltage:
Input Current = 6 mA
18…24V = On, 0…6V = Off
0…6V = On, 18…24V = Off
Dynamic Braking
Environment
Control
Electrical
250 ohm input impedance
100k ohm input impedance
1…10k ohms, 2 Watt minimum
3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
30V DC, 50 mA
10-bit, 0…10V, 1k ohm minimum
0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Non-inductive
10 bit, 4…20 mA, 525 ohm maximum
UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
HMCP circuit breaker or equivalent.
I
2
t Overload Protection, 150% for 60 sec., 200% for 3 sec. (provides Class 10 protection)
200% hardware limit, 300% instantaneous fault
Minimum Ride Through is 0.5 sec. - typical value is 2 seconds
100 milliseconds
100…120V AC Input – Trip occurs at 405V DC bus voltage ( = 150V AC incoming line)
200…240V AC Input – Trip occurs at 405V DC bus voltage ( = 290V AC incoming line)
380…480V AC Input – Trip occurs at 810V DC bus voltage ( = 575V AC incoming line)
460…600V AC Input (PF 40) – Trip occurs at 1005V DC bus voltage ( = 711V AC incoming line)
Under Voltage:
100…120V AC Input – Trip occurs at 210V DC bus voltage ( = 75V AC incoming line)
200…240V AC Input – Trip occurs at 210V DC bus voltage ( = 150V AC incoming line)
380…480V AC Input – Trip occurs at 390V DC bus voltage ( = 275V AC incoming line)
460…600V AC Input (PF 40)
If P042 = 1 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);
If P042 = 0 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)
Internal brake IGBT included with all ratings except No Brake drives (Cat. Nos. 22A-AxPxN103 or 22A-AxPxN113). Refer to page 11 for ordering information.
1000 m (3300 ft.) maximum without derating
Altitude:
IP20, NEMA/UL Type Open: –10 to 50 degrees C (14 to 122 degrees F)
Ambient Operating Temperature:
IP30, NEMA/UL Type 1: –10 to 40 degrees C (14 to 104 degrees F)
IP66, NEMA/UL Type 4X/12 (PF 40): –10 to 40 degrees C (14 to 104 degrees F)
Fan, all drive ratings
Cooling Method:
–40 to 85 degrees C (–40 to 185 degrees F)
Storage Temperature:
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas,
Atmosphere:
vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock (operating):
15G peak for 11ms duration (±1.0ms)
Vibration (operating):
1G peak, 5 to 2000 Hz
2…16 kHz. Drive rating based on 4 kHz.
Carrier Frequency:
Digital Input: Within ±0.05% of set output frequency.
Frequency Accuracy:
Analog Input: Within 0.5% of maximum output frequency.
Analog Output (PF 40): ±2% of full scale, 10-bit resolution.
Open Loop with Slip Compensation: ±2% of base speed across a 40:1 speed range.
Speed Regulation:
(PF 40): 1% of base speed across a 60:1 speed range.
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.
Stop Modes:
Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1
Accel/Decel:
second increments.
150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds.
Intermittent Overload:
Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection
Electronic Motor Overload Protection:
according to NEC article 430.126 (A) (2). UL 508C File 29572.
120V, 200…240V, 380…480V, 460…600V: ±10%
Voltage Tolerance:
48…63 Hz
Frequency Tolerance:
0.98 across entire speed range
Displacement Power Factor:
100,000 Amps symmetrical
Maximum Short Circuit Rating:
Rockwell Automation Publication 22-TD001I-EN-P - June 201321
PowerFlex 4 and 40 AC Drives
Product Dimensions
Approximate Dimensions
A
D
C
F
EB
G
5.5 (0.22)
Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
Frame
A
B
C
A
80 (3.15)
100 (3.94)
130 (5.1)
B
(1)
152 (5.98)
180 (7.09)
260 (10.2)
C
136 (5.35)
136 (5.35)
180 (7.1)
D
67 (2.64)
87 (3.43)
116 (4.57)
E
140 (5.51
168 (6.61)
246 (9.7)
F
59.3 (2.33)
87.4 (3.44)
–
G
(2)
185 (7.28)
213 (8.39)
320 (12.6)
Shipping Weight
1.4 (3.1)
2.2 (4.9)
4.3 (9.5)
(1)Overall height of standard IP 20/Open Type Drive.
(2)Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed.
Ratings are in kW and (HP).
PowerFlex 4 — Frame
A
120V AC – 1-Phase
0.2 (0.25)
0.4(0.5)
240V AC – 1-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
240V AC – 3-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
240V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10.0)
480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
600V AC – 3-Phase
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
B0.75 (1.0)
1.1 (1.5)
120V AC – 1-Phase
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
PowerFlex 40 — Frame
B
240V AC – 1-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
C2.2 (3.0)
Shaded areas are applicable to PowerFlex 40 only.
Rockwell Automation Publication 22-TD001I-EN-P - June 201325
2024年7月31日发(作者:战兰娜)
PowerFlex 4 and 40 AC Drives
Product Overview
Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4 and
40 AC drives are the smallest and most cost-effective members of the PowerFlex® family of drives. Available in power ratings
from 0.2 to 11 kW (0.25 to 15 HP) and in voltage classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed
to meet global OEM and end-user demands for flexibility, space savings, ease of use and are cost-effective alternatives for
speed control of applications such as machine tools, fans, pumps and conveyors and material handling systems
Reference Materials
For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:
Title
PowerFlex 4 User Manual
PowerFlex 40 User Manual
Wiring and Grounding Guidelines for PWM AC Drives
Preventive Maintenance of Industrial Control and Drive System Equipment
Safety Guidelines for the Application, Installation and Maintenance of Solid State Control
Publication
22A-UM001
22B-UM001
DRIVES-IN001
DRIVES-TD001
SGI-1.1
Online
/literature
For other information, contact Allen-Bradley Drives Technical Support:
Title
Allen-Bradley Drives Technical Support
Online
/support/abdrives
Shaded areas are applicable to PowerFlex 40 only.
2Rockwell Automation Publication 22-TD001I-EN-P - June 2013
PowerFlex 4 and 40 AC Drives
Use the chart below to assist in determining which product is most appropriate for an application.
Feature
Catalog Reference22A
(1.1) 1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(3.7) 5 HP/230V, 3ø
(3.7) 5 HP/460V, 3ø
150% for 60 seconds
200% for 3 seconds
●
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●
●
●
●
V/Hz
●
Not available on no brake models.
4
2…16 kHz
Maximum (kW)HP Rating/Input Voltage
Overload Capacity
IP30, NEMA/UL Type 1 Option
IP66, NEMA/UL Type 4X/12 (Indoor)
EMC Filtering
DIN Rail Mounting Standard
Integral Keypad with Speed Pot
Keypad - Remote LCD
Keypad CopyCat Function
Control Type
Internal DB Transistor
Preset Speeds
Carrier Frequency
Skip Frequency
Process Control Loop
StepLogic Functionality
Timer/Counter Functions
Control Voltage
Discrete Inputs
Analog Input - Unipolar
Analog Input - Bipolar
Analog Response
Relay Output
Digital/Optocoupler Output
Analog Output
Integral RS485
RS232 (Requires use of Serial Converter Module)
BACnet
ControlNet
DeviceNet
EtherNet/IP
LonWorks
PROFIBUS DP
(1)With 22-XCOMM-DC-BASE External mounting kit.
(2)Frame B only.
(3)When using bipolar input, the 0…10V unipolar input cannot be used.
22B
(1.1) 1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(7.5) 10 HP/230V, 3ø
(11.0) 15 HP/460V, 3ø
(11.0) 15 HP/600V, 3ø
150% for 60 seconds
200% for 3 seconds
●
●
(2)
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●
(Through 5 HP)
●
●
●
Sensorless Vector & V/Hz
●
8
2…16 kHz
●
●
(PID)
●
●
24V sink/source
3 fixed for START/STOP/REV
4 fully programmable
2
(0…10V and 4…20 mA)
1
(+/- 10V)
(3)
100 Hz (10 ms)
1 - N.O./N.C. dry contact
2
●
(0…10V or 4…20 mA)
●
●
●
●
●
●
●
●
24V sink/source
3 fixed for START/STOP/REV
2 fully programmable
1
(0…10V or 4…20 mA)
2 Hz (500 ms)
1 - N.O/N.C. dry contact
●
●
●
(1)
●
(1)
●
(1)
●
(1)
●
(1)
●
(1)
Rockwell Automation Publication 22-TD001I-EN-P - June 20137
PowerFlex 4 and 40 AC Drives
Catalog Number Explanation
Position
1-3456-8910111213-14
22A
–
a
A
b
a
Drive
1P5
c
N
d
c4
Rating
1
e
1
f
4
g
e
HIM
Code
1
AA
h
Code
22A
22B
Type
PowerFlex 4
PowerFlex 40
Code
1P4
2P3
4P0
6P0
Ph.
1
1
3
3
3
010
012
017
024
380-480V Three-Phase Input
Amps
1.4
2.3
4.0
6.0
10.5
12
17
24
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
Interface Module
Fixed Keypad
f
Emission Class
Code
0
1
Rating
Not Filtered
Filtered
b
Voltage Rating
Code
V
A
B
D
E
Voltage
120V ac
240V ac
240V ac
480V ac
600V ac
g
Brake IGBT
Code
3
4
Description
Without Brake
With Brake
c5
Rating
460-600V Three-Phase Input
Code
1P7
3P0
4P2
6P6
9P9
012
019
Amps
1.7
3.0
4.2
6.6
9.9
12
19
kW (Hp)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)
c1
Rating
100-120V Single-Phase Input
Code
2P3
5P0
6P0
Amps
2.3
5.0
6.0
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
h
Optional
Code
AA through ZZ
Purpose
Reserved for custom
firmware
c2
Rating
200-240V Single-Phase Input
Code
2P3
5P0
8P0
012
Amps
2.3
5.0
8.0
12
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
d
Enclosure
Code
C
F
Enclosure
IP66, NEMA/UL Type 4X *
Flange Mount - IP20, NEMA/UL
Type Open
Replacement Plate Drive - IP20,
NEMA/UL Type Open
Contact factory for ordering
information.
Panel Mount - IP20, NEMA/UL Type
Open
* Check availability before ordering.
c3
Rating
200-240V Three-Phase Input
Code
2P3
5P0
8P0
012
017
024
033
Amps
2.3
5.0
8.0
12
17.5
24
33
kW (Hp)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10)
H
N
8Rockwell Automation Publication 22-TD001I-EN-P - June 2013
PowerFlex 4 and 40 AC Drives
Input/Output Ratings
Approvals
Control Inputs
Output Frequency:
Efficiency:
PowerFlex 4: 0…240 Hz (Programmable)
PowerFlex 40: 0…400 Hz (Programmable)
97.5% (Typical)
CSA C 22.2 No. 14EN 61800-3
LV Directive 73/23/EEC
LV: EN 50178, EN 60204
EMC Directive 89/336/EEC
EMC: EN 61800-3
U
L
UL508C
C
U
L
Control Output –
Programmable Output
(form C relay)
Fuses and Circuit Breakers
Protective Features
Digital
SRC (Source) Mode:
SNK (Sink) Mode:
Analog
4…20 mA Analog:
0…10V DC Analog:
External Pot:
Resistive Rating
Opto Outputs (PF 40):
Analog Outputs (PF 40):
Inductive Rating
Opto Outputs (PF 40):
Analog Outputs (PF 40):
Recommended Fuse Type:
Recommended Circuit Breakers:
Motor Protection:
Overcurrent:
Control Ride Through:
Faultless Power Ride Through:
Over Voltage:
Input Current = 6 mA
18…24V = On, 0…6V = Off
0…6V = On, 18…24V = Off
Dynamic Braking
Environment
Control
Electrical
250 ohm input impedance
100k ohm input impedance
1…10k ohms, 2 Watt minimum
3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
30V DC, 50 mA
10-bit, 0…10V, 1k ohm minimum
0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Non-inductive
10 bit, 4…20 mA, 525 ohm maximum
UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
HMCP circuit breaker or equivalent.
I
2
t Overload Protection, 150% for 60 sec., 200% for 3 sec. (provides Class 10 protection)
200% hardware limit, 300% instantaneous fault
Minimum Ride Through is 0.5 sec. - typical value is 2 seconds
100 milliseconds
100…120V AC Input – Trip occurs at 405V DC bus voltage ( = 150V AC incoming line)
200…240V AC Input – Trip occurs at 405V DC bus voltage ( = 290V AC incoming line)
380…480V AC Input – Trip occurs at 810V DC bus voltage ( = 575V AC incoming line)
460…600V AC Input (PF 40) – Trip occurs at 1005V DC bus voltage ( = 711V AC incoming line)
Under Voltage:
100…120V AC Input – Trip occurs at 210V DC bus voltage ( = 75V AC incoming line)
200…240V AC Input – Trip occurs at 210V DC bus voltage ( = 150V AC incoming line)
380…480V AC Input – Trip occurs at 390V DC bus voltage ( = 275V AC incoming line)
460…600V AC Input (PF 40)
If P042 = 1 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);
If P042 = 0 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)
Internal brake IGBT included with all ratings except No Brake drives (Cat. Nos. 22A-AxPxN103 or 22A-AxPxN113). Refer to page 11 for ordering information.
1000 m (3300 ft.) maximum without derating
Altitude:
IP20, NEMA/UL Type Open: –10 to 50 degrees C (14 to 122 degrees F)
Ambient Operating Temperature:
IP30, NEMA/UL Type 1: –10 to 40 degrees C (14 to 104 degrees F)
IP66, NEMA/UL Type 4X/12 (PF 40): –10 to 40 degrees C (14 to 104 degrees F)
Fan, all drive ratings
Cooling Method:
–40 to 85 degrees C (–40 to 185 degrees F)
Storage Temperature:
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas,
Atmosphere:
vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock (operating):
15G peak for 11ms duration (±1.0ms)
Vibration (operating):
1G peak, 5 to 2000 Hz
2…16 kHz. Drive rating based on 4 kHz.
Carrier Frequency:
Digital Input: Within ±0.05% of set output frequency.
Frequency Accuracy:
Analog Input: Within 0.5% of maximum output frequency.
Analog Output (PF 40): ±2% of full scale, 10-bit resolution.
Open Loop with Slip Compensation: ±2% of base speed across a 40:1 speed range.
Speed Regulation:
(PF 40): 1% of base speed across a 60:1 speed range.
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.
Stop Modes:
Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1
Accel/Decel:
second increments.
150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds.
Intermittent Overload:
Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection
Electronic Motor Overload Protection:
according to NEC article 430.126 (A) (2). UL 508C File 29572.
120V, 200…240V, 380…480V, 460…600V: ±10%
Voltage Tolerance:
48…63 Hz
Frequency Tolerance:
0.98 across entire speed range
Displacement Power Factor:
100,000 Amps symmetrical
Maximum Short Circuit Rating:
Rockwell Automation Publication 22-TD001I-EN-P - June 201321
PowerFlex 4 and 40 AC Drives
Product Dimensions
Approximate Dimensions
A
D
C
F
EB
G
5.5 (0.22)
Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
Frame
A
B
C
A
80 (3.15)
100 (3.94)
130 (5.1)
B
(1)
152 (5.98)
180 (7.09)
260 (10.2)
C
136 (5.35)
136 (5.35)
180 (7.1)
D
67 (2.64)
87 (3.43)
116 (4.57)
E
140 (5.51
168 (6.61)
246 (9.7)
F
59.3 (2.33)
87.4 (3.44)
–
G
(2)
185 (7.28)
213 (8.39)
320 (12.6)
Shipping Weight
1.4 (3.1)
2.2 (4.9)
4.3 (9.5)
(1)Overall height of standard IP 20/Open Type Drive.
(2)Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed.
Ratings are in kW and (HP).
PowerFlex 4 — Frame
A
120V AC – 1-Phase
0.2 (0.25)
0.4(0.5)
240V AC – 1-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
240V AC – 3-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
240V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10.0)
480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
600V AC – 3-Phase
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)
B0.75 (1.0)
1.1 (1.5)
120V AC – 1-Phase
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
PowerFlex 40 — Frame
B
240V AC – 1-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
C2.2 (3.0)
Shaded areas are applicable to PowerFlex 40 only.
Rockwell Automation Publication 22-TD001I-EN-P - June 201325