Operating Instructions

en

RDG100KN

RDG160KN

RDG100KN / RDG160KN – the room thermostat with KNX communications that allows you to set the

ideal room temperature you want. The thermostat provides Comfort, Economy and Protection mode.

In addition it can operate in Auto timer mode according to a schedule via KNX bus.

The fan operates either in Automatic mode or at the selected speed when using Manual mode.

You can either rely on the factory settings or make adjustments that suit your individual needs.

Main display

Room temperature

Operating mode

Heating mode

Electric heater active

Cooling mode

Comfort mode

Economy mode

Auto timer mode

Outdoor temperature

Room temperature in degrees

Celsius

Room temperature in degrees

Fahrenheit

Button lock active

Fault indicator *

Condensation in the room *

Timer function active

Weekday 1 = Monday

7 = Sunday

Additional user info, e.g.

current time of day

Escape (Cancel)

Confirm (OK)

Operating mode button

Fan mode button

Rotary knob

Protection mode:

Protection against frost

Indicator for mode selection

Fan mode

Automatic fan

Manual fan:

Low Medium High

* Needs to be configured by your HVAC installer

Changing the room temperature

 Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to decrease

the current room temperature setpoint. The thermostat changes to Comfort

.

The setting range is 40 °C; it can be limited by parameters P09 and P10.

(for parameter settings, see reverse side).

Adjusting the fan speed

 Press the right button repeatedly until the desired fan mode is reached.

 In Automatic mode , the fan speed is automatically selected by the thermostat

depending on the setpoint and the actual room temperature.

RDG100KN: When the room temperature reaches the setpoint, the fan keeps

running at low speed (factory setting).

RDG160KN: The fan stops (factory setting) or keeps running at low speed (P15).

 In Manual mode, the fan operates independently and always runs at the speed

you set: low / medium / high.

Note:

If desired, you can change the fan mode selector option via P03: Auto / manual, Manual only, or

Manual including Protection mode.

Low Medium High

Changing the operating mode of the thermostat

Press the operating mode button repeatedly until the

symbol points to the operating

mode you desire.

1. Protection mode

 In protection mode, the plant stops operating. However, if the room temperature

falls below 8 °C, heating is switched on to protect the room against frost.

The setpoints for Protection mode can be changed by your HVAC installer if desired:

Changes made by installer:  Frost protection: _________ ˚C Heat protection: __________˚C

2. Comfort mode

 In Comfort mode, the thermostat maintains

the room temperature on the setpoint

which can be adjusted with the rotary knob

3. Auto Timer mode

 In Auto Timer mode, the thermostat automatically switches over between Comfort

and Economy mode according to the schedule via KNX bus.

If no schedule via KNX is available, then Auto Timer is replaced by Comfort.

4. Economy mode

 In Economy mode, the thermostat maintains the room temperature at a lower or

higher setpoint, thus saving energy and money.

 The thermostat can be set to Economy mode either by pressing the operating

mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus

command) such as window switch, keycard or presence detector.

 The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.

They can be adjusted via parameters P11 and P12 (for parameter settings, see

reverse side).

Important: These setpoints can be set to OFF; which means that the thermostat

is not active., i.e. no protective heating or cooling function. Risk of frost!

Changing from heating to cooling mode

 The changeover from heating to cooling (or vice versa) is made

– either automatically by a changeover sensor, or a changeover switch, or a

remote changeover switch via KNX command

– or manually by pressing the operating mode button.

If the thermostat is configured for "heating only" or "Cooling only", changeover is

not available (see parameter P01)

 To select cooling or heating manually (P01=2), press the operating mode button

until the symbol points to the mode you desire.

 With automatic changeover or continuous heating / cooling, symbols

indicate that the system currently heats or cools.

indicate that the system currently  With manual changeover, symbols

indicate that the system operates in heating or cooling mode. Symbols

currently heats or cools.

Timer to extended presence or absence

The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the timer.

1. To set the timer, press and hold the operating mode button.

While holding the button, turn the rotary knob clockwise or counterclockwise as required.

a) Turn the rotary knob clockwise to extend Comfort mode.

0...+9:30 Display:

b) Turn the rotary knob counterclockwise to extend Economy mode.

Display:

0...–9:30

2. Release the operating mode button and the mode is temporarily changed, indicated by

symbol.

 After the temporary timer has elapsed, the thermostat will resume operation in the operating mode

according to schedule via bus (if available). Without schedule:

– when extended Comfort mode ends  new operating mode = Economy

– when extended Economy mode ends  new operating mode = Comfort

 If Economy mode cannot be selected via the operating mode button (P02 ≠ 2), Protection mode will

be used for extended absence instead.

 The temporary timer function is aborted whenever a new setting is made.

Temporary timer to extend the Comfort mode

When the operating mode is Economy (commanded by schedule via KNX or by en external signal. e.g.

keycard), it can be set back to Comfort temporarily by pressing the operating mode button.

The

symbol will appear.

Pressing the operating mode button again will stop the timer.

This function is only available when parameter P02 = 1. Duration: * P68 = 0...360 min, factory setting = 0 min.

* Needs to be configured by your HVAC installer.

Reminder clean filter and display of external faults

FIL *

AL1 *

AL2 *

AL3 *

This message reminds you to clean the filter on your HVAC equipment.

It will appear after  _______ "fan operating hours" and disappear when the thermo-

stat is set to Protection

These fault messages tell you an external fault has occurred *:

AL1 : _______________________

AL3 : _______________________

AL2 : __________________________

* Needs to be configured by your HVAC installer

Button lock

 If the button lock function is enabled (parameter P14 = 2), then pressing the

right button for 3 seconds

will lock or unlock the buttons respectively.

Locked buttons are indicated with the key symbol

 If "Auto lock" is configured (P14 = 1), the thermostat will automatically lock the

buttons 10 seconds after the last adjustment.

Commissioning (by qualified HVAC installer)

To adapt the thermostat to your system and optimize the control performance, a number of control

parameters can be adjusted. This can be done during operation, either via the buttons on the thermo-

stat or via a commissioning tool.

Control parameters

If you wish to change control parameters, proceed as follows:

1. Press left and right buttons simultaneously for at least 4 seconds.

2. Release them and, within 2 seconds, press the right button again until "P01" is displayed.

3. Select the required parameter by turning the rotary knob.

4. Press button

(OK). The current value of the selected parameter starts blinking and can be changed

by turning the rotary knob.

5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.

If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the

parameter setting mode.

Parameter list

No.

P01

Description

Control sequence

Default value

2-pipe / 2-stage:

1 = cooling only

Setting range

0 = Heating only

1 = Cooling only

2 = H/C changeover, manual

3 = H/C changeover, automatic

4 = Heating and cooling

1 = Auto** / Comfort / Protection

2 = Auto** / Comfort / Economy /

Protection

0 = Auto / Manual

1 = Manual

2 = Auto / Manual / Protection

0 = °C

1 = °F

-3...+3 °C

0 = Room temperature

1 = Setpoint

0 = No display

1 = Room Temperature in °C / °F

2 = Outside temperature (via bus)

3 = Time of day (12h, via bus)

4 = Time of day (24h, via bus)

5 ... 40 °C

5 ... 40 °C

5 ... 40 °C

OFF, 5 °C…WcoolEconomy

OFF, WheatEconomy…40 °C

OFF = Disabled

ON

= Enabled

0 = Disabled

1 = Automatic

2 = Manual

0 = Disabled

1 = Low speed (heating and cooling)

2 = Low speed (cooling only)

Adj. 

4-pipe:

4 = H and C

P02

P03

P04

P05

P06

P07

Mode selection via operating mode

button

Mode selection via fan mode button

Selection of °C or °F

Sensor calibration

Standard temperature display

Additional user information

1

0 = Auto / Manual

0 = °C

0.0 K

0 = Room temp.

0 = No display

P08

P09

P10

P11

P12

P13

***

P14

P15

Comfort basic setpoint

Minimum setpoint limitation in

Comfort mode

Maximum setpoint limitation in

Comfort mode

Setpoint for heating in Economy mode

(WheatEconomy)

Setpoint for cooling in Economy mode

(WcoolEconomy)

Electric heater in cooling mode

Button lock

Fan stage in dead zone (Comfort)

(RDG160KN only)

21 °C

5 °C

35 °C

15 °C

30 °C

ON

0 = Disabled

0 = Disabled

** When no time schedule via KNX exists, then Auto is equal to Comfort.

*** Parameter P13 is only displayed with application 2-pipe with el. heater.

All temperature settings can be made in increments of 0.5 °C.

 Please record all changes you make!

Siemens Building Technologies

Subject to change

CE1B3191en

2012-09-19

2024年10月18日发(作者:牧明哲)

s

Operating Instructions

en

RDG100KN

RDG160KN

RDG100KN / RDG160KN – the room thermostat with KNX communications that allows you to set the

ideal room temperature you want. The thermostat provides Comfort, Economy and Protection mode.

In addition it can operate in Auto timer mode according to a schedule via KNX bus.

The fan operates either in Automatic mode or at the selected speed when using Manual mode.

You can either rely on the factory settings or make adjustments that suit your individual needs.

Main display

Room temperature

Operating mode

Heating mode

Electric heater active

Cooling mode

Comfort mode

Economy mode

Auto timer mode

Outdoor temperature

Room temperature in degrees

Celsius

Room temperature in degrees

Fahrenheit

Button lock active

Fault indicator *

Condensation in the room *

Timer function active

Weekday 1 = Monday

7 = Sunday

Additional user info, e.g.

current time of day

Escape (Cancel)

Confirm (OK)

Operating mode button

Fan mode button

Rotary knob

Protection mode:

Protection against frost

Indicator for mode selection

Fan mode

Automatic fan

Manual fan:

Low Medium High

* Needs to be configured by your HVAC installer

Changing the room temperature

 Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to decrease

the current room temperature setpoint. The thermostat changes to Comfort

.

The setting range is 40 °C; it can be limited by parameters P09 and P10.

(for parameter settings, see reverse side).

Adjusting the fan speed

 Press the right button repeatedly until the desired fan mode is reached.

 In Automatic mode , the fan speed is automatically selected by the thermostat

depending on the setpoint and the actual room temperature.

RDG100KN: When the room temperature reaches the setpoint, the fan keeps

running at low speed (factory setting).

RDG160KN: The fan stops (factory setting) or keeps running at low speed (P15).

 In Manual mode, the fan operates independently and always runs at the speed

you set: low / medium / high.

Note:

If desired, you can change the fan mode selector option via P03: Auto / manual, Manual only, or

Manual including Protection mode.

Low Medium High

Changing the operating mode of the thermostat

Press the operating mode button repeatedly until the

symbol points to the operating

mode you desire.

1. Protection mode

 In protection mode, the plant stops operating. However, if the room temperature

falls below 8 °C, heating is switched on to protect the room against frost.

The setpoints for Protection mode can be changed by your HVAC installer if desired:

Changes made by installer:  Frost protection: _________ ˚C Heat protection: __________˚C

2. Comfort mode

 In Comfort mode, the thermostat maintains

the room temperature on the setpoint

which can be adjusted with the rotary knob

3. Auto Timer mode

 In Auto Timer mode, the thermostat automatically switches over between Comfort

and Economy mode according to the schedule via KNX bus.

If no schedule via KNX is available, then Auto Timer is replaced by Comfort.

4. Economy mode

 In Economy mode, the thermostat maintains the room temperature at a lower or

higher setpoint, thus saving energy and money.

 The thermostat can be set to Economy mode either by pressing the operating

mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus

command) such as window switch, keycard or presence detector.

 The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.

They can be adjusted via parameters P11 and P12 (for parameter settings, see

reverse side).

Important: These setpoints can be set to OFF; which means that the thermostat

is not active., i.e. no protective heating or cooling function. Risk of frost!

Changing from heating to cooling mode

 The changeover from heating to cooling (or vice versa) is made

– either automatically by a changeover sensor, or a changeover switch, or a

remote changeover switch via KNX command

– or manually by pressing the operating mode button.

If the thermostat is configured for "heating only" or "Cooling only", changeover is

not available (see parameter P01)

 To select cooling or heating manually (P01=2), press the operating mode button

until the symbol points to the mode you desire.

 With automatic changeover or continuous heating / cooling, symbols

indicate that the system currently heats or cools.

indicate that the system currently  With manual changeover, symbols

indicate that the system operates in heating or cooling mode. Symbols

currently heats or cools.

Timer to extended presence or absence

The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the timer.

1. To set the timer, press and hold the operating mode button.

While holding the button, turn the rotary knob clockwise or counterclockwise as required.

a) Turn the rotary knob clockwise to extend Comfort mode.

0...+9:30 Display:

b) Turn the rotary knob counterclockwise to extend Economy mode.

Display:

0...–9:30

2. Release the operating mode button and the mode is temporarily changed, indicated by

symbol.

 After the temporary timer has elapsed, the thermostat will resume operation in the operating mode

according to schedule via bus (if available). Without schedule:

– when extended Comfort mode ends  new operating mode = Economy

– when extended Economy mode ends  new operating mode = Comfort

 If Economy mode cannot be selected via the operating mode button (P02 ≠ 2), Protection mode will

be used for extended absence instead.

 The temporary timer function is aborted whenever a new setting is made.

Temporary timer to extend the Comfort mode

When the operating mode is Economy (commanded by schedule via KNX or by en external signal. e.g.

keycard), it can be set back to Comfort temporarily by pressing the operating mode button.

The

symbol will appear.

Pressing the operating mode button again will stop the timer.

This function is only available when parameter P02 = 1. Duration: * P68 = 0...360 min, factory setting = 0 min.

* Needs to be configured by your HVAC installer.

Reminder clean filter and display of external faults

FIL *

AL1 *

AL2 *

AL3 *

This message reminds you to clean the filter on your HVAC equipment.

It will appear after  _______ "fan operating hours" and disappear when the thermo-

stat is set to Protection

These fault messages tell you an external fault has occurred *:

AL1 : _______________________

AL3 : _______________________

AL2 : __________________________

* Needs to be configured by your HVAC installer

Button lock

 If the button lock function is enabled (parameter P14 = 2), then pressing the

right button for 3 seconds

will lock or unlock the buttons respectively.

Locked buttons are indicated with the key symbol

 If "Auto lock" is configured (P14 = 1), the thermostat will automatically lock the

buttons 10 seconds after the last adjustment.

Commissioning (by qualified HVAC installer)

To adapt the thermostat to your system and optimize the control performance, a number of control

parameters can be adjusted. This can be done during operation, either via the buttons on the thermo-

stat or via a commissioning tool.

Control parameters

If you wish to change control parameters, proceed as follows:

1. Press left and right buttons simultaneously for at least 4 seconds.

2. Release them and, within 2 seconds, press the right button again until "P01" is displayed.

3. Select the required parameter by turning the rotary knob.

4. Press button

(OK). The current value of the selected parameter starts blinking and can be changed

by turning the rotary knob.

5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.

If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the

parameter setting mode.

Parameter list

No.

P01

Description

Control sequence

Default value

2-pipe / 2-stage:

1 = cooling only

Setting range

0 = Heating only

1 = Cooling only

2 = H/C changeover, manual

3 = H/C changeover, automatic

4 = Heating and cooling

1 = Auto** / Comfort / Protection

2 = Auto** / Comfort / Economy /

Protection

0 = Auto / Manual

1 = Manual

2 = Auto / Manual / Protection

0 = °C

1 = °F

-3...+3 °C

0 = Room temperature

1 = Setpoint

0 = No display

1 = Room Temperature in °C / °F

2 = Outside temperature (via bus)

3 = Time of day (12h, via bus)

4 = Time of day (24h, via bus)

5 ... 40 °C

5 ... 40 °C

5 ... 40 °C

OFF, 5 °C…WcoolEconomy

OFF, WheatEconomy…40 °C

OFF = Disabled

ON

= Enabled

0 = Disabled

1 = Automatic

2 = Manual

0 = Disabled

1 = Low speed (heating and cooling)

2 = Low speed (cooling only)

Adj. 

4-pipe:

4 = H and C

P02

P03

P04

P05

P06

P07

Mode selection via operating mode

button

Mode selection via fan mode button

Selection of °C or °F

Sensor calibration

Standard temperature display

Additional user information

1

0 = Auto / Manual

0 = °C

0.0 K

0 = Room temp.

0 = No display

P08

P09

P10

P11

P12

P13

***

P14

P15

Comfort basic setpoint

Minimum setpoint limitation in

Comfort mode

Maximum setpoint limitation in

Comfort mode

Setpoint for heating in Economy mode

(WheatEconomy)

Setpoint for cooling in Economy mode

(WcoolEconomy)

Electric heater in cooling mode

Button lock

Fan stage in dead zone (Comfort)

(RDG160KN only)

21 °C

5 °C

35 °C

15 °C

30 °C

ON

0 = Disabled

0 = Disabled

** When no time schedule via KNX exists, then Auto is equal to Comfort.

*** Parameter P13 is only displayed with application 2-pipe with el. heater.

All temperature settings can be made in increments of 0.5 °C.

 Please record all changes you make!

Siemens Building Technologies

Subject to change

CE1B3191en

2012-09-19