最新消息: USBMI致力于为网友们分享Windows、安卓、IOS等主流手机系统相关的资讯以及评测、同时提供相关教程、应用、软件下载等服务。

JUMO safetyM TB TW 温度限制器与温度监控器说明书

IT圈 admin 86浏览 0评论

2024年10月18日发(作者:严含文)

JUMO GmbH & Co. KG

Delivery address:Mackenrodtstraße 14,

36039 Fulda, Germany

Postal address:36035 Fulda, Germany

Phone:+49 661 6003-0

Fax:+49 661 6003-607

e-mail:*************

Internet:

JUMO Instrument Co. Ltd.

JUMO House

Temple Bank, Riverway

Harlow, Essex CM 20 2TT, UK

Phone:+44 1279 635533

Fax:+44 1279 635262

e-mail:*************.uk

Internet:

JUMO Process Control, Inc.

8 Technology Boulevard

Canastota, NY 13032, USA

Phone:315-697-JUMO

1-800-554-JUMO

Fax:315-697-5867

e-mail:************

Internet:

Seite 1/8

JUMO safetyM TB/TW Temperature

limiter, temperature monitor

according DIN EN 14597

with LCD for mounting on 35mm DIN rails

Brief description

The JUMO safetyM TB/TW is a freely programmable temperature limiting device.

The measurement input is freely configurable for RTD temperature probes and thermocouples,

as well as for current and voltage signals.

TB/TWs monitor thermal processes in systems for a set limit value.

If this is exceeded, the

built-in relay (with internal fuse) switches the system to a safe operational state and the LED K1

switches from green to red.

When the system returns to the o.k. region, the reset button (on the TB) has to be released

manually using an appropriate tool.

The TW, on the other hand, is reset automatically without any external action.

The binary output 24V/20mA produces a pre-alarm signal at an adjustable temperature before

reaching the limit value, which is additionally indicated via the LED KV.

TB/TWs are mounted on DIN rails and wired up by means of screw terminals with 2.5mm²

max. conductor cross-section.

A PC setup program is available as an accessory, which can be used to set and store probe

type, range, output action and inhibits.

Typ 701160/ …

Block diagram

Special features

kSetup program for configuration and

archive data backup

kClear, easy-to-read alphanumerical display

kDigital input filter with adjustable

filter time constant

k adjustable as absolute value or relative to

limit value

kWide supply voltage range

110 — 240V AC +10% /-15%

kConfigurable as TB or TW

k17 linearizations can be set

kInternal and external locking options

kinput 2 x Pt100 for differential measure-

ment

Approval/approval marks

(see technical data)

2015-03-01/00506174

Technical data

Analog inputs

RTD temperature probe

Designation

Pt 100 EN 60751

KTY11-6 PTC

Pt 1000 DIN

connection types

Sampling

Input filter

Special features

thermocouples

Measuring range

-200…+850°C

-50...150°C

-200…+850°C

2-wire, 3-wire circuits

210ms

Accuracy

1

0.1%

1%

0.1%

2nd order digital filter; filter constant adjustable from 0to100secs

2x Pt100 for differential measurement, display can also be programmed in °F

Designation

Fe-CuNi "L" DIN 43710

Fe-CuNi "J" EN 60584

Cu-CuNi "U" DIN 43710

Cu-CuNi "T" EN 60584

NiCr-Ni "K" EN 60584

NiCrSi-NiSi "N" EN 60584

Pt10Rh-Pt "S" EN 60584

Pt13Rh-Pt "R" EN 60584

Pt30Rh-Pt6Rh "B" EN 60584

W3Re-W25Re "D"

Cold junction

Cold junction accuracy

Sampling rate

Input filter

Special features

Measuring range

-200to+900°C

-200to+1200°C

-200to+600°C

-200to+400°C

-200to+1372°C

-100to+1300°C

0to+1768°C

0to+1768°C

300to1820°C

0...2495°C

Pt 100, internal

± 1K

210 ms

Accuracy

1

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

2nd order digital filter; filter constant adjustable from 0to100secs

also programmable in °F

1. Accuracy refers to the maximum extent of the measuring range.

If the measuring range is smaller, the linearisation accuracy is reduced .

DC voltage, DC current

Measuring range

0to20mA, voltage drop < 2 V

4to20mA, voltage drop < 2 V

0to10V, input resistance > 100 kΩ

2to10V, input resistance > 100 kW

Scaling

Sampling rate

Input filter

Accuracy

0.2%

0.1%

freely programmable within the limits

210 ms

2nd order digital filter; filter constant adjustable from 0to100secs

Measuring circuit monitoring

RTD temperature probe

and KTY11-6

Twin thermocouplesThermocouplesCurrent 0 to 20 mA, 4 to 20mA

Voltage 0 to 10 V, 2 to 10 V

Overrange and un-is detected

derrangeLEDs K1 and KV light up; "1999" flashes in the display

Probe and lead breakis detected

LEDs K1 and KV light up; "1999" flashes in the display; relay K1 is active.

Probe short circuitis detected

LEDs K1 and KV light up;"1999" flashes in the display

Relay K1 is inactive

is not detected

is detected at 4 to 20mA

and 2 to 10V

LEDs K1 and KV light up;

"1999" flashes in the display

Relay K1 is inactive

2015-03-01/00506174

Binary input

connection

1 floating contact

Function

Configurable unlocking, keyboard inhibit, level inhibit

Relay- and Binary output

1 relay100000 operations at a contact rating of:

AC 230/24V; 3(0,5)A; cosφ=1 (≥ 0,6); 50Hz

DC 24V; 3(0,5; τ=7ms)A

UL60730

AC230V; 3A

D300; 30k

AC/DC 24V; 3A, minimum current: DC 24V, 100mA

Contact protection circuit:

safety fuse 3.15AT, installed in the pole contact arm within the instrument

24 V DC / 20mA logic signal, short-circuit proof1 Binary output

Voltage supply

voltage supply

Power consumption

20 - 30V AC/DC, 48 ...63 Hz

110V/240V AC, +10% /-15%

5 VA

Aapproval/Marks

approval

marks

DIN

c UL us

Inspection authority

DIN CERTCO

Certificate/Inspection

numbers

TW/TB 1206 08

inspection basics

DIN EN 14597

UL 60730-2-9

valid for

all instrument versions

all instrument versionsUnderwriters Laboratories20091123-E325456

Switching action at limit value

Switching action inverse

Switching action direct

2015-03-01/00506174

Switching action at differential measurement

Switching action inverse

Test voltages to EN 60730, Part 1

Between input or output and supply

- at 110-240 V AC supply +10% /-15%

- at 20 - 30V AC/DC supply, 48 - 63 Hz

3.7kV/50Hz

3.7kV/50Hz

Electrical safety

Clearances / creep paths

Mains to electronic components and probe

Mains to the relay

Relay to electronic components and probe

Electrical safety

Protection type I

6 mm

/ ≥

8 mm

6 mm

/ ≥

8 mm

6 mm

/ ≥

8 mm

according to DIN EN 14597 (DIN EN 60730-2-9)

Overvoltage category III, pollution degree 2

with internal separation to SELV current circuits

Environmental influences

Ambient temperature range

Storage temperature range

Temperature error

Climatic conditions

EMC

Interference emission

Interference immunity

details refer to the full scale value

0...+55°C

-30...+70°C

≤ ± 0.005% / K dev. from 23°C

1

for resistance thermometers

≤ ± 0.01% / K dev. from 23°C

1

for thermocouple, current, voltage

85% rel. humidity, no condensation

(3K3 with extended temperature range to EN 60721)

to EN 14597 and standards from the EN 61326 series of standards

Class B

Test level for safety, control and regulating instruments (RS) to EN 14597

Housing

Material

Screw terminal

Mounting

mounting position

Weight

Protection type

polyamide (PA 6.6)

0.2-2.5mm

2

screw terminal

on 35mmx7.5mm DIN rail to EN 60715

vertical

approx. 160g

IP 20 to EN 60529

2015-03-01/00506174

Dimensions

Type 701160/...

DIN-approved probes for operation in air

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

902006/65-228-1003-1-15-500-668/000

902006/65-228-1003-1-15-710-668/000

902006/65-228-1003-1-15-1000-668/000

902006/55-228-1003-1-15-500-254/000

902006/55-228-1003-1-15-710-254/000

902006/55-228-1003-1-15-1000-254/000

902006/65-228-2003-1-15-500-668/000

902006/65-228-2003-1-15-710-668/000

902006/65-228-2003-1-15-1000-668/000

902006/55-228-2003-1-15-500-254/000

902006/55-228-2003-1-15-710-254/000

902006/55-228-2003-1-15-1000-254/000

Thermocouples Data Sheet 90.1006

901006/65-547-2043-15-500-668/000

901006/65-547-2043-15-710-668/000

901006/65-547-2043-15-1000-668/000

901006/65-546-2042-15-500-668/000

901006/65-546-2042-15-710-668/000

901006/65-546-2042-15-1000-668/000

901006/66-550-2043-6-500-668/000

901006/66-550-2043-6-355-668/000

901006/66-550-2043-6-250-668/000

901006/66-880-1044-6-250-668/000

901006/66-880-1044-6-355-668/000

901006/66-880-1044-6-500-668/000

901006/66-880-2044-6-250-668/000

901006/66-880-2044-6-355-668/000

901006/66-880-2044-6-500-668/000

90.019-F01

90.020-F01

90.021-F01

90.019-F11

90.020-F11

90.021-F11

90.023-F01

90.023-F02

90.023-F03

90.021

90.022

90.023

90-D-021

90-D-022

90-D-023

2 x PT10Rh-PT, TypE „S“0 ... 1300°C

1 x PT10Rh-PT, TypE „S“0 ... 1300°C

2 x NiCr-Ni, TypE „K“-35 ... +1000°C

2 x Fe-CuNi, TypE „L“-35 ... +700°C

2 x NiCr-Ni, TypE „K“-35 ... +800°C

500

710

1000

500

710

1000

500

355

250

250

355

500

250

355

500

Stop flange,

movable

Stop flange,

movable

-

-

-

-

-

-

90.271-F01

90.272-F01

90.273-F01

-

-

-

2 x Pt100-170 ... +700°C

2 x Pt100-170 ... +700°C

1 x Pt100-170 ... +700°C

1 x Pt100-170 ... +700°C500

710

1000

500

710

1000

500

710

1000

500

710

1000

movable

G1/2 compression

clamp

Stop flange,

movable

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

901006/66-953-1046-6-250-668/000

901006/66-953-1046-6-355-668/000

901006/66-953-1046-6-500-668/000

901006/66-953-2046-6-250-668/000

901006/66-953-2046-6-355-668/000

901006/66-953-2046-6-500-668/000

90.027

90.028

90.029

90-D-027

90-D-028

90-D-029

1 x PT30Rh-PT6Rh, TypE „B“600 ... 1500°C250

355

500

2 x PT30Rh-PT6Rh, TypE „B“600 ... 1500°C250

355

500

2015-03-01/00506174

DIN-approved probes for operation in water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-402-1003-1-9-100-104/000

90.2006/10-402-2003-1-9-100-104/000

902006/54-227-2003-1-15-710-254/000

902006/54-227-1003-1-15-710-254/000

902006/10-226-1003-1-9-250-104/000

902006/10-226-2003-1-9-250-104/000

Thermocouples Data Sheet 90.1006

901006/54-544-2043-15-710-254/000

901006/54-544-1043-15-710-254/000

901006/54-544-2042-15-710-254/000

901006/54-544-1042-15-710-254/000

90.020-F02

90.020-F03

90.020-F12

90.020-F13

2 x NiCr-Ni, Type „K“

1 x NiCr-Ni, Type „K“

2 x FeCuNi, Type „L“

1 x FeCuNi, Type „L“

-35 ... 550°670

65...670

65...670

65...670

movable

G1/2 compression clamp

90.272-F02

90.272-F03

90.239

90-D-239

1 x Pt100

2 x Pt100

2 x Pt100

1 x Pt100

1 x Pt100

2 x Pt100

-170 ... 480°C

-170 ... 550°C

-40 ... +400°C100

100

65...670

65...670

250

250

movable

G1/2 compression clamp

G1/2 screw connection

G1/2 screw connection

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

DIN-approved probes for operation in water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-402-1003-1-9-100-104/000

90.2006/10-402-2003-1-9-100-104/000

902006/54-227-2003-1-15-710-254/000

902006/54-227-1003-1-15-710-254/000

902006/10-226-1003-1-9-250-104/000

902006/10-226-2003-1-9-250-104/000

Thermocouples Data Sheet 90.1006

901006/54-544-2043-15-710-254/000

901006/54-544-1043-15-710-254/000

901006/54-544-2042-15-710-254/000

901006/54-544-1042-15-710-254/000

90.020-F02

90.020-F03

90.020-F12

90.020-F13

2 x NiCr-Ni, Type „K“

1 x NiCr-Ni, Type „K“

2 x FeCuNi, Type „L“

1 x FeCuNi, Type „L“

-35 ... 550°670

65...670

65...670

65...670

movable

G1/2 compression clamp

90.272-F02

90.272-F03

90.239

90-D-239

1 x Pt100

2 x Pt100

2 x Pt100

1 x Pt100

1 x Pt100

2 x Pt100

-170 ... 480°C

-170 ... 550°C

-40 ... +400°C100

100

65...670

65...670

250

250

movable

G1/2 compression clamp

G1/2 screw connection

G1/2 screw connection

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

DIN-approved probes for operation air, water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-390-1003-1-8-250-104/000

Thermocouples Data Sheet 90.1006

901006/45-551-2043-2-xxxx-11-xxxx2 x NiCr-Ni, Typ

E „K“

max. 1

2024年10月18日发(作者:严含文)

JUMO GmbH & Co. KG

Delivery address:Mackenrodtstraße 14,

36039 Fulda, Germany

Postal address:36035 Fulda, Germany

Phone:+49 661 6003-0

Fax:+49 661 6003-607

e-mail:*************

Internet:

JUMO Instrument Co. Ltd.

JUMO House

Temple Bank, Riverway

Harlow, Essex CM 20 2TT, UK

Phone:+44 1279 635533

Fax:+44 1279 635262

e-mail:*************.uk

Internet:

JUMO Process Control, Inc.

8 Technology Boulevard

Canastota, NY 13032, USA

Phone:315-697-JUMO

1-800-554-JUMO

Fax:315-697-5867

e-mail:************

Internet:

Seite 1/8

JUMO safetyM TB/TW Temperature

limiter, temperature monitor

according DIN EN 14597

with LCD for mounting on 35mm DIN rails

Brief description

The JUMO safetyM TB/TW is a freely programmable temperature limiting device.

The measurement input is freely configurable for RTD temperature probes and thermocouples,

as well as for current and voltage signals.

TB/TWs monitor thermal processes in systems for a set limit value.

If this is exceeded, the

built-in relay (with internal fuse) switches the system to a safe operational state and the LED K1

switches from green to red.

When the system returns to the o.k. region, the reset button (on the TB) has to be released

manually using an appropriate tool.

The TW, on the other hand, is reset automatically without any external action.

The binary output 24V/20mA produces a pre-alarm signal at an adjustable temperature before

reaching the limit value, which is additionally indicated via the LED KV.

TB/TWs are mounted on DIN rails and wired up by means of screw terminals with 2.5mm²

max. conductor cross-section.

A PC setup program is available as an accessory, which can be used to set and store probe

type, range, output action and inhibits.

Typ 701160/ …

Block diagram

Special features

kSetup program for configuration and

archive data backup

kClear, easy-to-read alphanumerical display

kDigital input filter with adjustable

filter time constant

k adjustable as absolute value or relative to

limit value

kWide supply voltage range

110 — 240V AC +10% /-15%

kConfigurable as TB or TW

k17 linearizations can be set

kInternal and external locking options

kinput 2 x Pt100 for differential measure-

ment

Approval/approval marks

(see technical data)

2015-03-01/00506174

Technical data

Analog inputs

RTD temperature probe

Designation

Pt 100 EN 60751

KTY11-6 PTC

Pt 1000 DIN

connection types

Sampling

Input filter

Special features

thermocouples

Measuring range

-200…+850°C

-50...150°C

-200…+850°C

2-wire, 3-wire circuits

210ms

Accuracy

1

0.1%

1%

0.1%

2nd order digital filter; filter constant adjustable from 0to100secs

2x Pt100 for differential measurement, display can also be programmed in °F

Designation

Fe-CuNi "L" DIN 43710

Fe-CuNi "J" EN 60584

Cu-CuNi "U" DIN 43710

Cu-CuNi "T" EN 60584

NiCr-Ni "K" EN 60584

NiCrSi-NiSi "N" EN 60584

Pt10Rh-Pt "S" EN 60584

Pt13Rh-Pt "R" EN 60584

Pt30Rh-Pt6Rh "B" EN 60584

W3Re-W25Re "D"

Cold junction

Cold junction accuracy

Sampling rate

Input filter

Special features

Measuring range

-200to+900°C

-200to+1200°C

-200to+600°C

-200to+400°C

-200to+1372°C

-100to+1300°C

0to+1768°C

0to+1768°C

300to1820°C

0...2495°C

Pt 100, internal

± 1K

210 ms

Accuracy

1

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

0.4%

2nd order digital filter; filter constant adjustable from 0to100secs

also programmable in °F

1. Accuracy refers to the maximum extent of the measuring range.

If the measuring range is smaller, the linearisation accuracy is reduced .

DC voltage, DC current

Measuring range

0to20mA, voltage drop < 2 V

4to20mA, voltage drop < 2 V

0to10V, input resistance > 100 kΩ

2to10V, input resistance > 100 kW

Scaling

Sampling rate

Input filter

Accuracy

0.2%

0.1%

freely programmable within the limits

210 ms

2nd order digital filter; filter constant adjustable from 0to100secs

Measuring circuit monitoring

RTD temperature probe

and KTY11-6

Twin thermocouplesThermocouplesCurrent 0 to 20 mA, 4 to 20mA

Voltage 0 to 10 V, 2 to 10 V

Overrange and un-is detected

derrangeLEDs K1 and KV light up; "1999" flashes in the display

Probe and lead breakis detected

LEDs K1 and KV light up; "1999" flashes in the display; relay K1 is active.

Probe short circuitis detected

LEDs K1 and KV light up;"1999" flashes in the display

Relay K1 is inactive

is not detected

is detected at 4 to 20mA

and 2 to 10V

LEDs K1 and KV light up;

"1999" flashes in the display

Relay K1 is inactive

2015-03-01/00506174

Binary input

connection

1 floating contact

Function

Configurable unlocking, keyboard inhibit, level inhibit

Relay- and Binary output

1 relay100000 operations at a contact rating of:

AC 230/24V; 3(0,5)A; cosφ=1 (≥ 0,6); 50Hz

DC 24V; 3(0,5; τ=7ms)A

UL60730

AC230V; 3A

D300; 30k

AC/DC 24V; 3A, minimum current: DC 24V, 100mA

Contact protection circuit:

safety fuse 3.15AT, installed in the pole contact arm within the instrument

24 V DC / 20mA logic signal, short-circuit proof1 Binary output

Voltage supply

voltage supply

Power consumption

20 - 30V AC/DC, 48 ...63 Hz

110V/240V AC, +10% /-15%

5 VA

Aapproval/Marks

approval

marks

DIN

c UL us

Inspection authority

DIN CERTCO

Certificate/Inspection

numbers

TW/TB 1206 08

inspection basics

DIN EN 14597

UL 60730-2-9

valid for

all instrument versions

all instrument versionsUnderwriters Laboratories20091123-E325456

Switching action at limit value

Switching action inverse

Switching action direct

2015-03-01/00506174

Switching action at differential measurement

Switching action inverse

Test voltages to EN 60730, Part 1

Between input or output and supply

- at 110-240 V AC supply +10% /-15%

- at 20 - 30V AC/DC supply, 48 - 63 Hz

3.7kV/50Hz

3.7kV/50Hz

Electrical safety

Clearances / creep paths

Mains to electronic components and probe

Mains to the relay

Relay to electronic components and probe

Electrical safety

Protection type I

6 mm

/ ≥

8 mm

6 mm

/ ≥

8 mm

6 mm

/ ≥

8 mm

according to DIN EN 14597 (DIN EN 60730-2-9)

Overvoltage category III, pollution degree 2

with internal separation to SELV current circuits

Environmental influences

Ambient temperature range

Storage temperature range

Temperature error

Climatic conditions

EMC

Interference emission

Interference immunity

details refer to the full scale value

0...+55°C

-30...+70°C

≤ ± 0.005% / K dev. from 23°C

1

for resistance thermometers

≤ ± 0.01% / K dev. from 23°C

1

for thermocouple, current, voltage

85% rel. humidity, no condensation

(3K3 with extended temperature range to EN 60721)

to EN 14597 and standards from the EN 61326 series of standards

Class B

Test level for safety, control and regulating instruments (RS) to EN 14597

Housing

Material

Screw terminal

Mounting

mounting position

Weight

Protection type

polyamide (PA 6.6)

0.2-2.5mm

2

screw terminal

on 35mmx7.5mm DIN rail to EN 60715

vertical

approx. 160g

IP 20 to EN 60529

2015-03-01/00506174

Dimensions

Type 701160/...

DIN-approved probes for operation in air

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

902006/65-228-1003-1-15-500-668/000

902006/65-228-1003-1-15-710-668/000

902006/65-228-1003-1-15-1000-668/000

902006/55-228-1003-1-15-500-254/000

902006/55-228-1003-1-15-710-254/000

902006/55-228-1003-1-15-1000-254/000

902006/65-228-2003-1-15-500-668/000

902006/65-228-2003-1-15-710-668/000

902006/65-228-2003-1-15-1000-668/000

902006/55-228-2003-1-15-500-254/000

902006/55-228-2003-1-15-710-254/000

902006/55-228-2003-1-15-1000-254/000

Thermocouples Data Sheet 90.1006

901006/65-547-2043-15-500-668/000

901006/65-547-2043-15-710-668/000

901006/65-547-2043-15-1000-668/000

901006/65-546-2042-15-500-668/000

901006/65-546-2042-15-710-668/000

901006/65-546-2042-15-1000-668/000

901006/66-550-2043-6-500-668/000

901006/66-550-2043-6-355-668/000

901006/66-550-2043-6-250-668/000

901006/66-880-1044-6-250-668/000

901006/66-880-1044-6-355-668/000

901006/66-880-1044-6-500-668/000

901006/66-880-2044-6-250-668/000

901006/66-880-2044-6-355-668/000

901006/66-880-2044-6-500-668/000

90.019-F01

90.020-F01

90.021-F01

90.019-F11

90.020-F11

90.021-F11

90.023-F01

90.023-F02

90.023-F03

90.021

90.022

90.023

90-D-021

90-D-022

90-D-023

2 x PT10Rh-PT, TypE „S“0 ... 1300°C

1 x PT10Rh-PT, TypE „S“0 ... 1300°C

2 x NiCr-Ni, TypE „K“-35 ... +1000°C

2 x Fe-CuNi, TypE „L“-35 ... +700°C

2 x NiCr-Ni, TypE „K“-35 ... +800°C

500

710

1000

500

710

1000

500

355

250

250

355

500

250

355

500

Stop flange,

movable

Stop flange,

movable

-

-

-

-

-

-

90.271-F01

90.272-F01

90.273-F01

-

-

-

2 x Pt100-170 ... +700°C

2 x Pt100-170 ... +700°C

1 x Pt100-170 ... +700°C

1 x Pt100-170 ... +700°C500

710

1000

500

710

1000

500

710

1000

500

710

1000

movable

G1/2 compression

clamp

Stop flange,

movable

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

901006/66-953-1046-6-250-668/000

901006/66-953-1046-6-355-668/000

901006/66-953-1046-6-500-668/000

901006/66-953-2046-6-250-668/000

901006/66-953-2046-6-355-668/000

901006/66-953-2046-6-500-668/000

90.027

90.028

90.029

90-D-027

90-D-028

90-D-029

1 x PT30Rh-PT6Rh, TypE „B“600 ... 1500°C250

355

500

2 x PT30Rh-PT6Rh, TypE „B“600 ... 1500°C250

355

500

2015-03-01/00506174

DIN-approved probes for operation in water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-402-1003-1-9-100-104/000

90.2006/10-402-2003-1-9-100-104/000

902006/54-227-2003-1-15-710-254/000

902006/54-227-1003-1-15-710-254/000

902006/10-226-1003-1-9-250-104/000

902006/10-226-2003-1-9-250-104/000

Thermocouples Data Sheet 90.1006

901006/54-544-2043-15-710-254/000

901006/54-544-1043-15-710-254/000

901006/54-544-2042-15-710-254/000

901006/54-544-1042-15-710-254/000

90.020-F02

90.020-F03

90.020-F12

90.020-F13

2 x NiCr-Ni, Type „K“

1 x NiCr-Ni, Type „K“

2 x FeCuNi, Type „L“

1 x FeCuNi, Type „L“

-35 ... 550°670

65...670

65...670

65...670

movable

G1/2 compression clamp

90.272-F02

90.272-F03

90.239

90-D-239

1 x Pt100

2 x Pt100

2 x Pt100

1 x Pt100

1 x Pt100

2 x Pt100

-170 ... 480°C

-170 ... 550°C

-40 ... +400°C100

100

65...670

65...670

250

250

movable

G1/2 compression clamp

G1/2 screw connection

G1/2 screw connection

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

DIN-approved probes for operation in water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-402-1003-1-9-100-104/000

90.2006/10-402-2003-1-9-100-104/000

902006/54-227-2003-1-15-710-254/000

902006/54-227-1003-1-15-710-254/000

902006/10-226-1003-1-9-250-104/000

902006/10-226-2003-1-9-250-104/000

Thermocouples Data Sheet 90.1006

901006/54-544-2043-15-710-254/000

901006/54-544-1043-15-710-254/000

901006/54-544-2042-15-710-254/000

901006/54-544-1042-15-710-254/000

90.020-F02

90.020-F03

90.020-F12

90.020-F13

2 x NiCr-Ni, Type „K“

1 x NiCr-Ni, Type „K“

2 x FeCuNi, Type „L“

1 x FeCuNi, Type „L“

-35 ... 550°670

65...670

65...670

65...670

movable

G1/2 compression clamp

90.272-F02

90.272-F03

90.239

90-D-239

1 x Pt100

2 x Pt100

2 x Pt100

1 x Pt100

1 x Pt100

2 x Pt100

-170 ... 480°C

-170 ... 550°C

-40 ... +400°C100

100

65...670

65...670

250

250

movable

G1/2 compression clamp

G1/2 screw connection

G1/2 screw connection

Old type

designation

Probe typeTemperature rangeNom. length mm

P

rocess connection

DIN-approved probes for operation air, water and oil

Note: Because of the high response accuracy, the use of thermowells (pockets) is not admissible.

Actual type designation

RTD temperature probe Data Sheet 90.2006

90.2006/10-390-1003-1-8-250-104/000

Thermocouples Data Sheet 90.1006

901006/45-551-2043-2-xxxx-11-xxxx2 x NiCr-Ni, Typ

E „K“

max. 1